32
No. Symptom
Indication
Abnormal point /
Condition
Condition Correspondence
LED1 (Red)
LED2
(Yellow)
20
Outdoor unit
operates.
Once Lighting
Primary current protection The input current exceeds 15 A.
These symptoms do not mean any ab-
normality of the product, but check the
following points.
• Check if indoor
fi
lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circu-
lation is short cycled.
Secondary current protec-
tion
The current of the compressor exceeds 15 A.
21
Twice Lighting
High-pressure protection The indoor gas pipe temperature exceeds 45°C during heating.
Defrosting in cooling
The indoor gas pipe temperature falls 3°C or below during cooling.
22
3 times
Lighting
Discharge temperature
protection
The discharge temperature exceeds 100°C during operation.
• Check refrigerant circuit and refriger-
ant amount.
• Refer to 9-5
. "Check of LEV".
• Refer to 9-5
. "Check of outdoor
thermistors".
23
4 times
Lighting Low discharge tempera-
ture protection
The frequency of the compressor is kept 80 Hz or more and the dis-
charge temperature is kept under 39°C for more than 20 minutes.
• Refer to 9-5
. "Check of LEV".
• Check refrigerant circuit and refriger-
ant amount.
24
5 times
Lighting
Cooling high-pressure
protection
The outdoor heat exchanger temperature exceeds 58°C during op-
eration.
This symptom does not mean any ab-
normality of the product, but check the
following points.
• Check if indoor
fi
lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circu-
lation is short cycled.
25
Outdoor unit
operates
9 times
Lighting
Inverter check mode
The unit is operated with emergency operation switch.
-
26
Lighting Lighting
Normal -
-
Summary of Contents for Mr.Slim MUZ-GC25NA - C1