MSZ-GE-6
2013 M-Series - MSZ-GE Heat Pump Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
Due to continuing improvement, above specification may be subject to change without notice.
3-1. SPECIFICATIONS
Model name
MSZ-GE24NA
Power supply
V, phase, Hz
208/230, 1, 60
Max. fuse size (time delay)/ Disconnect switch
A
20
Min. circuit ampacity
A
1.0
Blower Motor (ECM)
F.L.A
0.76
Airflow
Super High - High - Med. -
Low - Quiet
COOL Dry
(Wet)
CFM
738-628-469-388
(661-562-420-347)
HEAT Dry
CFM
406-321-237-170-145
Moisture removal
pt./h
5.1
Sensible Heat Factor
0.75
Sound level
Super High - High - Med. -
Low - Quiet
Cooling
dB(A)
53-49-41-34
Heating
dB(A)
52-49-41-32
Cond. drain connection O.D.
in.
5/8
Dimensions
W
in.
43-5/16
D
9-3/8
H
12-13/16
Weight
Ib.
37
External finish
Munsell 1.0Y 9.2/0.2
Control voltage (by built-in transformer)
12 - 24 VDC
NOTE
: Test conditions are based on ARI 210/240.
1: Rating conditions (Cooling) — Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB) Rated frequency
(Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB Rated frequency
2:
(Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB
Maximum frequency
MSZ-GE24NA