MSZ-GE-36

2013 M-Series - MSZ-GE Heat Pump Systems (June 2013)

© 2013 Mitsubishi Electric US, Inc.

Due to continuing improvement, above specification may be subject to change without notice.

3-9. CAPACITY CORRECTION TABLE BY REFRIGERANT PIPING LENGTH

Refrigerant piping length (ft)

25(std)

40

65

100

1.000

0.954

0.878

0.771

(3) M-SERIES PIPING CORRECTION COOLING

Refrigerant piping length (ft)

25(std)

40

65

100

1.000

0.989

0.972

0.955

(4) M-SERIES PIPING CORRECTION HEATING

Summary of Contents for Mr. Slim MSZ-GE06NA-8

Page 1: ...l Dimensions MSZ GE 11 3 3 Center of Gravity MSZ GE 16 3 4 Electrical Wiring Diagrams MSZ GE 17 3 5 Refrigerant System Diagrams MSZ GE 23 3 6 Capacity Correction Curve by Temperature MSZ GE 28 3 7 Capacity Correction Table by Temperature MSZ GE 30 3 8 Capacity Correction Curve by Refrigerant Piping Length MSZ GE 34 3 9 Capacity Correction Table by Refrigerant Piping Length MSZ GE 35 3 10 Charge Ca...

Page 2: ...Electric US Inc Due to continuing improvement above specification may be subject to change without notice 1 INDOOR UNITS MSZ GE06NA 8 MSZ GE09NA 8 MSZ GE12NA 8 MSZ GE15NA 8 MSZ GE18NA 8 MSZ GE24NA The MSZ GE06NA 8 is only compatible with the multi split MXZ heat pump systems ...

Page 3: ...Pump Systems June 2013 MSZ GE 3 2013 Mitsubishi Electric US Inc Due to continuing improvement above specification may be subject to change without notice 2 OUTDOOR UNITS MUY GE09NA MUY GE12NA MUY GE15NA 1 MUY GE18NA 1 MUY GE24NA ...

Page 4: ...ties Quiet operation Updated sleek compact indoor unit design Integrated i see Sensor automatically adjusts the unit s operation according to the temperature differences detected between the floor and the intake air ensuring optimum comfort and energy usage Base heater is available as an option Auto fan speed control Quiet Low Medium High and Super High Hand held Wireless Remote Controller Advance...

Page 5: ...n 31 7 16 D 9 1 8 H 11 5 8 Weight Ib 22 External finish Munsell 1 0Y 9 2 0 2 Control voltage by built in transformer 12 24 VDC Model name MSZ GE15NA 8 MSZ GE18NA 8 Power supply V phase Hz 208 230 1 60 Max fuse size time delay Disconnect switch A 15 Min circuit ampacity A 1 0 Blower Motor ECM F L A 0 76 Airflow Super High High Med Low Quiet COOL Dry Wet CFM 533 420 335 272 205 498 385 300 237 170 5...

Page 6: ...420 347 HEAT Dry CFM 406 321 237 170 145 Moisture removal pt h 5 1 Sensible Heat Factor 0 75 Sound level Super High High Med Low Quiet Cooling dB A 53 49 41 34 Heating dB A 52 49 41 32 Cond drain connection O D in 5 8 Dimensions W in 43 5 16 D 9 3 8 H 12 13 16 Weight Ib 37 External finish Munsell 1 0Y 9 2 0 2 Control voltage by built in transformer 12 24 VDC NOTE Test conditions are based on ARI 2...

Page 7: ...A 0 50 Compressor Model KNB073FQDHC KNB092FQAHC R L A 6 6 6 6 L R A 8 2 8 2 Refrigeration oil cc Model 320 NEO22 Refrigerant control Linear expansion valve Sound level 1 Cooling dB A 46 49 Heating dB A 50 51 Defrost method Reverse cycle Dimensions W in 31 1 2 D in 11 1 4 H in 21 5 8 Weight Ib 66 77 External finish Munsell 3Y 7 8 1 1 Remote controller Wireless type Control voltage by built in trans...

Page 8: ... 50 0 93 Compressor Model SNB130FQBH R L A 7 4 10 0 L R A 9 3 12 5 Refrigeration oil cc Model 450 NEO22 Refrigerant control Linear expansion valve Sound level 1 Cooling dB A 49 54 Heating dB A 51 56 Defrost method Reverse cycle Dimensions W in 31 1 2 33 1 16 D in 11 1 4 13 H in 21 5 8 33 7 16 Weight Ib 80 119 External finish Munsell 3Y 7 8 1 1 Remote controller Wireless type Control voltage by bui...

Page 9: ... SNB172FQKMT R L A 12 9 L R A 16 1 Refrigeration oil cc Model 0 40 FV50S Refrigerant control Linear expansion valve Sound level 1 Cooling dB A 55 Heating dB A 55 Defrost method Reverse Cycle Dimensions W in 33 1 16 D in 13 H in 34 5 8 Weight Ib 119 External finish Munsell 3Y 7 8 1 1 Remote controller Wireless type Control voltage by built in transformer VDC 12 24 Refrigerant piping Not supplied Re...

Page 10: ...t Indoor Unit SEER EER HSPF COP 47 F COP 17 F Energy Star Tax Credit Most Efficient WALL MOUNT HEAT PUMP MUZ GE09NA MSZ GE09NA 8 21 13 6 10 4 2 2 76 Yes Yes Yes MUZ GE12NA MSZ GE12NA 8 20 25 12 5 10 3 6 2 86 Yes Yes Yes MUZ GE15NA 1 MSZ GE15NA 8 21 13 10 3 3 2 88 Yes Yes Yes MUZ GE18NA 1 MSZ GE18NA 8 19 2 10 5 10 3 32 2 7 MUZ GE24NA MSZ GE24NA 19 12 5 10 3 46 2 64 Yes Yes Note Efficiency values ba...

Page 11: ...8 MSZ GE18NA 8 8 5 16 9 1 8 9 15 16 7 8 6 1 8 6 1 8 3 1 8 3 1 8 8 7 8 8 7 8 1 8 3 4 6 1 4 2 5 16 3 16 9 1 8 2 3 16 2 3 4 31 7 16 30 15 16 1 4 5 1 8 24 3 8 1 15 16 11 5 8 1 15 16 1 5 8 2 3 16 1 11 16 1 5 8 5 16 3 15 16 4 3 16 4 3 8 1 3 4 2 3 16 2 11 16 13 5 16 2 3 8 8 3 8 10 1 5 8 1 5 8 13 9 16 2 1 8 7 16 1 Oblong hole 7 16 13 16 Oblong hole Installation plate Indoor unit Wall hole ø2 9 16 Air in A...

Page 12: ... MSZ GE24NA 10 1 4 6 1 4 3 4 2 5 16 1 7 8 5 16 12 3 8 10 1 16 1 7 8 1 8 3 7 8 6 13 16 3 7 8 6 13 16 16 5 16 16 5 16 3 16 9 15 16 31 1 8 2 3 16 42 1 16 43 5 16 12 13 16 Air out Air in Insulation ø 1 1 8 Drain hose ø 5 8 Connected part O D Installation plate Wall hole ø 3 Wireless remote controller Installation plate Indoor unit Liquid line ø 1 4 19 11 16 Gas line ø 5 8 16 15 16 Insulation ø 1 15 16...

Page 13: ...flared GE15 6 23 32 2 5 7 8 2 23 32 1 3 4 15 3 4 12 12 3 4 13 9 16 11 16 1 9 16 7 8 21 5 8 11 1 32 13 32 31 1 2 19 11 16 5 15 16 11 29 32 17 32 29 32 11 1 4 Air in handle Air in Air out 2 3 8 13 16 Oval hole Drain hole 1 5 8 REQUIRED SPACE Basically open 4 inch or more without any obstruction in front and on both sides of the unit 1 4 i n o r m o r e 8 i n o r m o r e 4 i n o r m o r e 4 i n o r m...

Page 14: ...out 19 11 16 33 1 16 13 2 4 25 32 33 7 16 16 15 16 3 3 16 4 3 8 13 16 slot 1 11 32 1 9 16 Drain 3 holes ø1 5 16 3 0 3 5 2 9 16 Liquid 1 4 flared Gas 1 2 flared 3 9 16 8 11 32 Open as a rule 20 inch or more if the front and both sides are open 4 inch or more 8 inch or more if there are obstacles to both sides Open as a rule 20 inch or more if the back both sides and top are open REQUIRED SPACE 1 4 ...

Page 15: ... 25 32 33 1 16 Open as a rule 20 inch or more if the front and both sides are open 4 inch or more 8 inch or more if there are obstacles to both sides Open as a rule 20 inch or more if the back both sides and top are open 1 4 i n o r m o r e 4 i n o r m o r e Air in Air out 13 Service panel Gas refrigerant pipe joint Refrigerant pipe flared ø5 8 Liquid refrigerant pipe joint Refrigerant pipe flared...

Page 16: ...Z GE18NA 8 13 7 16 340 3 3 4 95 7 1 2 190 31 7 16 798 9 1 8 232 11 5 8 295 MSZ GE24NA 17 11 16 450 4 5 16 110 6 5 16 160 42 1 16 1100 10 1 4 261 12 13 16 325 Unit inch mm Model name A B C a b c MUZ GE09NA MUZ GE12NA MUZ GE15NA 1 11 1 16 280 5 9 16 140 9 1 2 240 31 1 2 800 11 1 4 285 21 5 8 550 MUZ GE18NA 1 11 13 16 300 5 7 8 150 13 3 8 340 33 1 16 840 13 330 33 7 16 850 MUZ GE24NA MSZ GE09NA 8 MSZ...

Page 17: ...Systems June 2013 MSZ GE 17 2013 Mitsubishi Electric US Inc Due to continuing improvement above specification may be subject to change without notice 3 4 ELECTRICAL WIRING DIAGRAMS MSZ GE09NA 8 MSZ GE12NA 8 MSZ GE15NA 8 MSZ GE18NA 8 ...

Page 18: ...es MSZ GE Heat Pump Systems June 2013 2013 Mitsubishi Electric US Inc Due to continuing improvement above specification may be subject to change without notice 3 4 ELECTRICAL WIRING DIAGRAMS MSZ GE24NA MSZ GE24NA MSY GE24NA ...

Page 19: ...Z GE Heat Pump Systems June 2013 MSZ GE 19 2013 Mitsubishi Electric US Inc Due to continuing improvement above specification may be subject to change without notice 3 4 ELECTRICAL WIRING DIAGRAMS MUZ GE09NA MUZ GE12NA ...

Page 20: ...ries MSZ GE Heat Pump Systems June 2013 2013 Mitsubishi Electric US Inc Due to continuing improvement above specification may be subject to change without notice 3 4 ELECTRICAL WIRING DIAGRAMS MUZ GE15NA 1 11 MUZ GE15NA 1 ...

Page 21: ...E Heat Pump Systems June 2013 MSZ GE 21 2013 Mitsubishi Electric US Inc Due to continuing improvement above specification may be subject to change without notice 3 4 ELECTRICAL WIRING DIAGRAMS MUZ GE18NA 1 13 MUZ GE18NA 1 ...

Page 22: ...2013 M Series MSZ GE Heat Pump Systems June 2013 2013 Mitsubishi Electric US Inc Due to continuing improvement above specification may be subject to change without notice 3 4 ELECTRICAL WIRING DIAGRAMS MUZ GE24NA ...

Page 23: ...MSY GE09 12NA ø1 2 MSZ GE15 18NA MSY GE15 18NA with heat insulator Refrigerant pipe ø1 4 with heat insulator Indoor coil thermistor RT12 main Indoor coil thermistor RT13 sub Refrigerant flow in cooling Refrigerant flow in heating Indoor heat exchanger Room temperature thermistor RT11 Refrigerant pipe ø5 8 with heat insulator Flared connection Flared connection Indoor coil thermistor RT12 main Refr...

Page 24: ...ature thermistor RT62 Flared connection Stop valve with strainar Stop valve with service port Refrigerant flow in cooling Compressor 4 way valve Refrigerant flow in heating MUZ Refrigerant pipe ø3 8 with heat insulator Refrigerant pipe ø1 4 with heat insulator R V coil MUZ heating ON cooling OFF Strainer 100 LEV Ambient temperature thermistor RT65 Muffler Capillary tube O D 0 118 I D 0 079 9 7 16 ...

Page 25: ...rainar Stop valve with service port Refrigerant flow in cooling Compressor 4 way valve Refrigerant flow in heating MUZ Refrigerant pipe ø3 8 GE12NA Refrigerant pipe ø1 2 GE15NA with heat insulator Refrigerant pipe ø1 4 with heat insulator R V coil MUZ heating ON cooling OFF Strainer 100 Capillary tube O D 0 118 I D 0 071 23 5 8 ø3 0 ø1 8 600 2 LEV Ambient temperature thermistor RT65 Muffler Capill...

Page 26: ... thermistor RT62 Flared connection Stop valve with strainar Stop valve with service port Capillary tube O D 0 142 I D 0 094 1 31 32 ø 3 6 ø 2 4 50 Refrigerant flow in cooling Compressor 4 way valve Refrigerant flow in heating MUZ Refrigerant pipe ø 1 2 with heat insulator Refrigerant pipe ø 1 4 with heat insulator LEV R V coil MUZ heating ON cooling OFF Muffler 100 Receiver Outdoor heat exchanger ...

Page 27: ...charge temperature thermistor RT62 Flared connection Stop valve Stop valve with service port Capillary tube Refrigerant flow in cooling Compressor Service port Service port 4 way valve Refrigerant pipe ø5 8 with heat insulator Refrigerant pipe ø1 4 with heat insulator LEV Muffler 100 Strainer 100 Receiver Outdoor heat exchanger temperature thermistor RT68 Ambient temperature thermistor RT65 Strain...

Page 28: ...rature F Indoor intake air WB temperature F SHF at rating condition 0 73 350 CFM Airflow 65 75 85 95 105 115 Outdoor intake air DB temperature F Total power consumption kW Total capacity 10 3 Btu h MUZ GE15NA 1 71 67 63 71 67 63 17 18 16 15 14 11 13 12 1 3 1 2 1 1 1 0 0 9 0 8 Indoor intake air WB temperature F Indoor intake air WB temperature F SHF at rating condition 0 80 498 CFM Airflow 65 75 85...

Page 29: ...29 2013 Mitsubishi Electric US Inc Due to continuing improvement above specification may be subject to change without notice 3 6 CAPACITY CORRECTION CURVE BY TEMPERATURE MUZ GE24NA DUE TO CONTINUES RESEARCH AND PRODUCT IMPROVEMENT DATA ARE STILL UNDER REVIEW ...

Page 30: ...0 94 12 9 7 8 1 01 12 0 7 3 1 06 11 0 6 7 1 10 67 13 9 10 3 0 81 13 0 9 6 0 89 12 0 8 9 0 96 11 2 8 3 1 02 10 3 7 6 1 07 63 13 1 11 4 0 77 12 1 10 6 0 85 11 3 9 9 0 92 10 3 9 0 0 98 9 4 8 2 1 02 MUZ GE15NA 1 71 17 2 11 4 0 96 16 0 10 7 1 05 15 1 10 0 1 13 14 0 9 3 1 19 12 9 8 6 1 24 67 16 2 13 0 0 91 15 1 12 1 1 00 14 0 11 2 1 08 13 0 10 4 1 14 12 0 9 6 1 20 63 15 3 14 2 0 86 14 1 13 2 0 96 13 2 1...

Page 31: ...18 0 1 06 18 5 1 08 21 0 1 12 65 9 0 0 57 11 3 0 73 14 1 0 87 16 5 0 98 18 5 1 03 19 1 1 05 21 4 1 10 MUZ GE18NA 1 75 9 1 0 64 11 9 0 81 14 9 0 95 17 8 1 06 20 1 1 12 20 7 1 13 23 5 1 18 70 9 8 0 62 12 7 0 78 15 5 0 93 18 2 1 04 20 6 1 09 21 2 1 11 24 0 1 16 65 10 3 0 59 13 0 0 75 16 2 0 90 18 8 1 01 21 2 1 06 21 8 1 08 24 5 1 13 NOTE 1 IDB Intake air dry bulb temperature TC Total Capacity 10 3 Bt...

Page 32: ...91 0 83 0 76 63 1 16 1 10 1 06 1 02 0 96 0 88 0 81 64 1 18 1 13 1 08 1 04 0 98 0 90 0 83 68 1 23 1 18 1 14 1 10 1 03 0 96 0 89 72 1 28 1 23 1 20 1 15 1 09 1 02 0 95 75 1 34 1 29 1 26 1 22 1 15 1 08 1 02 79 1 38 1 34 1 32 1 28 1 21 1 14 1 07 3 M SERIES COOLING CORRECTION Outdoor intake temperature W B F 43 39 36 32 28 25 21 18 14 Outdoor intake temperature W B C 6 4 2 0 2 4 6 8 10 Correction factor...

Page 33: ...0 68 0 83 0 96 1 05 1 05 1 05 MUZ GE24NA 65 0 79 0 92 0 96 1 00 1 03 1 03 MUZ GE18NA 1 65 0 65 0 80 0 91 1 00 1 03 1 03 MUZ GE15NA 1 65 0 74 0 90 0 96 0 97 1 03 1 03 MUZ GE12NA 65 0 66 0 81 0 91 1 01 1 03 1 03 MUZ GE09NA 65 0 67 0 82 0 94 1 03 1 03 1 03 MUZ GE24NA 70 0 76 0 89 0 93 0 96 1 00 1 00 MUZ GE18NA 1 70 0 63 0 77 0 88 0 97 1 00 1 00 MUZ GE15NA 1 70 0 72 0 87 0 93 0 94 1 00 1 00 MUZ GE12NA...

Page 34: ... 2013 Mitsubishi Electric US Inc Due to continuing improvement above specification may be subject to change without notice 3 8 CAPACITY CORRECTION CURVE BY REFRIGERANT PIPING LENGTH DUE TO CONTINUES RESEARCH AND PRODUCT IMPROVEMENT DATA ARE STILL UNDER REVIEW ...

Page 35: ...4NA 1 0 0 954 0 878 0 771 Model Refrigerant piping ft Piping size in Additional piping Max length A Additional piping Max height B Gas Liquid Outside diameter Minimum Wall thickness Outside diameter Minimum Wall thickness MUZ GE09NA 65 40 3 8 0 0315 1 4 0 0315 MUZ GE12NA 1 MUZ GE15NA 1 65 40 1 2 0 0315 1 4 0 0315 MUZ GE18NA 1 100 50 1 2 0 0315 3 8 0 0315 MUZ GE24NA 100 50 5 8 0 0315 3 8 0 0315 2 M...

Page 36: ... specification may be subject to change without notice 3 9 CAPACITY CORRECTION TABLE BY REFRIGERANT PIPING LENGTH Refrigerant piping length ft 25 std 40 65 100 1 000 0 954 0 878 0 771 3 M SERIES PIPING CORRECTION COOLING Refrigerant piping length ft 25 std 40 65 100 1 000 0 989 0 972 0 955 4 M SERIES PIPING CORRECTION HEATING ...

Page 37: ...ed Refrigerant piping length one way ft 25 30 40 50 60 70 80 90 100 MUZ GE15NA 1 3 lb 7 oz 0 1 08 3 24 5 40 7 56 9 72 11 88 14 04 16 20 NOTE Calculation X oz 1 08 5 oz ft Refrigerant piping length ft 25 NOTE Refrigerant piping exceeding 33 ft requires additional refrigerant charge according to the calculation Model Outdoor unit precharged Refrigerant piping length one way ft 33 40 50 60 70 80 90 1...

Page 38: ...varies according to the size of the room and furniture arranged inside the room Model name Mode Function Airflow CFM Air speed ft s Coverage ft MSZ GE06NA HEAT Dry 406 20 6 29 5 COOL Dry 321 16 3 23 5 Wet 286 14 5 21 0 MSZ GE09NA 8 HEAT Dry 406 20 6 29 5 COOL Dry 321 16 3 23 5 Wet 286 14 5 21 0 MSZ GE12NA 8 HEAT Dry 406 20 6 29 5 COOL Dry 321 16 3 23 5 Wet 286 14 5 21 0 MSZ GE15NA 8 HEAT Dry 463 2...

Page 39: ...es MSZ GE Heat Pump Systems June 2013 MSZ GE 39 2013 Mitsubishi Electric US Inc Due to continuing improvement above specification may be subject to change without notice 3 12 SOUND PRESSURE LEVELS MSY GE06 09NA 8 ...

Page 40: ... 2013 M Series MSZ GE Heat Pump Systems June 2013 2013 Mitsubishi Electric US Inc Due to continuing improvement above specification may be subject to change without notice 3 12 SOUND PRESSURE LEVELS MSZ GE12NA 8 ...

Page 41: ... MSZ GE 41 2013 Mitsubishi Electric US Inc Due to continuing improvement above specification may be subject to change without notice 3 12 SOUND PRESSURE LEVELS MSZ GE15NA 8 DUE TO CONTINUES RESEARCH AND PRODUCT IMPROVEMENT DATA ARE STILL UNDER REVIEW ...

Page 42: ... 2013 M Series MSZ GE Heat Pump Systems June 2013 2013 Mitsubishi Electric US Inc Due to continuing improvement above specification may be subject to change without notice 3 12 SOUND PRESSURE LEVELS MSZ GE18NA 8 ...

Page 43: ... MSZ FE18NA MSZ FE18NA MSZ FE18NA MSZ FE18NA 1m NOTCH SPL dB A LINE 0 8m COOL Rated 53 53 53 53 HEAT Rated 53 53 53 53 MICROPHONE Test conditions are based on JIS Z8731 Ambient temperature Cooling DB 27 WB 19 Heating DB 20 WB 15 10 20 30 40 50 60 70 80 90 63 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES Hz OCTAVE BAND SOUND PRESSURE LEVEL dB re 0 002 MICRO BAR NC 70 NC 60 NC 50 NC 40 NC ...

Page 44: ...erion Curves MUZ GE12NA UNIT NOTCH SPL dB A LINE 1m COOL 49 MICROPHONE HEAT 51 Test conditions are based on JIS Z8731 Ambient temperature Cooling DB 35 WB 24 Heating DB 7 WB 6 10 20 30 40 50 60 70 80 90 63 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES Hz OCTAVE BAND SOUND PRESSURE LEVEL dB re 0 002 MICRO BAR NC 70 NC 60 NC 50 NC 40 NC 30 NC 20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINU...

Page 45: ...erion Curves MUZ GE12NA UNIT NOTCH SPL dB A LINE 1m COOL 49 MICROPHONE HEAT 51 Test conditions are based on JIS Z8731 Ambient temperature Cooling DB 35 WB 24 Heating DB 7 WB 6 10 20 30 40 50 60 70 80 90 63 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES Hz OCTAVE BAND SOUND PRESSURE LEVEL dB re 0 002 MICRO BAR NC 70 NC 60 NC 50 NC 40 NC 30 NC 20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINU...

Page 46: ...rion Curves MUZ GE15NA UNIT NOTCH SPL dB A LINE 1m COOL 49 MICROPHONE HEAT 51 Test conditions are based on JIS Z8731 Ambient temperature Cooling DB 35 WB 24 Heating DB 7 WB 6 10 20 30 40 50 60 70 80 90 63 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES Hz OCTAVE BAND SOUND PRESSURE LEVEL dB re 0 002 MICRO BAR NC 70 NC 60 NC 50 NC 40 NC 30 NC 20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUO...

Page 47: ... MSZ GE 47 2013 Mitsubishi Electric US Inc Due to continuing improvement above specification may be subject to change without notice 3 12 SOUND PRESSURE LEVELS MUZ GE18NA 1 DUE TO CONTINUES RESEARCH AND PRODUCT IMPROVEMENT DATA ARE STILL UNDER REVIEW ...

Page 48: ... MSZ FE18NA MSZ FE18NA MSZ FE18NA MSZ FE18NA 1m NOTCH SPL dB A LINE 0 8m COOL Rated 53 53 53 53 HEAT Rated 53 53 53 53 MICROPHONE Test conditions are based on JIS Z8731 Ambient temperature Cooling DB 27 WB 19 Heating DB 20 WB 15 10 20 30 40 50 60 70 80 90 63 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES Hz OCTAVE BAND SOUND PRESSURE LEVEL dB re 0 002 MICRO BAR NC 70 NC 60 NC 50 NC 40 NC ...

Page 49: ...WB F Outdoor Condition Intake air temperature Heating 43 65 15 47 75 13 70 80 70 60 67 60 Standard temperature Maximum temperature Minimum temperature 1 OUTDOOR UNIT MUZ GE09NA MUZ GE12NA MUZ GE15NA 1 MUZ GE18NA 1 MUZ GE24NA OPERATING RANGE A POWER SUPPLY Rated voltage Guaranteed Voltage V Outdoor unit 208 230 V 1 phase 60 Hz Min 187 208 230 Max 253 B OPERATION Mode Condition Intake air temperatur...

Page 50: ...Platinum Catalyst Deodorizing Filter GE06 09 12 15 18 MAC 333IF E System Control Interface MA Contact terminal and M NET Control Adapter Supplemental heat and humidifier adaptor All Models MAC 408FT E Anti Allergy Enzyme Filter qty of 2 GE06 09 12 15 18 MCCH1 Outdoor Air Sensor reads both outside temperature and humidity displayed on MRCH1 and MCCH1 if installed All Models MHK1 Multi functional ha...

Page 51: ...plication X87 721 Simple MA Remote Controller requires MAC 333IF E interface for MSY Z and MFZ indoor units MLS143812T 15 Diamondback Linesets 1 4 x 3 8 x 15 1 2 Twin Tube Insulation GE09 12 MLS143812T 30 1 4 x 3 8 x 30 1 2 Twin Tube Insulation MLS143812T 50 1 4 x 3 8 x 50 1 2 Twin Tube Insulation MLS143812T 65 1 4 x 3 8 x 65 1 2 Twin Tube Insulation MLS141212T 15 1 4 x 1 2 x 15 1 2 Twin Tube Insu...

Page 52: ...mber Descriptions Applicable model MPLS385812T 10 Diamondback Linesets 3 8 x 5 8 x 10 1 2 Twin Tube Insulation GE24 MPLS385812T 15 3 8 x 5 8 x 15 1 2 Twin Tube Insulation MPLS385812T 30 3 8 x 5 8 x 30 1 2 Twin Tube Insulation MPLS385812T 50 3 8 x 5 8 x 50 1 2 Twin Tube Insulation MPLS385812T 65 3 8 x 5 8 x 65 1 2 Twin Tube Insulation MPLS385812T 100 3 8 x 5 8 x 100 1 2 Twin Tube Insulation 3 14 AC...

Page 53: ...SD 400P Outdoor Unit 3 1 4 inch Mounting Base Pair Plastic ULTRILITE1 Condensing Unit Mounting Pad 16 x 36 x 3 MAC 640BH U Outdoor Unit Drain Pan Heater used during defrost cycle GE09 12 15 MAC 641BH U Outdoor Unit Drain Pan Heater used during defrost cycle GE18 MAC 642BH U Outdoor Unit Drain Pan Heater used during defrost cycle GE24 MAC 886SG E Outdoor air outlet guide for directing discharge air...

Page 54: ...MSZ GE 54 2013 M Series MSZ GE Heat Pump Systems June 2013 2013 Mitsubishi Electric US Inc Due to continuing improvement above specification may be subject to change without notice ...

Reviews: