background image

Copper pipe

Good

No good

Tilted

Uneven Burred

90

°

A

Tightening torque

ft. · Ibs

Cap for service port

10 to 13

Cap for stop valve

15 to 22

6-2 PIPE CONNECTION

Note:

When bending the pipe, a specified tool should be used.

1

Indoor unit connection

Connect both liquid pipe and gas pipe to indoor unit.

Apply a thin coat of refrigeration oil 

J

 on the seat surface of pipe.

For connection, align the center of both pipe and union, then tighten the first 3 to 4
turns in flare nut by hand.

For tightening the union part of the indoor unit side, use the table below as a standard
and tighten the flare nut using two wrenches. Excessive tightening damages the flare
section.

Pipe diameter

Tightening torque

mm

inch

ft. · Ibs

9.52

3/8

25 to 30

15.88

5/8

54 to 58

Burr

Copper pipe

Spare
reamer

Pipe
cutter

Flare nut

Copper pipe

Flaring tool

Die

Copper pipe

Flare nut

Die

Copper pipe

York

Smooth all around

Even length
all around

Inside is shining without any scratches.

Close

Open

Hexagonal wrench

Stop valve

PURGING PROCEDURES

Connect the refrigerant pipes (both liquid pipe and gas pipe) between the indoor
and the outdoor unit.

Remove the service port cap of the stop valve on the gas pipe side of the outdoor
unit. (The stop valve will not work in it initial state fresh out of the factory (totally
closed with cap on).)

Connect the gauge manifold valve and the vacuum pump to the service port of the
stop valve on the gas pipe side of the outdoor unit.

Run the vacuum pump. (Vacuumize for more than 15 minutes.)

Check the vacuum with the gauge manifold valve, then close the gauge manifold
valve and stop the vacuum pump.

Leave as it is for one or two minutes. Make sure the pointer gauge manifold valve
remains in the same position. Confirm that the pressure gauge shows -0.101 Mpa
[Gauge] (-30 in. Hg).

Pipe length up to 25 ft.
No gas charge is needed.

Pipe length exceeding 25 ft.
Charge the prescribed amount
of gas. (refer to 3)

Remove the gauge manifold valve quickly from the service port of the stop valve.

After refrigerant pipes are connected and evacuated, fully open all stop valves on
both sides of gas pipe and liquid pipe.
Operating without fully opening lowers the performance and this causes trouble.

Tighten the cap to the service port to obtain the initial status.

Retighten the cap.

Leak test

2

Outdoor unit connection

Connect pipes to the pipe joint part of the stop valve in the same method as the indoor
unit.

For tightening, use the same tightening torque applied for indoor unit and tighten the
flare nut with torque wrench or spanner.

INSULATION AND TAPING

1

Cover piping joints with pipe cover.

2

For outdoor unit side, surely insulate every piping including valves.

3

Using piping tape 

G

, apply taping starting from the entry of outdoor unit.

Fix the end of piping tape 

G

 with adhesive tape.

When piping has to be arranged through above ceiling, closet or area where the
temperature and humidity are high, wind additional commercially sold insulation for
prevention of condensation.

6-3 PURGING PROCEDURES·LEAK TEST

6. INDOOR/OUTDOOR UNIT CONNECTION

FINISHING AND TEST RUN

6-1 FLARING WORK

Main cause of gas leakage is defect in flaring work.
Perform flaring work correctly in the following procedure.

1 Pipe cutting

Cut the copper pipe correctly with pipe cutter.

2 Burrs removal

Completely remove all burrs from the cut cross section of the pipe.

Put the end of the copper pipe downward to prevent burrs from dropping in the pipe.

3 Putting nut on

Remove flare nuts attached to indoor and outdoor
units, then put them on pipe having completed
burr removal.
(not possible to put them on after flaring work)

4 Flaring work

Perform flaring work using flaring tool as shown below.

Outside diameter

A

mm

inch

inch

9.52

3/8

1/8

15.88

5/8

5/32

Firmly hold copper pipe in a die in the dimension shown in the table above.

5 Check

Compare the flared work with figure below.

If flare is noted to be defective, cut off the flared section and perform flaring work
again.

Gauge manifold valve

Stop valve
(Liquid)

Hexagonal

wrench

Caps

Stop valve (Gas)

Vacuum pump

Charge

hose

* Remove the GUARD before air purge,

and reinstall the GUARD after servicing.

GUARD

Service port

Summary of Contents for Mr.SLIM MS24WN

Page 1: ...telephone ground wire Defective grounding could cause an electric shock Do not install the unit in a place where an inflammable gas leaks If gas leak and accumulate in the area surrounding the unit it could cause an explosion Install a ground leakage breaker depending on the installation place Where it is humid If a ground leakage breaker is not installed it could cause an electric shock Perform t...

Page 2: ...e requirement 3 INSTALLATION DIAGRAM ACCESSORIES FLARED CONNECTIONS This unit has flared connections on both indoor and outdoor sides Remove the valve cover of the outdoor unit then connect the pipe Refrigerant pipes are used to connect the indoor and outdoor units Limits Pipe length 50 ft max Height difference 25 ft max No of bends 10 max Refrigerant adjustment If pipe length exceeds 25 ft additi...

Page 3: ...ike that flowing between buildings cannot be expected keep the height or width of obstacles within the following range Otherwise there is the risk of short cycle occurring If the front or rear side satisfies the requirements there is no special restriction on the remaining side Obstruction width 1 5 times width of outdoor unit or smaller Obstruction height Unit height or lower 6 Obstacles on 4 sur...

Page 4: ...e memorized by the indoor electronic control P C board The auto restart function sets to work the moment the power has restored after power failure then the unit will restart automatically If the unit is operated in I FEEL CONTROL mode before power failure the operation is not memorized In I FEEL CONTROL mode the operation is decided by the initial room temperature at re start Operation 1 If the p...

Page 5: ...eve C and hook the upper part of indoor unit on the installation plate 1 Then move the unit to the very edge of the left side for putting the piping easily in the back space of the indoor unit After that cut the part of packing material spacer assembly to hook it on the back rib and lift the indoor unit as shown in the figure below Connect the refrigerant piping with the extension pipe B Thrust th...

Page 6: ...ll the wires lightly to confirm that they do not move If the connecting wire is incorrectly connected to the terminal block the unit does not operate normally If a ground is incorrect it may cause an electric shock Right piping knockout Fasten with wiring clamp Indoor Outdoor unit connecting terminals Power supply terminals Pipe cover Service panel Service panel Pipe cover Rear wiring Loosen termi...

Page 7: ...e stop valve After refrigerant pipes are connected and evacuated fully open all stop valves on both sides of gas pipe and liquid pipe Operating without fully opening lowers the performance and this causes trouble Tighten the cap to the service port to obtain the initial status Retighten the cap Leak test 2 Outdoor unit connection Connect pipes to the pipe joint part of the stop valve in the same m...

Page 8: ...mostat does not work during this time After 30 minutes the unit will start the EMERGENCY OPERATION at a fixed temperature setting of 75 F in COOL MODE Perform test run in the following procedure PROCEDURE Press the EMERGENCY OPERATION switch 1 Press it once and after test run for 30 minutes the EMERGENCY COOL MODE starts If the left side lamp of the operation indicator blinks every 0 5 seconds ins...

Reviews: