4

Release the hooks.

EMERGENCY
OPERATION switch

Mode

Operation Indicator lamp

1

COOL

(Light)

(Off)

2

STOP

(Off)

(Off)

EMERGENCY
OPERATION switch

Mode

Operation Indicator lamp

1

COOL

(Light)

(Off)

2

HEAT

(Off)

(Light)

3

STOP

(Off)

(Off)

Push

Go down

Indoor

unit

Union

Liquid pipe

Gas pipe

Stop valve

Outdoor

unit

Refrigerant gas cylinder
operating valve

Charge hose

Service port
Note: If the charge
hose is connected
to the service port,
be sure to remove
the GUARD before
servicing.

Refrigerant gas cylinder

SCALE

7. FOR MOVEMENT AND MAINTENANCE

7-1 REMOVING AND REINSTALLING THE FRONT PANEL

FRONT PANEL REMOVAL

FRONT PANEL REINSTALLATION

Note:

Do not open the front panel up beyond the level position.
The panel may come off in order to prevent it from being damaged.

1

Set the horizontal vane to the position as below before reinstalling the front
panel.

2

Attach the bottom of the front panel under the horizontal vane.

3

Fit in the top of the front panel.

4

Fit in the bottom of the front panel and tighten it using screws.

5

Push the section of the front panel marked by the arrow and fit the panel into the
air conditioner.

7-2 REMOVING THE INDOOR UNIT

Remove the bottom of the indoor unit from the installation plate.

1

Remove the front panel. (See FRONT PANEL REMOVAL shown above.)

2

Insert flat screwdrivers into the square holes at the left and right bottom of the
indoor unit and push them up; the bottom of the indoor unit goes down and the
hooks are released.

7-3 GAS CHARGE

1

Connect gas cylinder to the service port of stop valve (3-way).

2

Perform air purge of the pipe (or hose) coming from refrigerant gas cylinder.

3

Replenish specified amount of the refrigerant, while operating the air conditioner
for cooling.

 CAUTION

Never charge liquid refrigerant, such as by inverting the gas cylinder while
charging, otherwise troubles may be generated.

To maintain the high pressure of the gas cylinder, warm the gas cylinder with warm
water (under 104

°

F) during cold season. But never use naked fire or steam.

Square hole

5

Push

Horizontal vane

3

2 4

1

Point the
horizontal
vane slightly
downward.

(R22) Gas charge

1

Remove the screw caps.

2

Remove three screws.

3

Pull the bottom.

Hold this concave section and pull the bottom
forward to remove the front panel.

6-4 TEST RUN

  MS type

Before performing the test run, recheck any wrong wiring.
Wrong wiring prevents normal operation or results in blown fuse disabling
operation.

The test run can be started by pressing EMERGENCY OPERATION switch. When
the EMERGENCY OPERATION switch is once pressed, the unit will start the test
run (continuous operation) for 30 minutes.
A thermostat does not work during this time. After 30 minutes the unit will start the
EMERGENCY OPERATION at a fixed temperature setting of 75

°

F in COOL MODE.

Perform test run in the following procedure.

PROCEDURE

Press the EMERGENCY OPERATION switch.

1

Press it once, and after test run for 30 minutes the EMERGENCY COOL MODE starts.

If the left side lamp of the operation indicator blinks every 0.5 seconds, inspect
the indoor/outdoor connecting wire 

A

 for mis-wiring.

2

Press it once more, and the operation stops.
(The operation mode alternates between 

1

 and 

2

 every time the EMERGENCY

OPERATION switch is pressed.)

MSH type

Before performing the test run, recheck any wrong wiring.
Wrong wiring prevents normal operation or results in blown fuse disabling operation.

The test run can be started by pressing EMERGENCY OPERATION switch. When
the EMERGENCY OPERATION switch is once pressed, the unit will start the test
run (continuous operation) for 30 minutes.
A thermostat does not work during this time. After 30 minutes the unit will start the
EMERGENCY OPERATION at a fixed temperature setting of 75

°

F in COOL MODE

or HEAT MODE.

Perform test run in the following procedure.

PROCEDURE

Press the EMERGENCY OPERATION switch.

1

Press it once, and after test run for 30 minutes the EMERGENCY COOL MODE starts.

If the left side lamp of the operation indicator blinks every 0.5 seconds, inspect
the indoor/outdoor connecting wire 

A

 for mis-wiring.

2

Press it once more, and the EMERGENCY HEAT MODE starts.

3

Press it once more, and the operation stops.
(The operation mode changes in order of 

1

 ~ 

3

 every time the EMERGENCY

OPERATION switch is pressed.)

In starting the heating operation, indoor unit fan may not operate to prevent blowing
cool air. Please wait for a few minutes until the temperature of heat exchanger rises
and warm air blows out.

MS type and MSH type

Checking the remote (infrared) signal reception

Press the ON/OFF button on the remote controller and check that an electronic sound
is heard from the indoor unit. Press the ON/OFF button again to turn the air condi-
tioner off.

If the indoor unit is operated with the remote controller, both the
test run and the emergency operation are released by commands
from the remote controller.

Once the compressor stops, the restart preventive device operates so the compres-
sor will not operate for three minutes to protect the air conditioner.

6-5 EXPLANATION TO THE CUSTOMER

Using the OPERATING INSTRUCTIONS, explain the following to the customer, how
to control temperature, how to remove the air filters, how to remove or put the re-
mote controller in the remote controller holder, how to clean, precautions for opera-
tion, etc.

Recommend the customer to read the OPERATING INSTRUCTIONS carefully.

1

2

3

1

Remove the fixing
screw.

2

Move the corner
box to right and
pull it downward.

3

Release the
bottom part of the
unit downward and
pull it forward.

Summary of Contents for Mr.SLIM MS24WN

Page 1: ...telephone ground wire Defective grounding could cause an electric shock Do not install the unit in a place where an inflammable gas leaks If gas leak and accumulate in the area surrounding the unit it could cause an explosion Install a ground leakage breaker depending on the installation place Where it is humid If a ground leakage breaker is not installed it could cause an electric shock Perform t...

Page 2: ...e requirement 3 INSTALLATION DIAGRAM ACCESSORIES FLARED CONNECTIONS This unit has flared connections on both indoor and outdoor sides Remove the valve cover of the outdoor unit then connect the pipe Refrigerant pipes are used to connect the indoor and outdoor units Limits Pipe length 50 ft max Height difference 25 ft max No of bends 10 max Refrigerant adjustment If pipe length exceeds 25 ft additi...

Page 3: ...ike that flowing between buildings cannot be expected keep the height or width of obstacles within the following range Otherwise there is the risk of short cycle occurring If the front or rear side satisfies the requirements there is no special restriction on the remaining side Obstruction width 1 5 times width of outdoor unit or smaller Obstruction height Unit height or lower 6 Obstacles on 4 sur...

Page 4: ...e memorized by the indoor electronic control P C board The auto restart function sets to work the moment the power has restored after power failure then the unit will restart automatically If the unit is operated in I FEEL CONTROL mode before power failure the operation is not memorized In I FEEL CONTROL mode the operation is decided by the initial room temperature at re start Operation 1 If the p...

Page 5: ...eve C and hook the upper part of indoor unit on the installation plate 1 Then move the unit to the very edge of the left side for putting the piping easily in the back space of the indoor unit After that cut the part of packing material spacer assembly to hook it on the back rib and lift the indoor unit as shown in the figure below Connect the refrigerant piping with the extension pipe B Thrust th...

Page 6: ...ll the wires lightly to confirm that they do not move If the connecting wire is incorrectly connected to the terminal block the unit does not operate normally If a ground is incorrect it may cause an electric shock Right piping knockout Fasten with wiring clamp Indoor Outdoor unit connecting terminals Power supply terminals Pipe cover Service panel Service panel Pipe cover Rear wiring Loosen termi...

Page 7: ...e stop valve After refrigerant pipes are connected and evacuated fully open all stop valves on both sides of gas pipe and liquid pipe Operating without fully opening lowers the performance and this causes trouble Tighten the cap to the service port to obtain the initial status Retighten the cap Leak test 2 Outdoor unit connection Connect pipes to the pipe joint part of the stop valve in the same m...

Page 8: ...mostat does not work during this time After 30 minutes the unit will start the EMERGENCY OPERATION at a fixed temperature setting of 75 F in COOL MODE Perform test run in the following procedure PROCEDURE Press the EMERGENCY OPERATION switch 1 Press it once and after test run for 30 minutes the EMERGENCY COOL MODE starts If the left side lamp of the operation indicator blinks every 0 5 seconds ins...

Reviews: