En-8

Installation place

Avoid installing the air conditioner in the following places.

•  Where there is much machine oil.
•  Salty places such as the seaside.
• Where 

sul

fi

 de gas is generated such as a hot spring.

•  Where oil is splashed or where the area is 

fi

 lled with oily smoke.

•  Where there is high-frequency or wireless equipment.
•  Where the air from the outdoor unit air outlet is blocked.
•  Where the operation sound or air from the outdoor unit does not bother the 

house next door.

Electrical work

•  Provide an exclusive circuit for the power supply of the air conditioner.
•  Be sure to observe the breaker capacity.

If you have any questions, consult your dealer.

I

NSTALLATION PLACE 

AND ELECTRICAL WORK

S

PECIFICATIONS

To prevent the effects 

of a 

fl

 uorescent lamp, 

keep as far apart as 

possible.

wall, etc.

Inverter-type 

fl

 uorescent lamp

Keep a space to 
prevent the pic-
ture distortion or 
the noise.

1 m 

or more

Radio

100 
mm or 
more

Well- 
ventilated dry 
place

200/500 mm 
or more

TV

Cordless 
phone or 
Portable 
phone

3 m or 

more

1 m 

or more

The installation location of the outdoor unit should 

be at least 3 m away from the antennas for TV sets, 

radios, etc. In areas where the reception is weak, 

provide greater space between the outdoor unit and 

the antenna of the affected device if operation of the air 

conditioner interferes with radio or TV reception.

1

Set to the highest temperature in manual COOL mode, 
and operate for 3 to 4 hours. 

 Page 4 

This dries the inside of the unit.

2

Press 

 to stop the operation.

3

Turn off the breaker and/or disconnect the power supply 
plug.

4

Remove all batteries from the remote controller.

When using the air conditioner again:

1

Clean the air 

fi

 lter. 

 Page 6 

2

Check that the air inlet and outlet of the indoor and 
outdoor units are not blocked.

3

Check that the earth is connected correctly.

W

HEN THE AIR CONDITIONER IS NOT 

GOING TO BE USED FOR A LONG TIME

Model

MCF-GN13VA

MCF-GN18VA

MCF-GN24VA

Dimensions

×

 W 

×

 D (mm)

Indoor

650 × 1100 × 180

650 × 1100 × 180

650 × 1100 × 180

Outdoor

525 × 718 × 255

880 × 840 × 330

880 × 840 × 330

Weight (kg)

Indoor

26

26

26

Outdoor

34

48

61

Note:

1. Rating condition
  Cooling — Indoor: 

27°C DB, 19°C WB

   

Outdoor:  35°C DB, 24°C WB

2. Guaranteed operating range

Indoor

Outdoor

Upper limit

32°C DB

23°C WB

43°C DB

Lower limit

21°C DB

15°C WB

21°C DB

 

Environment care

Mitsubishi Electric Air conditioner has been designed environment-friendly. The plastic composition can be used as recycle part. 
For the optimum ef

fi

 ciency and energy saving, users are recommended to operate air conditioners as following suggestion.

Turn off air conditioner in case of not in use.
Turn off ventilator in case of not in use.
The set temperature should not be set lower than 25°C.
The cleaning of condensing coil should be performed at least every 3 months.
The cleaning of air cleaning 

fi

 lter should be performed in the period described in this manual.

(GN13/GN18,GN24)

Summary of Contents for Mr.Slim MCF-GN13VA

Page 1: ...glish OPERATING INSTRUCTIONS For user To use this unit correctly and safely be sure to read this operating instructions before use SPLIT TYPE AIR CONDITIONERS INDOOR UNIT MCF GN13VA MCF GN18VA MCF GN24VA ...

Page 2: ...s death serious injury etc with a high probability CAUTION Incorrect handling could cause serious hazard depending on the conditions Children should be supervised to ensure that they do not play with the appliance Do not insert your finger a stick or other objects into the air inlet or outlet This may cause injury since the fan inside rotates at high speeds during operation In case of an abnormal ...

Page 3: ...rvation Turn the breaker OFF when you hear thunder and there is a possibility of a lightning strike The unit may be damaged if lightning strikes After the air conditioner is used for several seasons perform inspection and maintenance in addition to normal cleaning Dirt or dust in the unit may create an unpleasant odor contribute to growth of fungi such as mold or clog the drain passage and cause w...

Page 4: ...er batteries Setting current time NAME OF EACH PART PREPARATION BEFORE OPERATION 1 Remove the front lid 2 Insert the negative pole of AAA alkaline batteries first 3 Install the front lid 4 Press RESET 1 Press CLOCK 3 Press CLOCK again 2 Press the TIME buttons to set the time Each press increases decreas es the time by 1 minute 10 minutes when pressed longer Indoor unit Remote controller Deodorizin...

Page 5: ...anged when the room temperature is more than 2 C higher than the set temperature In this case please wait until the room temperature drops to within 2 C of the set temperature COOL mode Enjoy cool air at your desired temperature DRY mode Dehumidify your room The room may be cooled slightly Temperature cannot be set during DRY mode FAN mode Circulate the air in your room Emergency operation When th...

Page 6: ...ing COOL DRY when the vane is set to position 4 or 5 vane automatically moves to position 1 after 1 hour to prevent water dripping Swing The vane moves up and down intermittently To change the horizontal airflow direction Move the vertical vane manually before starting operation 1 Press or during operation to set the timer ON timer The unit will turns ON at the set time OFF timer The unit will tur...

Page 7: ...r outlet The air cleaning filter is disposable If the color of the filter turns brown replace the filter at once Replace it with a new air cleaning filter every 4 months for best performance Parts Number MAC 1200FT with frame Parts Number MAC 1600FT no frame Note Clean the filters regularly for best performance and to reduce power consumption Air filter Catechin air filter Clean every 2 weeks Remo...

Page 8: ...planation Check points Remote controller The display on the remote controller does not appear or it is dim The indoor unit does not respond to the remote control signal Are the batteries exhausted Page 3 Is the polarity of the batteries correct Page 3 Are any buttons on the remote controller of other electric appliances being pressed Does not cool The room cannot be cooled sufficiently Is the temp...

Page 9: ...eception 1 Set to the highest temperature in manual COOL mode and operate for 3 to 4 hours Page 4 This dries the inside of the unit 2 Press to stop the operation 3 Turn off the breaker and or disconnect the power supply plug 4 Remove all batteries from the remote controller When using the air conditioner again 1 Clean the air filter Page 6 2 Check that the air inlet and outlet of the indoor and ou...

Page 10: ...เกิดอันตรายร าย แรง เช น เสียชีวิต บาดเจ บสาหัส เป นต น ข อควรระวัง หากใช งานไม ถูกต อง อาจทําให เกิดอันตรายร ายแรงได ตามป จจัย แวดล อม ห ามสอดนิ ว ไม หรือวัตถุอื นใด เข าไปในช องลมเข าและช องลมออก มิฉะนั นอาจทําให บาดเจ บได เนื องจากในขณะที เครื องทํางาน พัดลมที อยู ด านใน จะหมุนด วยความเร วสูง หากมีสิ งผิดปกติเกิดขึ น เช น กลิ นเหม นไหม ควรหยุดใช เครื องปรับอากาศ และถอดปลั กไฟออก หรือสับเบรกเกอร...

Page 11: ...ีการเผาไหม หากอากาศถ ายเทไม เพียงพออาจทําให ขาดออกซิเจนได สับเบรกเกอร ลงเมื อฝนฟ าคะนองเพราะอาจเกิดฟ าผ าได เครื องอาจชํารุดหากฟ าผ า เมื อใช งานเครื องมานานหลายฤดูกาลแล ว ควรทําการตรวจสอบ และซ อมบํารุงเพิ มเติมนอกเหนือจากการทําความสะอาดปกติ สิ งสกปรกหรือฝุ นละอองในเครื องอาจทําให เกิดกลิ นอันไม พึงประสงค ทําให เกิดเชื อราต างๆ หรืออุดตันช องระบายจนทําให มีนํ ารั วไหลออกจากเครื อง ภายในอาคารได ขอค...

Page 12: ...ี ของรีโมทคอนโทรล การตั งเวลาในป จจุบัน ูู ชื อชิ นส วน ใ ไ การเตรียมพร อมก อนการใช งาน 1 ถอดฝาหน าออก 2 ใส แบตเตอรี อัลคาไลน ขนาด AAA โดยใส ด านที เป นขั วลบก อน 3 ใส ฝาหน าเข าไป 4 กด RESET 1 กด CLOCK 3 กด CLOCK อีกครั ง 2 กดปุ ม TIME เพื อตั งเวลา ในการกดแต ละครั ง จะเพิ ม ลดเวลา 1 นาที 10 นาที หากกดค างไว เครื องภายในอาคาร รีโมทคอนโทรล แผ นกรองขจัดกลิ น ชิ นส วนอุปกรณ เสริม ช องลมเข า ด านหลัง...

Page 13: ...แปลง หากอุณหภูมิห องสูง กว าอุณหภูมิที ตั งไว มากกว า 2 ในกรณีนี ควรรอจนกว าอุณหภูมิจะลดลงโดยสูงกว าอุณหภูมิที ตั ง ไว ไม เกิน 2 C โหมดทําความเย น COOL ใช กําหนดความเย นตามอุณหภูมิที ต องการ โหมดระบายความชื น DRY ลดความชื นภายในห อง ห องอาจเย นไม มากนัก โหมดระบายความชื น ไม สามารถตั งค าอุณหภูมิได โหมดพัดลม FAN หมุนเวียนอากาศภายในห อง การทํางานฉุกเฉิน เมื อไม สามารถใช งานรีโมทคอนโทรลได เป ดการทําง...

Page 14: ...DRY ในระหว างทําความเย น COOL ระบายความชื น DRY เมื อตั งใบพัดไว ในตําแหน ง 4 หรือ 5 ใบพัดจะ เคลื อนไปยังตําแหน ง 1 โดยอัตโนมัติ เมื อเวลาผ านไปประมาณ 1 ชั วโมง ทั งนี เพื อป องกันไม ให นํ าหยด ส าย ใบพัดจะขยับขึ นและลงเป นระยะ การเปลี ยนทิศทางการระบายลมแอร ในแนวนอน ขยับใบพัดแนวนอนด วยตนเองก อนจะเป ดเครื องให ทํางาน 1 กด หรือ ในระหว างการทํางานเพื อตั งนาฬ กาจับเวลา ตั งเวลาเป ด เครื องจะเป ดตามเว...

Page 15: ...หากสีของแผ นกรองคลํ าลง ควรเปลี ยนแผ นกรองชุดใหม ทันที เปลี ยนแผ นกรองชุดใหม ทุกๆ 4 เดือน เพื อให คงประสิทธิภาพในการทํางานสูงสุด หมายเลขชิ นส วน MAC 1200FT พร อมโครง หมายเลขชิ นส วน MAC 1600FT ไม มีโครง หมายเหตุ ทําความสะอาดแผ นกรองเป นประจําเพื อให คงประสิทธิภาพในการทํางานสูงสุดและช วยลด การสิ นเปลืองพลังงาน แผ นกรองอากาศ แผ นกรองคาเทชิน Catechin ทําความสะอาดทุก 2 สัปดาห กําจัดฝุ นละอองออกโดยใช เ...

Page 16: ...คําอธิบายและจุดตรวจสอบ รีโมทคอนโทรล หน าจอของรีโมทคอนโทรลจะไม แสดง ผลใดๆ หรือหน าจอเลือนลาง เครื อง ภายในอาคารจะไม ตอบสนองต อ สัญญาณรีโมทคอนโทรล แบตเตอรี หมดหรือไม หน า 3 ใส แบตเตอรี ถูกต องตามขั ว หรือไม หน า 3 กดปุ มใดปุ มหนึ งบนรีโมทคอนโทรลของเครื องใช ไฟฟ าอื น อยู หรือไม ไม เย น ห องเย นไม พอ ตั งค าอุณหภูมิไว ถูกต องหรือไม หน า 4 ตั งค าพัดลมไว ถูกต องหรือไม ควรเปลี ยนความแรงพัดให แรงขึ น แผ...

Page 17: ...มเย น COOL ที ปรับตั งค าเอง แล วใช งาน ประมาณ 3 ถึง 4 ชั วโมง หน า 4 ซึ งจะช วยให ด านในของเครื องแห ง 2 กด เพื อหยุดการทํางาน 3 สับเบรกเกอร ลง และ หรือถอดปลั กไฟออก 4 ถอดแบตเตอรี ทั งหมดออกมาจากรีโมทคอนโทรล เมื อกลับมาใช งานเครื องปรับอากาศอีกครั ง 1 ทําความสะอาดแผ นกรอง หน า 6 2 ตรวจสอบว าไม มีสิ งใดมาอุดตัดช องลมเข าและช องลมออกในเครื องภายในอาคาร และภายนอกอาคาร 3 ตรวจสอบว าต อสายดินไว ถูกต อง...

Page 18: ...VN79C791H01 HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Reviews: