12
PEAD-AA
External Static
Pressure
Setting No.
Wired or RedLINK
Remote Controller
Mode No. 8
Mode No. 10
35 Pa
2
1
50 Pa
3
1
70 Pa
1
2
100 Pa
2
2
125 Pa
3
2
SEZ
External Static
Pressure
Setting No.
Wired or RedLINK
Remote Controller
Mode No. 8
Mode No. 10
5 Pa (0.02 in. WG)
1
2
15 Pa (0.06 in. WG)
1
1
35 Pa (0.14 in. WG)
2
1
50 Pa (0.20 in. WG)
3
1
SVZ - Vertical, Horizontal Left &
Right
External Static
Pressure
Setting No.
Wired or RedLINK
Remote Controller
Mode No. 8
Mode No. 10
0.3 in. WG (75 Pa)
1
1
0.5 in. WG (125 Pa)
2
1
0.8 in. WG (200 Pa)
3
1
*
Regarding to down flow setting, please refer to down flow kit
installation manual.
Static Pressure Settings
SVZ -Downflow
External Static
Pressure
Setting No.
Wired or RedLINK
Remote Controller
Mode No. 8
Mode No. 10
0.3 in. WG (75 Pa)
1
2
0.5 in. WG (125 Pa)
2
2
0.6 in. WG (200 Pa)
3
2
PVA - Vertical, Horizontal Left &
Right
External Static
Pressure
Setting No.
Wired or RedLINK
Remote Controller
Mode No. 8
Mode No. 10
0.3 in. WG (75 Pa)
1
1
0.5 in. WG (125 Pa)
2
1
0.8 in. WG (200 Pa)
3
1
* Regarding to down flow setting, please refer to down flow kit
installation manual.
PVA - Downflow
External Static
Pressure
Setting No.
Wired or RedLINK
Remote Controller
Mode No. 8
Mode No. 10
0.3 in. WG (75 Pa)
1
2
0.5 in. WG (125 Pa)
2
2
0.8 in. WG (200 Pa)*
3
2
*PVA-A42 in Downflow External Static pressure: 0.70.
Vane Settings
Mode No. 11
Setting No.
PLA-EA
SLZ-KF
PCA-KA
1
Downward setting (vanes angle setup 3) Not setting
No vanes
2
Middle setting (vanes angle setup 1)
Draft less (vanes angle setup 1)
(Vanes angle setup 1)
3
Draft less (vanes angle setup 2)
Downward setting (vanes angle setup 2) (Vanes angle setup 2)
33-00446EFS_B.indd 12
10/17/2019 3:09:01 PM