13 - 26
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.3.2 Input power supply circuit
WARNING
Insulate the connections of the power supply terminals. Not doing so can cause an
electric shock.
Magnetic contactor wiring connector on the converter unit CNP1.
Unattached state may cause an electric shock.
CAUTION
Always, connect the magnetic contactor (MC) between the main circuit power
supply and L
1
, L
2
, and L
3
of the converter unit, and configure to shut off the power
supply on the side of the converter unit power supply. If the magnetic contactor
(MC) is not connected, a large current keeps flowing and may cause a fire when
the converter unit or the drive unit malfunctions.
Use the trouble signal to switch power off. Otherwise, a regenerative transistor
fault or the like may overheat the regenerative resistor, causing a fire.
Connect the power supply phases (U, V, W) of the servo amplifier and servo motor
correctly. Not doing so can cause the servo motor to run abnormally.
Do not connect a 3-phase 200V power supply or a 3-phase 400V power supply
directly to the servo motor. Doing so can cause a failure.
POINT
Magnetic contactor control connector (CNP1) of the converter unit can be
made valid or invalid with parameter No. PA02 of the converter unit. Refer to
section 13.3.1 and 13.3.6 for details of CNP1 and section 13.5 for the
parameter settings.
When using the external dynamic brake, refer to section 11.6 and 13.9.6.
Summary of Contents for Melservo MR-J3- 350B4
Page 15: ...A 14 MEMO ...
Page 21: ...6 MEMO ...
Page 107: ...3 52 3 SIGNALS AND WIRING MEMO ...
Page 171: ...7 16 7 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Page 181: ...8 10 8 TROUBLESHOOTING MEMO ...
Page 193: ...9 12 9 OUTLINE DRAWINGS MEMO ...
Page 297: ...12 6 12 ABSOLUTE POSITION DETECTION SYSTEM MEMO ...
Page 397: ...13 100 13 SERVO AMPLIFIERS WITH A LARGE CAPACITY 30k TO 55kW MEMO ...