9 TROUBLESHOOTING
9. TROUBLESHOOTING
For troubleshooting in the Normal service mode (MODE 0) and Extended service
mode (MODE E), the causes of errors, which are located using the status of LEDs, and
measures against the errors are described below.
When the operation is in the Normal service mode (MODE 0) or Extended service
mode (MODE E), the TEST LED indicator and PRM SET LED indicator of QJ71PB92D
go off.
LED
Status
Cause
Corrective Action
RUN
Goes OFF
The watchdog timer monitoring
time is exceeded.
Please consult your sales
representative.
SD/RD
Flashes at a
high rate
There is a slave station with
which the initial communication
cannot be performed
(The parameter does not match
the actual slave station).
Please consult your sales
representative.
TOKEN Goes OFF
The token is not cycled.
• Make sure that the PROFIBUS-
DP cable is connected.
• Check the terminating resistance
set switch for correct function.
• Make sure that the station
addresses are not overlapped
with each other.
• Make sure that the HSA does not
exceed the maximum station
address of the network.
PRM SET Flashes
The parameter is not set.
Set the parameters using the GX
Configurator-DP.
RSP ERR Goes ON
A communication trouble occurs. Read the trouble information from
the communication trouble
information area of the buffer
memory.
• An active slave station is not set
for the parameter.
• A slave station having a station
address overlapped with that of
the master station is set for the
parameter.
Correct the parameters.
(If the FAULT LED indicator does
not go off even when the
parameters are corrected, contact
the nearest branch.)
FAULT
Goes ON
• An unexpected error other than
those specified above occurs.
Please consult your sales
representative.
9