8.3 Remote Password
This section provides the list of parameters for use of remote password and describes parameter details.
A remote password are set for an Ethernet module, serial communication module, modem interface
module, or Built-in Ethernet port QCPU
.
Figure 8.18 Remote password settings dialog box
Table8.20 Remote password setting list
Item
Parameter No.
Description
Setting range
Default
Reference
Password settings
-
Enter a remote password.
Four characters or less
(alphanumeric characters, special
symbols)
-
• QnUDE(H)CPU:
QnUCPU Userís
Manual
(Communication
via Built-in
Ethernet Port)
• QJ71E71:
Ethernet module
manual
• QJ71C24:
Serial
communication
module manual
• QJ71CMO:
Modem interface
module manual
Password
active
module
settings
Model
name
-
Select a model name of the module
for which the remote password set
to the CPU module is checked.
• QnUDE(H)CPU
• QJ71E71
• QJ71C24/CMO
-
Start XY
-
Set the start address of the module
for which the remote password is
checked.
0000
H
to 0FE0
H
-
Detail
-
Set details of the remote password
for the QJ71E71.
-
-
User connection No.
-
Select user connection No.
Connection 1 to Connection 16
-
System connection
-
Select a valid port of the remote
password for system connection.
Specify a valid port of the remote
password.
• Auto open UDP port
• FTP transmission port (TCP/IP)
• GX Developer transmission port
(TCP/IP)
• GX Developer transmission port
(UDP/IP), Dedicated instruction,
CC IE Control, MNET/10(H) relay
transmission port.
• HTTP port
-