CHAPTER6 FUNCTIONS
1
2
3
4
5
6
7
8
6.7 Q Series-compatible M
odule
Input Res
ponse Time Selection (
I/O R
esp
onse
Time)
6
-
27
(2) Input response time setting
Set input response time values in the I/O assignment tab of the PLC parameter dialog box.
1)
Make I/O assignment for the target module
.
2)
Click the
button.
3)
On the screen opened, select an input response time value (“I/O response time”).
(3) Precautions
(a) When input response time is shortened
The shorter the input response time is, the more the CPU module is susceptible to noise.
Consider the operating environment when setting input response time values.
(b) Enabling the setting
The input response time setting will be enabled when:
• the CPU module is powered off and then on, or
• the CPU module is reset.
Figure 6.22 Input response time setting
Detailed setting
1) Make I/O assignment.
2) Click the Detailed setting button.
3) Select the input response time.