APPX
Appendix 2 Accuracy
57
A
Appendix 2
Accuracy
Accuracy of D/A conversion is determined by the accuracy for the maximum value of analog output value.
An output characteristic change through changes of the offset/gain setting or the output range does not sacrifice the accuracy,
which is maintained within the described range of the performance specifications.
The following graph shows the fluctuation range of accuracy when the range of -10 to 10V is selected.
The accuracy is
0.1% (
10mV) at ambient temperature of 25
5
; the accuracy is
0.3% (
30mV) at ambient temperature
of 0 to 55
. (except for the conditions under noise.)
digit: Digital value
V: Analog output value (V)
(1): Fluctuation range
-32000
0
0
-10
10
32000
digit
V
(1)
Summary of Contents for MELSEC iQ-R60DA4