3.4. Switch-3: Setting Item Switch
There is “Setting Item Switch” which is assigned by following tables. These values are enabled when
Switch-
1 is set “DISP. (SET.)” or “SETTING”.
Table 3-5 Setting Item of Switch-3 (CBV2)
Rotary position
of Switch-3
CBV2-A02S1
Description
Related
chapters
1
U<
(V)
Undervoltage operating value
2
U<
TIME (s)
Undervoltage operating time
3
U<
UV-TEST
Undervoltage test mode
4
U>
(V)
Overvoltage operating value
5
U>
TIME (s)
Overvoltage operating time
6
−
7
−
8
−
9
−
10
FREQ.
Frequency setting
11
ALARM HOLD
Digital output condition of alarm contact by
self-diagnosis
(hold / un-hold)
12
−
13
COMM. ST. No.
Slave address of Modbus
14
−
15
PASSWORD
Set password
Even though Switch-
1 set “DISP. (SET.)”,
current password doesn’t displayed.
16
−
Table 3-6 Setting Item of Switch-3 (COC4)
Rotary position
of Switch-3
COC4-A02S1
Description
Related
chapters
1
I>
(A)
IDMT overcurrent operating value (51)
2
I>
TM
IDMT overcurrent time multiplier (51)
3
I>
CURVE
IDMT characteristic curve (51)
4
I>>
(A)
Instantaneous overcurrent operating value
(50)
5
I >
(A)
Ground overcurrent operating value (51N)
6
I >
TM
IDMT ground overcurrent time multiplier
(51N)
7
I >
CURVE
IDMT characteristic curve (51N)
8
I >>
(A)
Instantaneous ground overcurrent
operating value (50N)
9
−
10
FREQ.
Frequency setting
11
ALARM HOLD
Digital output condition of alarm contact by
self-diagnosis
(hold / un-hold)
12
−
13
COMM. ST. No.
Slave address of Modbus
14
−
15
PASSWORD
Set password
Even though Switch-
1 set “DISP. (SET.)”,
current password doesn’t displayed.
16
−