8 -
7
EMC AND LOW VOLTAGE DIRECTIVES
8.
(b) When connecting a cable longer than 2m, but not exceeding 10m
• Ground the shield section of the external wiring cable with a cable clamp.
(Ground the shield at the closest location to the A1SD75-S3 external wiring
connector.)
• Install a ferrite core.
• Connect the external wiring cable to a drive unit or an external device in the
shortest distance.
(c) Models and required quantities of the ferrite core and cable clamp
• Cable clamp
• Ferrite core
• Required quantity
(d) Cable clamp position
Model: AD75CK (manufactured by Mitsubishi Electric Corporation)
Model: ZCAT3035-1330 (manufactured by TDK Corporation)
Contact: TDK Corporation
Cable Length
Optional Part
Required Quantity
1 axis
2 axes
3 axes
Within 2m
AD75CK
1
1
1
2m to 10m
AD75CK
1
1
1
ZCAT3035-1330
1
2
3
A1SD75
AD75CK
Inside control panel
20 to 30cm