- 29 -
3. Setting
3.7
Setting Menu 6: Setting the Analog Output
This section shows how to set analog output. When the ME-4210-SS96 optional plug-in module is not installed, this test menu will be skipped.
In the operation mode, press and simultaneously for 2 seconds or more, and the following operation becomes available.
SET
RESET
Set the measurement item to be output to analog output CH1.
Select a measurement item for output from the following table.
(1)
For 3-phase 4-wire
3-phase 4-wire
non
A
1
A
2
A
3
A
N
A
AVG
(CH1)
Demand
A
1
Demand
A
2
Demand
A
3
Demand
A
N
Demand
A
AVG
V
1N
V
2N
V
3N
V
AVG
(L-N)(CH2)
V
12
V
23
V
31
V
AVG
(L-L)
W
1
W
2
W
3
W
∑
(CH3)
var
1
var
2
var
3
var
∑
VA
1
VA
2
VA
3
VA
∑
PF
1
PF
2
PF
3
PF
∑
(CH4)
Hz
Harmonic
A
1
Harmonic
A
2
Harmonic
A
3
Harmonic
A
N
Harmonic
V
1N
Harmonic
V
2N
Harmonic
V
3N
AVG
:
Average,
∑:
Total RMS Value
(2)
For other phase wire system except 3-phase 4-wire
3-phase 3-wire
1-phase 3-wire
(1N2 display)
1-phase 3-wire
(1N3 display)
1-phase 2-wire
non
A
1
(CH1)
A
2
A
3
A
AVG
Demand
A
1
Demand
A
2
Demand
A
3
Demand
A
AVG
V
12
(CH2)
V
23
V
31
V
AVG
W(CH3)
var
PF(CH4)
Hz
Harmonic
A
1
Harmonic
A
3
Harmonic
V
12
Harmonic
V
23
non
A
1
(CH1)
A
N
A
2
A
AVG
Demand
A
1
Demand
A
N
Demand
A
2
Demand
A
AVG
V
1N
(CH2)
V
2N
V
12
V
AVG
W(CH3)
var
PF(CH4)
Hz
Harmonic
A
1
Harmonic
A
2
Harmonic
V
1N
Harmonic
V
2N
non
A
1
(CH1)
A
N
A
3
A
AVG
Demand
A
1
Demand
A
N
Demand
A
3
Demand
A
AVG
V
1N
(CH2)
V
3N
V
13
V
AVG
W(CH3)
var
PF(CH4)
Hz
Harmonic
A
1
Harmonic
A
3
Harmonic
V
1N
Harmonic
V
3N
non
A(CH1)
Demand
A
V(CH2)
W(CH3)
var
PF(CH4)
Hz
Harmonic
A
Harmonic
V
AVG
:
Average,
∑:
Total RMS Value
①
Analog output CH1
output item
Note 1:The same measurement item can be set for each analog output.
Note 2:It is possible to select measurement item that are not included in the set display pattern.
Note 3:Setting to "non" are minimum output. In addition, it moves to the next analog output setting.
Note 4:Underlined portions are the factory default settings for measurement elements assigned to each
analog output.
Note 5:VA is output by scaling 0 to 100% of the rating.
Note 6:When Frequency(Setting menu 1.5) is set to “50Hz”, Hz is output by a scale form 45Hz to 55Hz.
When Frequency(Setting menu 1.5) is set to “60Hz”, Hz is output by a scale form 55Hz to 65Hz.
Note 7:For the harmonic current, the total RMS value is output by a scale from 0 to 60%of the rating.
For the harmonic voltage, the total distortion ratio is output by scaling 0 to 20%.
SET
DISPLAY
SET
DISPLAY
Set the setting menu number to “6”.
(as shown in the right figure)
Setting menu