- 24 -
3.Setting
3.6 Setting Menu 5:
Pulse and Alarm Settings (Setting Upper/Lower Limit Alarm, Motor Starting Current
Mask Function, Pulse Output, etc.)
This section shows how to set the upper/lower limit alarm, backlight flickering during alarm, motor starting current delay time, and
pulse output.
In the operation mode, press and simultaneously for 2 seconds or more, and the following operation becomes available.
For more details about each function, refer to the corresponding pages.
U
pper/lower limit alarm → Page
s 56 and 57
, Motor startup current → Page
60
SET
RESET
Set the Alarm item 1 to be allowed to measurement items.
The upper/lower limit measurement values can be monitored by this setting.
(
1
)
For 3-phase 4-wire
(
2
)
For other phase wire system except 3-phase 4-wire
①
Alarm item 1
Note 1. Measurement items that are not selected in the display pattern can be selected.
Note 2. DA: Current demand, DAN: N-phase current
demand
, V (L-N): Phase to
neutral voltage, V (L-L): phase to phase voltage, DW: Rolling demand
Display when "non"
is selected
Display when
"A upper limit" is
selected
DW upper limit
var upper limit
var lower limit
PF upper limit
PF lower limit
Hz upper limit
Hz lower limit
Harmonic current total RMS Value
N-phase harmonic current total RMS value
Harmonic voltage total distortion ratio
non
A upper limit
A lower limit
AN upper limit
DA upper limit
DA lower limit
DAN upper limit
V (L-N) upper limit
V (L-N) lower limit
V (L-L) upper limit
V (L-L) lower limit
W upper limit
W lower limit
non
A upper limit
A lower limit
DA upper limit
DA lower limit
V upper limit
V lower limit
W upper limit
W lower limit
DW upper limit
var upper limit
var lower limit
PF upper limit
PF lower limit
Hz upper limit
Hz lower limit
Harmonic current total RMS value
Harmonic voltage total distortion ratio
Set the setting menu number to “5”.
(as shown in the right figure)
Setting menu
SET
DISPLAY
SET
DISPLAY