15
MAC-333IF-E
(5) Details of remote control (for giving priority to last operation performed by continuous contact switch)
SYSTEM CONTROL Interface
Brown
Red
Orange
Function
summary
The operation can be started/stopped or enabled/disabled according to the last operation performed by continuous contact switches.
System
configuration
Behavior
· Switch 2
· When it opens, the ON/OFF operation with the paired remote controller is enabled.
· When it closes, the ON/OFF operation with the paired remote controller is disabled.
* “Paired remote controller” includes the wireless remote controller that comes with the room air conditioner, the MA remote controller, and the ME remote controller.
· Switch 1
· When it opens, the air conditioner stops.
· When it closes, the air conditioner operates.
* The system control interface will process the last command among those sent by switch 1, the paired remote controller, and the M-NET system controller.
MAC-333IF-E
CN591
3
2
1
Switch 1
Switch 2
a
· The switches can be used on the following condition:
12 VDC, 0.5 to 2.0 mA
Switch setting
· Input mode (continuous contact)
Make settings for the continuous contact switches.
SW No.
Dip switch
Operating details
SW500
SW502
· SW502-2,3: OFF
· SW500-6,8: OFF
Specifications
of communication
cable
· Cable type
a: Sheathed cable, size 0.3 mm
2
or more
· Cable length
a: Cable size is 0.3 mm
2
: 50 m or less / Cable size is 0.5 mm
2
: 100 m or less
ON
1
2
3
4
5
6
7
8
OFF
ON
1
2
3
4
5
6
7
8
OFF
Note
·The operation of the paired remote controller prohibited by the Switch 2 is the ON/OFF operation only.
Other operations, such as setting the temperature, are enabled.
· When the interface is connected to the M-NET system, even if Switch 2 prohibits the operation with the paired remote controller,
the ON/OFF operation with the system controller is enabled.
· When the interface is connected to the M-NET system, if the system controller prohibits the manual ON/OFF operation, the ON/OFF operation
with the Switch 1 and 2 is prohibited. To enable the Switch 1 and 2, do not disable the manual operation prohibition on the system controller.
· When the group setting is made with the M-NET system or the MA remote controller, connect Switch 1 and 2 to the interface with the
lowest M-NET address or refrigerant address. The wireless remote controller cannot be used together.
ON
OFF
SW No.
Dip switch
SW No.
Dip switch
SW No.
Dip switch
· Input change
Change the input logic.
Operating details
SW502-4
· OFF:
It behaves as described in the “Behavior” section in this chart.
· ON :
· Switch 1
· When it opens, the air conditioner operates.
· When it closes, the air conditioner stops.
· Switch 2
· When it opens, the ON/OFF operation with the paired remote controller is disabled.
· When it closes, the ON/OFF operation with the paired remote controller is enabled.
· Behavior setting when the operation is prohibited by the contact switch
The air conditioner can be stopped when the operation is prohibited by the contact switch.
Operating details
SW502-5
· OFF:
· Switch 1*
· It behaves as described in the “Behavior” section in this chart.
· Switch 2*
· When it opens, the ON/OFF operation with the paired remote controller is enabled.
· When it closes, the ON/OFF operation with the paired remote controller is disabled,
and the state of the air conditioner will not change.
· ON:
· Switch 1*
· It behaves as described in the “Behavior” section in this chart.
· Switch 2
*
· When it opens, the ON/OFF operation with the paired remote controller is enabled.
· When it closes, the ON/OFF operation with the paired remote controller is disabled.
The air conditioner stops.
· Behavior setting when the operation prohibition is cancelled by the contact switch
The air conditioner can be started to work when the operation prohibition is cancelled by the contact switch.
Operating details
SW502-6
· OFF:
· Switch 1*
· It behaves as described in the “Behavior” section in this chart.
· Switch 2
*
· When it opens, the ON/OFF operation with the paired remote controller is enabled,
and the state of the air conditioner will not change.
· When it closes, the ON/OFF operation with the paired remote controller is prohibited.
· ON:
· Switch 1*
· It behaves as described in the “Behavior” section in this chart.
· Switch 2
*
· When it opens, the ON/OFF operation with the paired remote controller is enabled,
and the air conditioner operates.
· When it closes, the ON/OFF operation with the paired remote controller is prohibited.
ON
1
2
3
4
5
6
7
8
OFF
ON
1
2
3
4
5
6
7
8
OFF
ON
1
2
3
4
5
6
7
8
OFF
ON
OFF
ON
OFF
* The behavior described here occurs when the SW502-4 is OFF.
When SW502-4 is ON, the behaviors when the switches open and close will come out the opposite.