4 SETTING OF DIP SWITCH AND ROTARY SWITCH
Rotary switches (SW501, SW510) … M-NET address setting
• Set the switches before turning on the power. The interface unit will not work normally if the switches are not set
correctly.
SW510
SW501
SW580
SW No.
M-NET Address
Description
SW510
SW501
*Both SW510 and SW501
are set to “0” at the factory
setting.
*SW580 is set to “0” at the
factory setting.
• Set the address for centralized control. (Address can be set from 01 to 50.)
• SW510 sets the tens place of the address and SW501 sets the ones place of the address.
For example, to set the address to 25, set SW510 to “2” and SW501 to “5.”
* The figure to the left indicates that the address is set to “1”.
• Set different addresses to each unit in the same system.
SW No.
Refrigerant Address
Description
SW580
• When the MA remote controller is not used, set the refrigerant address (SW580) to “1.”
• Set the address to “0” for the interface which supplies power to the MA remote controller.
• When more than one unit of room air conditioner is operated in the group setting, set different addresses
to each unit.
* A to F of the rotary switch corresponds to the refrigerant address of 10 to 15 respectively.
SW No.
Functions
OFF (Factory setting)
ON
Not available
— (Set to OFF)
—
ON/OFF control by main power source
Disabled
Enabled
Detecting position of room temperature sensor
Indoor unit
MA remote controller
Output settings
Outputs for ON/OFF, error/normal, heater ON/OFF, and humidifier ON/OFF
Input settings
Inputs for ON/OFF and disabling/enabling operation
Inputs for ON/OFF and heating/cooling
Interface status check display
LE501: Communication with indoor unit
LE502: Communication with M-NET System
LE581: Power supply to
MA remote controller
LE501: Communication with
MA remote controller
LE502: OFF
LE581: Power supply to
MA remote controller
Not available
SW500-1
SW500-2
SW500-3
SW500-4
SW500-5
SW500-6
SW500-7
SW500-8
— (Set to OFF)
—
SW No.
Functions
OFF (Factory setting)
ON
12 VDC is output during operation,
in abnormal state, etc.
12 VDC is output when the air conditioner
stops, in normal state, etc.
Continuous contact
Instantaneous contact
ON/OFF operation with M-NET system
controller is enabled.
ON/OFF operation with M-NET system
controller is disabled.
Input mode is set to
continuous contact
Certain behavior is performed, for example
running or operating the air conditioner is prohibited,
by closing the continuous contact switch.
Certain behavior is performed, for example
running or operating the air conditioner is prohibited,
by opening the continuous contact switch.
Input mode is set to
Instantaneous contact
ON/OFF operation is inverted by switching
the instantaneous contact switches.
Only either ON or OFF operation is enabled
regardless of how often the contact switches
are switched.
The operation stops.
The operation starts.
— (Set to OFF)
—
Output change
Input mode
Setting for the range of operation
prohibited by contact switches
Input
change
Behavior setting when the operation
is prohibited by the contact switch
Behavior setting when the operation
prohibition is cancelled by
the contact switch
The state remains the same as that before
the operation is prohibited.
The state remains the same as that before
the operation prohibition is cancelled.
Not available
Setting when P series is included in
the same group
(only when running group operation
using the MA remote controller)
SW502-1
SW502-2
SW502-3
SW502-4
SW502-5
SW502-6
SW502-7
SW502-8
Not included
Included
tens place ones place
Rotary switch (SW580) … Refrigerant address setting
Dip Switch (SW500): Function setting switch A
Dip Switch (SW502): Function setting switch B