App - 17 App - 17
MELSEC-Q
APPENDICES
(1) Functions
(a) Restores the offset/gain values of the user range setting stored in the CPU
to the D/A converter module.
(b) There are two types of interlock signals for the G(P).OGSTOR instruction:
the completion device (D) and the status display device at completion (D) +
1.
1) Completion device
Turns on in the END processing of the scan where the G(P).OGSTOR
instruction is completed, and turns off in the next END processing.
2) Status display device at completion
Turns on and off depending on the completion status of the
G(P).OGSTOR instruction.
Normal completion : Stays off and does not change.
Abnormal completion : Turns on in the END processing of the scan
where the G(P).OGSTOR instruction is
completed, and turns off in the next END
processing.
(c) When the offset/gain values are restored, the reference accuracy falls to
about less than three times of the accuracy before that.
(2) Operation error
In any of the following cases, an error occurs and the corresponding error codes
are stored into the completion status area (S)+1.
Error code
Case resulting in operation error
161
The G(P).OGSTOR instruction was executed in the offset/gain setting
mode.
162
The G(P).OGSTOR instruction was executed consecutively.
163
The G(P).OGSTOR instruction was executed for the model that differs
from the model for which the G(P).OGLOAD instruction had been
executed.
Sequence program
END processing
G.OGSTOR instruction
ON
OFF
Completion device (D)
OFF
Status display device
at completion (D)+1
OFF
ON
ON Abnormal
completion
Normal completion
1 scan
Execution completion of
the G.OGSTOR instruction
END processing
END processing END processing
Summary of Contents for GX Configurator-DA
Page 2: ......
Page 17: ...A 15 A 15 MEMO ...
Page 116: ...6 3 6 3 MELSEC Q 6 PROGRAMMING 2 Programming example ...
Page 185: ...App 20 App 20 MELSEC Q APPENDICES 3 Q62DA Q64DA Unit mm 4 Q68DAV Q68DAI Unit mm ...
Page 186: ...App 21 App 21 MELSEC Q APPENDICES MEMO ...
Page 189: ...WARRANTY ...
Page 191: ......