App - 13 App - 13
MELSEC-Q
APPENDICES
Appendix 2.3 G(P).OGSTOR
Restores the offset/gain values of the user range setting stored in the CPU to the D/A
converter module.
Setting
data
Usable devices
Internal device
(System, user)
File
register
Link direct device
J \
Intelligent
function module
device
U \G
Index
register Z
Constant
Other
Bit Word
Bit Word
K,
H $
(S) —
— —
—
—
(D)
— —
—
—
Setting data
Setting
data
Description
Setting range
Data type
Un
Start I/O number of the module
0 to FE
H
Binary 16 bits
(S)
1
Start number of the device in which control data is stored.
Within the range of the
specified device
Device name
(D)
Device that is turned on 1 scan on completion of dedicated
instruction processing.
(D) + 1 also turns on at an abnormal completion.
Within the range of the
specified device
Bit
1 When executing the G(P).OGLOAD instruction, specify the device designated in (S).
Do not change the data read with the G(P).OGLOAD instruction.
If it is changed, normal operation cannot be guaranteed.
Control data of the Q62DAN and Q62DA
Device
Item
Setting data
Setting range
Set by
(S) System
area
—
—
—
(S) + 1
Completion status
Stores the status when the instruction
is complete.
0
: Normal completion
Other than 0 : Abnormal completion
(Error code)
— System
(S) + 2
Pass data classification setting
The value set to Pass data
classification setting (S)+2 using the
G(P).OGLOAD instruction is stored.
0: Voltage specified
1: Current specified
0000
H
to 0003
H
User
(S) + 3
System area
—
—
—
(S) + 4 CH1 Industrial shipment settings offset value
—
—
System
(S) + 5 CH1 Industrial shipment settings gain value
—
—
System
(S) + 6 CH2 Industrial shipment settings offset value
—
—
System
(S) + 7 CH2 Industrial shipment settings gain value
—
—
System
(S) + 8
CH1 User range settings offset value
—
—
System
(S) + 9
CH1 User range settings gain value
—
—
System
(S) + 10
CH2 User range settings offset value
—
—
System
(S) + 11
CH2 User range settings gain value
—
—
System
Command
G.OGSTOR
Command
GP.OGSTOR
Un
(S)
(D)
Un
(S)
(D)
[Instruction
symbol]
[Execution
condition]
G.OGSTOR
GP.OGSTOR
0
CH.2 CH.1
b15
b2
b1
b0
0
Summary of Contents for GX Configurator-DA
Page 2: ......
Page 17: ...A 15 A 15 MEMO ...
Page 116: ...6 3 6 3 MELSEC Q 6 PROGRAMMING 2 Programming example ...
Page 185: ...App 20 App 20 MELSEC Q APPENDICES 3 Q62DA Q64DA Unit mm 4 Q68DAV Q68DAI Unit mm ...
Page 186: ...App 21 App 21 MELSEC Q APPENDICES MEMO ...
Page 189: ...WARRANTY ...
Page 191: ......