background image

JY997D43901H

Safety Precaution

 

(Read these precautions before using.)

Before using this product, please read this manual and the relevant manuals

introduced in this manual carefully and pay full attention to safety to handle the

product correctly.

The precautions given in this manual are concerned with this product.

In this manual, the safety precautions are ranked as "WARNING" and

"CAUTION".

Depending on circumstances, procedures indicated by "CAUTION" may also be

linked to serious results. 

In any case, it is important to follow the directions for usage.

          

Indicates that incorrect handling may cause hazardous
conditions, resulting in death or severe injury.

Indicates that incorrect handling may cause hazardous
conditions, resulting in medium or slight personal injury
or physical damage.

DESIGN PRECAUTIONS

Some failures of the GOT or cable may keep the outputs on or off.

An external monitoring circuit should be provided to check for output signals

which may lead to a serious accident.

Not doing so can cause an accident due to false output or malfunction.

If a communication fault (including cable disconnection) occurs during

monitoring on the GOT, communication between the GOT and PLC CPU is

suspended and the GOT becomes inoperative.

A system where the GOT is used should be configured to perform any

significant operation to the system by using the switches of a device other

than the GOT on the assumption that a GOT communication fault will occur.

Not doing so can cause an accident due to false output or malfunction.

Do not use the GOT as the warning device that may cause a serious

accident. An independent and redundant hardware or mechanical interlock is

required to configure the device that displays and outputs serious warning.

Failure to observe this instruction may result in an accident due to incorrect

output or malfunction.

Incorrect operation of the touch switch(s) may lead to a serious accident if the

GOT backlight is gone out. When the GOT backlight goes out, the POWER

LED flickers (green/orange) and the display section turns black and causes

the monitor screen to appear blank, while the input of the touch switch(s)

remains active. This may confuse an operator in thinking that the GOT is in

"screensaver" mode, who then tries to release the GOT from this mode by

touching the display section, which may cause a touch switch to operate.

Note that the following occurs on the GOT when the backlight goes out.

- The POWER LED flickers (green/orange) and the monitor screen appears 

blank

The display section is an analog-resistive type touch panel.

If you touch the display section simultaneously in 2 points or more, the switch

that is located around the center of the touched point, if any, may operate.

Do not touch the display section in 2 points or more simultaneously.

Doing so may cause an accident due to incorrect output or malfunction.

When programs or parameters of the controller (such as a PLC) that is

monitored by the GOT are changed, be sure to reset the GOT or shut off the

power of the GOT at the same time.

Not doing so can cause an accident due to false output or malfunction.

DESIGN PRECAUTIONS

When the security of the GOT and relevant information need to be protected
against illegal access from an external device via the Internet, take measures at
the user's discretion.
Failure to do so may cause the configured information to be read out illegally.

DESIGN PRECAUTIONS

Do not bundle the control and communication cables with main-circuit, power or
other wiring.

Run the above cables separately from such wiring and keep them a minimum of
100mm (3.94in.) apart.Not doing so noise can cause a malfunction.

Do not press the GOT display section with a pointed material as a pen or driver.
Doing so can result in a damage or failure of the display section.

When using the GOT with Ethernet connection, available IP addresses are
restricted depending on the system configuration.

- When connecting two or more GOT units to the Ethernet network:

Do not specify the IP address "192.168.0.18" to the GOT or any connected 
equipment.

- When connecting one GOT unit to the Ethernet network:

Do not specify the IP address "192.168.0.18" to any connected equipment 
other than the GOT.
If the IP address "192.168.0.18" is specified in the above system configuration, 
IP address overlap occurs when the GOT is started up, and adverse effect 
may be given to communication in the equipment in which the IP address 
"192.168.0.18" is set. Operation executed at IP address overlap varies 
depending on the equipment and system.

Turn on the power of the connected equipment and network equipment, and
make them ready for communication before connecting them to the GOT.

If the connected equipment and network equipment are not ready for
communication, a communication error may occur in the GOT.

MOUNTING PRECAUTIONS

Be sure to shut off all phases of the external power supply used by the system
before mounting or removing the GOT to/from the panel.

Not doing so can cause the unit to fail or malfunction.

MOUNTING PRECAUTIONS

Use the GOT in the environment that satisfies the general specifications
described in this manual. Not doing so can cause an electric shock, fire,
malfunction or product damage or deterioration.

When mounting the GOT to the control panel, tighten the mounting screws in the
specified torque range. Undertightening can cause the GOT to drop, short circuit
or malfunction, and deteriorate the waterproof effect and oilproof effect.
Overtightening can cause a drop, short circuit or malfunction due to the damage
of the screws or the GOT, and deteriorate the waterproof effect and oilproof effect
due to distortion of the protective cover for oil, GOT or panel.

Never drop cutting chips and electric wire chips into the ventilation window of the
GOT when you drill screw holes or perform wiring.
Otherwise, fire, failure or malfunction may be caused.

When inserting/removing a SD card into/from the GOT, turn the SD card access

switch off in advance. Failure to do so may corrupt data within the SD card.

When removing a SD card from the GOT, make sure to support the SD card by
hand, as it may pop out. Failure to do so may cause the SD card to drop from the
GOT and break.

When installing a USB memory to the GOT, make sure to install the USB memory
to the USB interface firmly.
Failure to do so may cause a malfunction due to poor contact.

Before removing the USB memory from the GOT, operate the utility screen for
removal. After the successful completion dialog box is displayed, remove the
memory by hand carefully. Failure to do so may cause the USB memory to drop,
resulting in a damage or failure of the memory.

Operate and store the GOT in environments without direct sunlight, high
temperature, dust, humidity, and vibrations.

When using the GOT in the environment of oil or chemicals, use the protective
cover for oil. 
Failure to do so may cause failure or malfunction due to the oil or chemical
entering into the GOT.

WIRING PRECAUTIONS

Be sure to shut off all phases of the external power supply used by the system
before wiring. Failure to do so may result in an electric shock, product damage or
malfunctions.

Please make sure to ground FG terminal of the GOT power supply section by
applying 100 or less which is used exclusively for the GOT. Not doing so may
cause an electric shock or malfunction.

WIRING PRECAUTIONS

Correctly wire the GOT power supply section after confirming the rated voltage
and terminal arrangement of the product. Not doing so can cause a fire or failure.

Tighten the terminal screws of the GOT power supply section in the specified
torque range. Undertightening can cause a short circuit or malfunction.

Overtightening can cause a short circuit or malfunction due to the damage of the
screws or the GOT.

Exercise care to avoid foreign matter such as chips and wire offcuts entering the
GOT. Not doing so can cause a fire, failure or malfunction.

WIRING PRECAUTIONS

The cables connected to the unit must be run in ducts or clamped.

Not doing so can cause the unit or cable to be damaged due to the dangling,
motion or accidental pulling of the cables or can cause a malfunction due to a
cable connection fault.

When unplugging the cable connected to the unit, do not hold and pull the cable
portion.
Doing so can cause the unit or cable to be damaged or can cause a malfunction
due to a cable connection fault.

Plug the communication cable into the connector of the connected unit and
tighten the mounting and terminal screws in the specified torque range.
Undertightening can cause a short circuit or malfunction. Overtightening can

cause a short circuit or malfunction due to the damage of the screws or unit.

TEST OPERATION 
PRECAUTIONS

Before performing the test operations of the user creation monitor screen (such
as turning ON or OFF bit device, changing the word device current value,
changing the settings or current values of the timer or counter, and changing the
buffer memory current value), read through the manual carefully and make

yourself familiar with the operation method.
During test operation, never change the data of the devices which are used to
perform significant operation for the system. False output or malfunction can

cause an accident.

STARTUP/MAINTENANCE 
PRECAUTIONS

When power is on, do not touch the terminals.
Doing so can cause an electric shock or malfunction.

Connect the battery correctly. Do not discharge, disassemble, heat, short, solder
or throw the battery into the fire. Incorrect handling may cause the battery to

generate heat, burst or take fire, resulting in injuries or fires.

Before starting cleaning or terminal screw retightening, always switch off the
power externally in all phases. Not switching the power off in all phases can
cause a unit failure or malfunction. Undertightening can cause a short circuit or
malfunction. Overtightening can cause a short circuit or malfunction due to the
damage of the screws or unit.

STARTUP/MAINTENANCE 
PRECAUTIONS

Do not disassemble or modify the unit.
Doing so can cause a failure, malfunction, injury or fire.

Do not touch the conductive and electronic parts of the unit directly.
Doing so can cause a unit malfunction or failure.

The cables connected to the unit must be run in ducts or clamped.
Not doing so can cause the unit or cable to be damaged due to the dangling,
motion or accidental pulling of the cables or can cause a malfunction due to a
cable connection fault.

When unplugging the cable connected to the unit, do not hold and pull the cable
portion. Doing so can cause the unit or cable to be damaged or can cause a
malfunction due to a cable connection fault.

Do not drop or apply any impact to the battery.If any impact has been applied,
discard the battery and never use it.
The battery may be damaged by the drop or impact.

Before touching the unit, always touch grounded metal, etc. to discharge static
electricity from human body, etc.
Not doing so can cause the unit to fail or malfunction.

Replace battery with GT11-50BAT by Mitsubishi electric Co. only.
Use of another battery may present a risk of fire or explosion.

Dispose of used battery promptly.
Keep away from children. Do not disassemble and do not dispose of in fire.

DISPOSAL PRECAUTIONS

When disposing of the product, handle it as industrial waste.

When disposing of batteries, separate them from other wastes according to the
local regulations.
(For details of the battery directive in EU member states, refer GOT User's
Manual.)

Associated Manuals

The following manuals are relevant to this product. When these loose manuals
are required, please consult with our local distributor.

*1 Stored in the GT Works3/GT Designer3 in PDF format.

For details of a PLC to be connected, refer to the PLC user's manual respectively.

Bundled Items

 

TOUCH PANEL 
PRECAUTIONS

For the analog-resistive film type touch panels, normally the adjustment is

not required.

However, the difference between a touched position and the object position

may occur as the period of use elapses.

When any difference between a touched position and the object position

occurs, execute the touch panel calibration.

When any difference between a touched position and the object position

occurs, other object may be activated.

This may cause an unexpected operation due to incorrect output or

malfunction.

TRANSPORTATION 
PRECAUTIONS

When transporting lithium batteries, make sure to treat them based on the

transport regulations. 

(Refer to User's Manual for details of the regurated models.)

Before transporting the GOT, turn the GOT power on and check that the

battery voltage status is normal on the Time setting & display screen (utilities

screen). In addition, confirm that the adequate battery life remains on the

rating plate.

Transporting the GOT with the low battery voltage or the battery the reached

battery life may unstabilize the backup data unstable during transportation.

Make sure to transport the GOT main unit and/or relevant unit(s) in the

manner they will not be exposed to the impact exceeding the impact

resistance described in the general specifications of this manual, as they are

precision devices. Failure to do so may cause the unit to fail.

Check if the unit operates correctly after transportation.

Manual name

Contents

Manual Number

(Model Code)

GT14 User’s Manual
(sold separately)

D e s c r i b e s   t h e   G T 1 4   h a r d w a r e -
relevant content such as part names,
external dimensions, mounting, power
supply wiring, specifications, and
introduction to option devices

JY997D44801

(09R823)

GT Designer3 
Version1 Screen 
Design Manual
(For GOT1000 
S e r i e s )
(Fundamentals) 
1/2, 2/2
(sold separately) 

*1

D e s c r i b e s   m e t h o d s   o f   t h e   G T
Designer3 installation operation, basic
operation for drawing and transmitting
data to GOT1000 series

SH-080866ENG

(1D7MB9)

GT Designer3 
Version1 Screen
Design Manual
(For GOT1000 
Series) (Functions) 
1/2, 2/2
(sold separately) 

*1

Describes specifications and settings
of the object functions used in GT
Designer3

SH-080867ENG

(1D7MC1)

Product 

Name

Model Name

Specifications

GOT

GT1455-QTBDE

5.7" diagonal [320 

 240 dots], TFT color (65536

colors), built-in battery and Ethernet interface

GT1455-QTBD

5.7" diagonal [320 

 240 dots], TFT color (65536

colors), built-in battery

GT1450-QMBDE

5.7" diagonal [320 

 240 dots], TFT monochrome

(black/white), built-in battery and Ethernet interface

GT1450-QMBD

5.7" diagonal [320 

 240 dots], TFT monochrome

(black/white), built-in battery 

GT1450-QLBDE

5.7" diagonal [320 

 240 dots], STN monochrome

(black/white), built-in battery and Ethernet interface

GT1450-QLBD

5.7" diagonal [320 

 240 dots], STN monochrome

(black/white), built-in battery

1. Features

1) Improved monitoring performance and connectivity to FA devices

- Multiple languages are displayed using the Unicode2.1-compatible fonts 

and beautiful characters are drawn using the TrueType and high quality 
fonts.

- Two types of display modes are provided: 65536-colors display and 

monochrome display.
In the monochrome display, 16 scales are used to improve the display.
A fine and beautiful full-color display which shows even small characters 
clearly, is enabled by adopting the high intensity, wide viewing angle and 
high definition TFT color LCD. (Also compatible with digital screen displays 
with 65536 colors, BMP, etc.)

- High-speed monitoring through high-speed serial communication at 115.2 

kbps maximum or through Ethernet connection.

- High speed display and high speed touch switch response.

2) More efficient GOT operations including screen design, startup, adjustment,

management and maintenance works

- The 9MB built-in flash memory is included as standard.
- SD card interface is included as standard.
- RS-232 interface is included as standard.
- RS-422/485 interface is included as standard.
- USB interface (host/device) are included as standard.
- Ethernet interface is included. (in some models)

3) Enhanced support of FA setup tools

- PLC program transfer and monitoring are possible via the personal 

computer that is connected to the GOT if connected directly to the A, QnA, 
L, Q, or FX series of the PLC CPU (FA transparent function).

2. Part Name

2.1 Front 

For the PC connection, refer to the following.



GT14 User’s Manual

Bundled item

Quantity

Mounting brackets

4

Mounting screws: M4 x 35mm (1.38")

4

Dust-/Water-proof packing

1

GT14 General Description (This manual)

1

No

Name

Specifications

1) Display screen

Displays the utility screen and the user creation
screen.
GT1455-QTBD(E):320

240 dots, TFT color liquid 

crystal

GT1450-QMBD(E):320

240 dots, TFT monochrome 

(white/black) liquid crystal, 16
scales

GT1450-QLBD(E):320

240 dots, STN monochrome 

(white/black) liquid crystal, 16
scales

2) Touch panel

For operating the touch switches in the utility screen
and the user creation screen

3) POWER LED

Lit in green: Power is correctly supplied
Lit in orange: Screen saving
Blinking in orange/green: Blown backlight bulb
Not lit: Power is not supplied

4) Logo label

Removable

5) USB interface

USB interface for connecting a personal computer
(Device)
O S   i n s t a l l a t i o n ,   p r o j e c t   d a t a   d o w n l o a d ,   FA
transparent

6)

USB environmental 
protection cover

Opens/Closes when the USB interface is used.

1)  2)

5)  6)

3)

4)

2.2 Back/Bottom

For the connection to the controller (PLC, microcomputer board, bar code reader,
RFID, etc) or PC, refer to the following.



GT14 User’s Manual

No.

Name

Specifications

1)

RS-232 
interface

For communicating with controller or personal computer 
(D-sub 9-pin male)

2)

RS-422/485 
interface

For communicating with controller (D-sub 9-pin female)

3)

USB interface

For data transfer, data storage USB interface (Host)

4)

Hole for 
preventing 
USB 
cable 
disconnection

Hole for fixing the USB cable with a cable tie (such as 
Insulock) to prevent disconnection

5)

Rating plate 
(nameplate)

--

6)

SD card 
interface

Interface for installing the SD card to GOT

7)

SD card 
access LED

Lit: SD card accessed
Not lit: SD card not accessed

8)

SD card 
access switch

Switch for prohibiting access to SD card before removing 
the SD card from the GOT
ON: SD card being accessed (SD card removal prohibited)
OFF: No access to SD card (SD card removal possible)

9)

Battery

GT11-50BAT battery for storing clock data, alarm history 
and recipe data

10)

Battery cover

Open or close when replacing the battery.
Opened and closed when the terminating resistor is 
changed over

11)

Power terminal

Power terminal and FG terminal
(for power supply (24VDC) to GOT and grounding)

12)

Power terminal 
cover

Open or close when connecting a power terminal.
(Color: transparent)

13)

Reset switch

Hardware reset switch (Use an isolated rod to operate.)

14)

Terminating
resistor
selector switch

Terminating resistor selector switch of RS-422/485
(330

/OPEN/110

)

15)

Ethernet 
communication 
status LED

SD RD: Turns on in green during data communication,
100M:Turns on in green during 100Mbps transmission.

16)

Ethernet 
interface

For connecting the equipment through Ethernet 
(RJ-45 connector)

17)

Hole for unit 
installation 
fitting

Hole for the inserting installation fittings (accessory) during 
the GOT installation to the panel 
(4 holes at top and bottom)

1)

2)

15)

10)

3)

11) 12)

6)

13)

8)

7)

5)

4)

Battery cover opened

14)

9)

17)

17)

16)

3. Specifications

3.1 General Specifications

*1 Do not use or store the GOT under pressure higher than the atmospheric pressure of altitude 0m (0ft.). Failure to observe this instruction may cause a malfunction.

When the air inside the control panel is purged by pressurization, the surface sheet may be lifted by high pressure. As a result, the touch panel may be difficult to press,
and the sheet may be peeled off.

*2 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the

machinery within the premises.
Category 



 applies to equipment for which electrical power is supplied from fixed facilities.

The surge voltage withstand level for up to the raged voltage of 300 V is 2500 V.

*3 This index indicates the degree to which conductive material is generated in the environment where the equipment is used.

In pollution degree 2, only non-conductive pollution occurs but temporary conductivity may be produced due to condensation.

3.2 Performance Specifications

Item

Specifications

Operating ambient 
temperature

Display section

0 to 50

C

Other than display section 0 to 55

C (When mounted horizontally), 0 to 50

C (When mounted vertically)

Storage ambient temperature

-20 to 60

C

Operating ambient humidity

10 to 90% RH, non-condensing (STN liquid crystal type to be stored at or below 39

C WBT.)

Storage ambient humidity

10 to 90% RH, non-condensing (STN liquid crystal type to be stored at or below 39

C WBT.)

Vibration resistance

Conforms to JIS 
B3502 and 
IEC61131-2

Frequency

Acceleration

Half-amplitude

Sweep Count

Under intermittent 
vibration

5 to 8.4Hz

--

3.5mm

10 times each in X, 

Y and Z directions

8.4 to 150Hz

9.8m/s

2

--

Under continuous 
vibration

5 to 8.4Hz

--

1.75mm

8.4 to 150Hz

4.9m/s

2

--

Shock resistance

Conforms to JIS B3502, IEC 61131-2 (147 m/s

2

, 3 times each in X, Y and Z directions)

Operating atmosphere

Must be free of lamp black, corrosive gas, flammable gas, or excessive amount of electro conductive dust particles and
must be no direct sunlight. (Same as for saving)

Operating altitude

*1

2000 m (6562 ft) max.

Installation location

Inside control panel

Overvoltage category

*2



 or less

Pollution degree

*3

2 or less

Cooling method

Self-cooling

Item

Specifications

GT1455-QTBD(E)

GT1450-QMBD(E)

GT1450-QLBD(E)

Display 
section

*1

Type

TFT color liquid crystal

TFT monochrome (white/black)
 liquid crystal

STN monochrome (white/black)
 liquid crystal

Screen size

5.7"

Resolution

320 

 240 dots

Display size

W115(4.53) 

 H86(3.39)[mm](inch) (Horizontal format)

Display character

16-dot standard font: 20 characters 

 15 lines, 12-dot standard font: 26 characters 

 20 lines

Display color

65536 colors

Monochrome (white/black), 16 scales

Display angle

*2

Left/Right: 80 degrees, Top: 80 degrees, Bottom: 60 degrees (Horizontal format)

Left/Right: 45 degrees, 
Top: 20 degrees, 
Bottom: 40 degrees (Horizontal format) 

Contrast adjustment

--

32-level adjustmen

Intensity of LCD only

400[cd/m

2

]

300[cd/m

2

]

Intensity adjustment

8-level adjustment

Life

Approx. 50,000h. (Time for display intensity to become 1/5 at operating ambient temperature of 25

C)

Backlight

LED (irreplaceable by a user) Backlight off/screen saving time can be set.

*3

Life

Approx. 70,000h or longer (Time for display intensity reaches 50% at the operating ambient temperature of 25

C)

To u c h
panel

*4

Type

Analog resistive film touch panel

Key size

Minimum 2 

 2 dots (per key)

N u m b e r   o f   p o i n ts   t o u c h e d
simultaneously

Simultaneous presses not allowed. (Only 1 point can be touched.)

Life

1 million times or more (operating force 0.98N max.)

Memory

C drive

*5

Flash memory (Internal), for storing project data (9Mbytes) and OS

Life (Number of write times) 100,000 times

D drive

SRAM (Internal), 512kbytes (battery backup)

Battery

GT11-50BAT lithium battery

Type

Magnesium maganese dioxide lithium primary battery

Backup target

Clock data, alarm history, recipe data, time action setting value, advanced alarm/advanced recipe, logging, hardcopy and 
SRAM user area

Life

Approx. 5 years (Operating ambient temperature of 25

C)

GT1455-QTBD(E), GT1450-QMBD(E)

GT1450-QLBD(E)

GT14 General Description

This manual describes the part names, dimensions, mounting, and specifications
of the product. Before use, read this manual and manuals of relevant products
fully to acquire proficiency in handling and operating the product. Make sure to
learn all the product information, safety information, and precautions.
And, store this manual in a safe place so that you can take it out and read it
whenever necessary. Always forward it to the end user.
Registration
Ethernet is a trademark of Xerox Corporation in the United States. The company
name and the product name to be described in this manual are the registered
trademarks or trademarks of each company.

Effective April 2018
Specifications are subject to change without notice.

 2011 MITSUBISHI ELECTRIC CORPORATION

Manual Number

JY997D43901H

Date

April 2018

Summary of Contents for Got1000 GT1455-QTBDE

Page 1: ...uch panels normally the adjustment is not required However the difference between a touched position and the object position may occur as the period of use elapses When any difference between a touched position and the object position occurs execute the touch panel calibration When any difference between a touched position and the object position occurs other object may be activated This may cause...

Page 2: ...uch panels normally the adjustment is not required However the difference between a touched position and the object position may occur as the period of use elapses When any difference between a touched position and the object position occurs execute the touch panel calibration When any difference between a touched position and the object position occurs other object may be activated This may cause...

Page 3: ...5 QTBD GT1450 QMBD GT1450 QLBD GT1455 QTBDE GT1450 QMBDE GT1450 QLBDE 164 6 46 22 0 87 120 4 73 22 0 87 120 4 73 152 5 99 135 5 32 47 1 86 6 0 24 55 2 17 4 40UNC inch screw type M2 6 Metric screw type Panel thickness 2 to 4mm 0 07 to 0 15 or less Unit mm inch 23 0 91 10 0 4 10 0 4 120 4 73 No Name 1 PLC connection cable PC connection cable 120 4 73 140 5 52 152 5 99 30 1 19 1 Unit mm inch 153 6 03...

Page 4: ...5 QTBD GT1450 QMBD GT1450 QLBD GT1455 QTBDE GT1450 QMBDE GT1450 QLBDE 164 6 46 22 0 87 120 4 73 22 0 87 120 4 73 152 5 99 135 5 32 47 1 86 6 0 24 55 2 17 4 40UNC inch screw type M2 6 Metric screw type Panel thickness 2 to 4mm 0 07 to 0 15 or less Unit mm inch 23 0 91 10 0 4 10 0 4 120 4 73 No Name 1 PLC connection cable PC connection cable 120 4 73 140 5 52 152 5 99 30 1 19 1 Unit mm inch 153 6 03...

Page 5: ...uch panels normally the adjustment is not required However the difference between a touched position and the object position may occur as the period of use elapses When any difference between a touched position and the object position occurs execute the touch panel calibration When any difference between a touched position and the object position occurs other object may be activated This may cause...

Page 6: ...5 QTBD GT1450 QMBD GT1450 QLBD GT1455 QTBDE GT1450 QMBDE GT1450 QLBDE 164 6 46 22 0 87 120 4 73 22 0 87 120 4 73 152 5 99 135 5 32 47 1 86 6 0 24 55 2 17 4 40UNC inch screw type M2 6 Metric screw type Panel thickness 2 to 4mm 0 07 to 0 15 or less Unit mm inch 23 0 91 10 0 4 10 0 4 120 4 73 No Name 1 PLC connection cable PC connection cable 120 4 73 140 5 52 152 5 99 30 1 19 1 Unit mm inch 153 6 03...

Reviews: