5-1-4 Setting the Addresses of the Recipient
5-1-5 Mail format
Error mails are sent in the format shown below.
To monitor and operate the unit with the maintenance tool via
mail from a remote location, enter the mail address of the
receiver in the [Mail Communication Setting].
A maximum of 10 addresses can be registered.
E-mail communication is possible only with the recipients
whose addresses are registered on this screen.
From:Mitsubishi Building(000001)
Date:11/09/2005 16:32:12
Error unit:065
Error code:1302
Status:Occurrence
Item
Format
Remarks
Mail title
Set title
Refer to 5-1-3 (1) for the setting of mail title.
From
GB-24A unit name and unit ID
Refer to 4-2-1 for the setting of GB-24A unit
name and unit ID.
Date
dd/MM/yyyy hh:mm:ss
Date of error
Note: The date format set in section 4-2-5 will be
applied.
Error unit
When an error occurs on air conditioners and
general equipment
- M-NET address of the error source
Note: When an error occurs on the general
equipment that is connected via DIDO
controller, M-NET address of the DIDO
controller will be sent. (which means an error
occurs on one of the general equipment that is
connected to the DIDO controller)
Error code
4-digit error
When an error occurs on air conditioners
Refer to the service manual for each unit.
When an error occurs on general equipment
0091:General equipment error
Status
“Occurrence” or “Recovery”
Error status