22
5-2 Settings for measurement
To measure the temperature or the amount of electricity, click the [Function1]-[Measurement] in the menu, and
open the Measurement screen. Settings for controllers used for measurement can be made.
After the settings are made, click [Save Settings] to send setting data to GB-24A.
Note: If the user logs in as a manager, some of the operations may be prohibited.
5-2-1 Registering AI controllers for temperature/humidity sensors
System settings for measurement sensors can be made. Up to two temperature/humidity sensors can be
connected to one AI controller.
(1) Use the scroll bar, and select the address to which the AI controller (PAC-YG63MCA) is connected.
(2) Select the icon of the AI controller (
) in the column of items to be measured.
Note: To disconnect the AI controller, click the icon of the AI controller that has been selected. The icon will be in unselected state.
(3) Enter the name of the sensor.
(4) Select either the temperature icon (
) or the humidity icon
(
).
(5) Enter the measurable range of the temperature or of the humidity.
Note: When the Pt sensor is connected, the range must be between -30ºC and +60ºC. When the sensors other than the Pt
sensors are connected, enter the ranges that are described in the operation manuals.
(6) To receive an e-mail when the temperature or the humidity exceeds a certain value, set the upper/lower
limit alarm values (occurrence, recovery).
Note: To avoid repeating occurrence and recovery, it is recommended that the difference between the occurrence value and the
recovery value is approx. 1ºC.
Setting details
Set the details for
measurement.
Save Settings
Send setting data to
GB-24A.
Trend interval
Select the data saving interval.
Address
Unit address will be
displayed here.
Selection of decimal
point character
Select the decimal point
character.
Scroll bar
Switch the address.
Mail sending settings
Set the Type of E-Mail,
Mail Subject, and E-Mail
Address.
Selection of items to be
measured
Select the items to be
measured between by sensors
(such as temperature/humidity)
or by meters (such as amount
of electricity).
Selection of separator
character
Select the separator character
for CSV file.
Refresh
Read setting data from GB-24A.
Temperature/humidity selection
Sensor name
Measurable range
Settings for upper/
lower limit alarm
Items to be
measured
Address
Setting Details
of sensor 1
Setting Details
of sensor 2
Upper limit
(occurrence)
Upper limit
(recovery)
Lower limit
(recovery)
Lower limit
(occurrence)
Scroll bar