[FMOV(P)] (Transferring the same data in a batch)
[BMOV(P)] (Transferring block data in a batch)
■
FMOV
When the input condition turns on, the FMOV instruction transfers data in the device specified by (s) to the
(n) points of
device areas starting from the device specified by (d).
The following figure shows the operation of when X3 turns on and the FMOV instruction is executed.
• The FMOV instruction is useful for clearing many data sets in a batch.
The FMOV instruction substitutes the multiple RST instructions.
X3
(d)
(s)
K8
D100
K365
FMOVP
(n)
X4
K16
D108
K7000
FMOVP
X5
(d)
(s)
K16
D132
D100
BMOVP
(n)
X6
K48
D100
K0
FMOVP
X3
(d)
(s)
K8
D100
K365
FMOVP
(n)
K365
365
365
365
365
365
D100
D101
D102
D107
•••
•••
(d)
(s)
(n)
8 sets of data (K8)
Same
X6
K8
D100
K0
FMOV
X6
D100
RST
D101
RST
D107
RST
■
BMOV
When the input condition turns on, the BMOV instruction batch-transfers the (n) points of data stored
starting from the
device specified by (s) to the areas starting from the device specified by (d).
The following figure shows the operation of when X5 turns on and the BMOV instruction is executed.
• The BMOV instruction is useful for the following applications.
• Saving logging data in files
• Saving important data (such as automatic operation data and measurement data) into the latch areas, for example the
data register set for backing up data at power-off in parameter, to prevent data loss at an unintended power failure
X5
K16
D132
D100
BMOVP
(s)
(n)
(d)
365
D100
365
D132
•••
•••
•••
•••
•••
365
D107
365
D139
7000
D108
7000
D140
•••
•••
•••
•••
•••
7000
D115
7000
D147
(s)
(d)