3 System Configuration
3.2 Devices Required for Network Configuration
22
FX
3U
-ENET-ADP User's Manual
3.2
Devices Required for Network Configuration
This section explains the devices that are required to configure a network.
Network installation work requires sufficient safeguards; ask a network specialist for installation.
When connecting the Ethernet adapter to a network, either 10BASE-T or 100BASE-TX can be used.
The Ethernet adapter detects whether it is 10BASE-T or 100BASE-TX, and full-duplex or half-duplex
transmission mode according to the hub. (Auto detection function)
For connection to the hub without the auto detection function, set half-duplex mode on the hub side.
1) Connection using 100BASE-TX
Use devices that satisfy the standards of IEEE802.3 and 100BASE-TX.
• Shielded twisted pair cable (STP cable), category 5 or better
Use a straight cable for connection between a hub and the Ethernet adapter.
(A cross cable can also be used when connecting the Ethernet adapter directly to the external device,
not through a hub.)
• RJ45 plug
• 100Mbps hub
2) Connection using 10BASE-T
Use devices that satisfy the standards of IEEE802.3 and 10BASE-T.
Use devices that satisfy the standards of IEEE802.3 and 100BASE-TX.
• Shielded twisted pair cable (STP cable), category 3 or better
Use a straight cable for connection between a hub and the Ethernet adapter.
(A cross cable can also be used when connecting the Ethernet adapter directly to the external device,
not through the hub.)
• RJ45 plug
• 10Mbps hub
3.3
Applicable Systems
3.3.1
Applicable PLC
The version number can be checked by reading the last three digits of device D8001 or D8101.
*1. An expansion board is required to connect the FX
3U
-ENET-ADP with FX
3U
/FX
3UC
-32MT-LT(-2) PLCs.
3.3.2
Applicable Software
1. GX Works2
Use the following version when setting the Ethernet adapter or using the MELSOFT connection function.
Caution
• If an older version is used, programming will not be possible.
• In order to set up the Ethernet adapter via GX Works2, FX Configurator-EN needs to be installed.
Model name
Applicability
FX
3U
Series PLC
*1
Ver. 3.10 and later
Only one FX
3U
-ENET-ADP unit can be connected to a main unit.
FX
3UC
Series PLC
*1
Ver. 3.10 and later
Only one FX
3U
-ENET-ADP unit can be connected to a main unit.
Software
Applicability
GX Works2
• SW DNC-GXW2-E
Ver. 1.73B or later
Summary of Contents for FX3U-ENET-ADP