This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
(2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
(3) Special damages and secondary damages whether foreseeable or not, compensation for
accidents, and compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
and other tasks.
For safe use
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.
•
•
•
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Side
A
Side
B
JAPANESE
ENGLISH
JY997D40801C
Side
B
Safety Precaution
(Read these precautions before use.)
If the equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
This manual classify the safety precautions into two categories:
and
.
Depending on circumstances, procedures indicated by
may also be
linked to serious results.
In any case, it is important to follow the directions for usage.
Associated Manuals
How to obtain manuals
For the necessary product manuals or documents, consult with the Mitsubishi
Electric dealer from where you purchase your product.
Indicates that incorrect handling may cause hazardous
conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous
conditions, resulting in medium or slight personal injury
or physical damage.
Manual name
Manual No.
Description
FX
3G
Series
User’s Manual
- Hardware Edition
JY997D31301
MODEL CODE:
09R521
E x p l a i n s F X
3 G
S e r i e s P L C
specification details for I/O, wiring,
installation, and maintenance.
FX
3U
Series
User’s Manual
- Hardware Edition
JY997D16501
MODEL CODE:
09R516
E x p l a i n s F X
3 U
S e r i e s P L C
specification details for I/O, wiring,
installation, and maintenance.
FX
3UC
Series
User’s Manual
- Hardware Edition
JY997D28701
MODEL CODE:
09R519
E x p l a i n s F X
3 U C
S e r i e s P L C
specification details for I/O, wiring,
installation, and maintenance.
FX
2N
HARDWARE MANUAL
JY992D66301
MODEL CODE:
09R508
E x p l a i n s F X
2 N
S e r i e s P L C
specification details for I/O, wiring,
installation, and maintenance.
FX
2NC
(D/UL)
HARDWARE MANUAL
JY992D87201
Explains FX
2NC
(D/UL) Series PLC
specification details for I/O, wiring,
installation, and maintenance.
FX
2NC
(DSS/DS)
HARDWARE MANUAL
JY992D76401
MODEL CODE:
09R509
Explains FX
2NC
(DSS/DS) Series
PLC specification details for I/O,
wiring, installation, and maintenance.
FX
1N
HARDWARE MANUAL
JY992D89301
MODEL CODE:
09R511
E x p l a i n s F X
1 N
S e r i e s P L C
specification details for I/O, wiring,
installation, and maintenance.
Certification of UL, cUL standards
FX
2N
-8EYR-S-ES/UL units comply with the UL standards (UL, cUL).
UL, cUL File Number: E95239
Regarding the standards that comply with the main unit, please refer to either the FX
series product catalog or consult with your nearest Mitsubishi product provider.
Compliance with EC directive (CE Marking)
This product complies with EC directive, however, this document does not guarantee
that a mechanical system including this product will comply with EC directive.
Compliance to EMC directive and LVD directive for the entire mechanical module
should be checked by the user/manufacturer. For more information please consult with
your nearest Mitsubishi product provider.
Caution for EC Directive
•
Please use the programmable controllers while installed in conductive shielded
control panels under a general industrial environment.
•
Programmable controllers are open-type devices that must be installed and used
within conductive control panels. Please secure the control box lid to the control box
(for conduction). Installation within a control box greatly affects the safety of the
system and aids in shielding noise from the programmable controller.
•
For the control panel, use the product having sufficient strength, fire protectiveness
and shielding property to an installation environment.
•
24 V DC of the power supply must be supplied from the circuit double/reinforced
insulated from the main power supply (MAINS).
Caution for compliance with the LVD directive (EN61010-2-201:2013)
*1
•
To an external connection port other than AC power supply terminal and AC input/
output terminal, connect the circuit separated from a dangerous voltage by a
double/reinforced insulation.
•
Between the commons having the adjacent relay output terminals, if an external
power supply is higher than 120 V AC, the insulation is basic. Therefore, when
using 120 V AC or higher external power supply and 30 V DC/AC or lower external
power supply between the adjacent commons, do not handle 30 V DC/AC or lower
external power supply as a touchable part, (When handling 30 V DC/AC or lower
external power supply as a touchable part, add a basic insulation.)
•
Do not wire two or more crimp terminals to one terminal. (If the wiring with two or
more wires is needed, take an appropriate action such as adding an external
terminal.)
•
For crimp terminals to be used for the wiring applied with 30 V AC or higher, use the
products with insulating sleeves.
•
Cutoff device such as a breaker or a circuit protector should be installed in
accordance with the following precautions.
-
Use EN60947-1 or EN60947-3 standards.
-
Place the cutoff device so that it can be operated easily.
-
Specify that the cutoff device is for this equipment.
*1 For the time of compliance with the LVD directive (EN61010-2-201:2013), refer
to the manual of the PLC to be connected.
1. Outline
1.1 Outline
The FX
2N
-8EYR-S-ES/UL output extension block (hereinafter called FX
2N
-8EYR-S-
ES/UL) is a extension block to connect the FX
3G
/FX
3U
/FX
3UC
/FX
2N
/FX
2NC
/FX
1N
/
FX
1NC
Series main units.
FX
2N
-8EYR-S-ES/UL has 8 points relay outputs, and all output terminals have
separate reference terminals (Commons).
1.2 Communication Function
Check if the following product and items are included in the package:
1.3 External Dimensions, Part Names
Included Items
FX
2N
-8EYR-S-ES/UL
1 unit
Input/output number label
1 sheet
Dust proof protection sheet
1 sheet
Manuals (Japanese version, English version)
1 manual each
No.
Name
[1]
Extension cable
[2]
Top cover
[3]
Power LED
[4]
Direct mounting hole (mounting screw: M4 screw)
[5]
Output LED
[6]
Nameplate
[7]
DIN rail mounting groove
(DIN rail: DIN46277, 35mm (1.38") width)
[8]
DIN rail mounting hook
[9]
Output terminal block (M3 terminal screw)
[10]
Extension connector
87 (3.43")
80 (3.15")
(mounting hole pitch)
90 (3.55")
9 (0.36")
40 (1.58")
2- 4.5 mounting holes
[1] [2] [3] [4]
[5]
[6]
[7]
[8]
Unit: mm (inches)
MASS (weight): Approx. 0.3 kg (0.66 lbs)
Without cover
[9]
[10]
2. General specifications and Installation
DESIGN
PRECAUTIONS
•
Make sure to have the following safety circuits outside the PLC to ensure
safe system operation even during external power supply problems or PLC
failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop circuit, a
protection circuit, an interlock circuit for opposite movements (such as
normal vs. reverse rotation), and an interlock circuit (to prevent damage
to the equipment at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer
error, during self-diagnosis, all outputs are turned off. Also, when an error
that cannot be detected by the PLC CPU occurs in an input/output control
block, output control may be disabled.
External circuits and mechanisms should be designed to ensure safe
machinery operation in such a case.
3) Note that when an error occurs in a relay output device, the output could
be held either on or off.
For output signals that may lead to serious accidents, external circuits
and mechanisms should be designed to ensure safe machinery operation
in such a case.
DESIGN
PRECAUTIONS
•
Do not bundle the control line together with or lay it close to the main circuit
or power line. As a guideline, lay the control line at least 100mm (3.94") or
more away from the main circuit or power line.
Noise may cause malfunctions.
•
Install module so that excessive force will not be applied to the terminal
blocks.
Failure to do so may result in wire damage/breakage or PLC failure.
INSTALLATION
PRECAUTIONS
•
Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
INSTALLATION
PRECAUTIONS
•
Use the product within the generic environment specifications described in
PLC main unit manual (Hardware Edition).
Never use the product in areas with excessive dust, oily smoke, conductive
dusts, corrosive gas (salt air, Cl
2
, H
2
S, SO
2
, or NO
2
), flammable gas,
vibration or impacts, or expose it to high temperature, condensation, or rain
and wind.
If the product is used in such conditions, electric shock, fire, malfunctions,
deterioration or damage may occur.
•
Do not touch the conductive parts of the product directly.
Doing so may cause device failures or malfunctions.
•
Install the product securely using a DIN rail or mounting screws.
•
Install the product on a flat surface.
If the mounting surface is rough, undue force will be applied to the PC board,
thereby causing nonconformities.
•
When drilling screw holes or wiring, make sure that cutting and wiring debris
do not enter the ventilation slits of the PLC.
Failure to do so may cause fire, equipment failures or malfunctions.
•
Be sure to remove the dust proof sheet from the PLC's ventilation slits port
when installation work is completed.
Failure to do so may cause fire, equipment failures or malfunctions.
•
Connect the extension cables securely to their designated connectors.
Loose connections may cause malfunctions.
Notes
•
When a dust proof sheet is supplied with module, keep the sheet applied to
the ventilation slits during installation and wiring work.
•
To prevent temperature rise, do not install the PLC on a floor, a ceiling or a
vertical surface. Install it horizontally on a wall.
•
Keep a space of 50 mm or more between the module main body and another
device or structure. Install the module as far away as possible from high-
voltage lines, high-voltage devices and power equipment.
Failure to do so may cause fire, equipment failures or malfunctions.
2.1 General specifications
The general specifications are equivalent to the PLC main unit.
→
For general specifications, refer to the manual of the PLC main unit.
2.2 Installation
The product is mounted by the following method.
•
DIN rail mounting
•
Direct mounting (mounting screw: M4 screw)
For details, refer to the respective PLC manual.
3. Power supply/output specifications and examples of
external wiring
WIRING
PRECAUTIONS
•
Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING
PRECAUTIONS
•
When drilling screw holes or wiring, make sure cutting or wire debris does not
enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
•
Do not wire vacant terminals externally.
Doing so may damage the product.
•
Make sure to properly wire to the terminal blocks in accordance with the
following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit,
wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions described
in the manual
- Tightening torque should follow the specifications in the manual
- Tighten the screws using a Phillips-head screwdriver No.2 (shaft diameter
6 mm (0.24”) or less). Make sure that the screwdriver does not touch the
partition part of the terminal block.
STARTUP AND
MAINTENANCE
PRECAUTIONS
•
Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
* For repair, contact your local Mitsubishi Electric representative.
•
Do not drop the product or exert strong impact to it.
Doing so may cause damage.
•
Do not use the chemicals for cleaning.
•
If there is the possibility of touching the PLC inside a control panel in
maintenance, make sure to discharge to avoid the influence of static
electricity.
DISPOSAL
PRECAUTIONS
•
Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORTATION AND
STORAGE PRECAUTIONS
•
The product is a precision instrument. During transportation, avoid impacts
larger than those specified in the general specifications by using dedicated
packaging boxes and shock-absorbing palettes.
Failure to do so may cause failures in the product.
After transportation, verify operation of the product and check for damage of
the mounting part, etc.
3.1 Wiring
3.1.1
Cable end treatment and tightening torque
For the terminals of FX
2N
-8EYR-S-ES/UL, M3 screws are used.
The electric wire ends should be treated as shown below.
Tighten the screws to a torque of 0.5 to 0.8 N
•
m
Do not tighten terminal screws with a torque outside the above-mentioned range.
Failure to do so may cause equipment failures or malfunctions.
•
When one wire is connected to one terminal
<Reference>
•
When two wires are connected to one terminal
*1
<Reference>
*1 To adapt the LVD directive (EN61010-2-201:2013) of the EC directive, avoid the
wiring with two wires to the built-in terminal, and take an appropriate action such
as adding an external terminal.
For the time of compliance with the LVD directive (EN61010-2-201:2013), refer
to the manual of the PLC to be connected.
3.2 Power supply specifications
*1 For details on power supply connections, refer to the respective PLC manual.
Power supply specification is the same as the FX
2N
-8EYR(-ES/UL). When there
is not a description in the PLC manual, please select in the same way as the
FX
2N
-8EYR(-ES/UL).
Terminal
manufacturer
Type No.
Applicable
cable
Certification
Pressure
bonding tool
J.S.T. Mfg.
Co., Ltd.
FV1.25-B3A
AWG22 to 16
UL Listed
YA-1 (J.S.T. Mfg.
Co., Ltd.)
FV2-MS3
AWG16 to 14
Terminal
manufacturer
Type No.
Applicable
cable
Certification
Pressure
bonding tool
J.S.T. Mfg.
Co., Ltd.
FV1.25-B3A
AWG22 to 16
UL Listed
YA-1 (J.S.T. Mfg.
Co., Ltd.)
Item
Specifications
Internal 24V DC
*1
24V DC 75mA
24V DC power is either supplied internally from the main unit or
input/output extension unit, or from an extension power supply
unit.
5V DC
*1
5V DC 30mA
5V DC power is either supplied internally from the main unit or
input/output extension unit, or from an extension power supply
unit.
3.2 (0.13")
6.2 mm (0.24")
or less
Terminal
screw
Solderless
terminal
6.2 mm (0.24")
or less
3.2 (0.13")
Terminal
6.3 mm(0.25")
or more
6.3 mm(0.25")
or more
6.2 mm (0.24")
or less
6.2 mm (0.24")
or less
3.2 (0.13")
3.2 (0.13")
Terminal
Terminal
screw
Solderless
terminal
3.3 Output specifications and example of external wiring
3.3.1
Relay output specifications
3.3.2
Example of relay output wiring
4. Terminal layouts
Item
Output specifications
Number of output points
8 points (All points have separate reference
terminals (Commons))
Output connecting type
Terminal block
Output form
Relay
External power supply
30V DC or less, 240V AC or less
(Between 250V and 240V CE, UL, and cUL are not
compliant.)
Max. load
Resistance
load
2A/1point
Inductive
load
80VA/1point
Min. load
5V DC, 2mA (reference value)
Open circuit leakage current
-
Response
time
OFF
→
ON
Approx. 10ms
ON
→
OFF
Circuit insulation
Mechanical insulation
Display of output operation
LED lights when power is applied to relay coil.
FX
2N
-8EYR-S-ES/UL
24V DC
100V AC
Fuse
Y0
Y0
Load
Fuse
Y7
Y7
Load
Y0
Y1
Y2
Y3
Y3
Y4
Y4
Y5
Y7
Y7
Y6
Y6
Y5
Y0
Y1
Y2
含有有害6物质的名称,含有量,含有部品
本产品中所含有的有害6 物质的名称,含有量,含有部品如下表所示。
产品中有害物质的名称及含量
本表格依据SJ/T 11364的规定编制。
○:表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572
规定的限量要求以下。
×:表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T
26572规定的限量要求。
部件名称
有害物质
铅
(Pb)
汞
(Hg)
镉
(Cd)
六价铬
(Cr(VI))
多溴联苯
(PBB)
多溴
二苯醚
(PBDE)
可编程
控制器
外壳
印刷基板
○
○
○
○
○
○
○
○
○
○
○
×
「电器电子产品有害物质限制使用标识要求」的表示方式
Note: This symbol mark is for China only.
FX
2N
-8EYR-S-ES/UL
HARDWARE MANUAL
This manual describes the part names, dimensions, mounting, and specifications
of the product. Before use, read this manual and the manuals of all relevant
products fully to acquire proficiency in handling and operating the product. Make
sure to learn all the product information, safety information, and precautions.
Store this manual in a safe place so that it can be taken out and read whenever
necessary. Always forward it to the end user.
Registration:
Phillips is a registered trademark of Phillips Screw Company.
The company and product names described in this manual are registered
trademarks or the trademarks of their respective companies.
Effective December 2017
Specifications are subject to change without notice.
Manual Number
JY997D40801
Revision
C
Date
December 2017