background image

PRE-OPERATION INSTRUCTIONS

11

1

NOTE

 • Do not operate the keys with sharp tools.
 • Do not press the LCD part.
 • Do not peel off the waterproof seal affixed to the FR-LU08-01. If the seal is peeled off, the FR-LU08-01 does not 

conform to IP55.

g

FR-LU08

PU/EXT key

Switches the operation mode between PU, PUJOG, and External.

FR-LU08-01

HAND/AUTO key

Switches the operation mode between HAND (PU), HANDJOG (PUJOG), and AUTO 
(External).

h

MON key

Displays the first priority monitor.

i

MENU key

Displays the Quick menu.
Displays the Function menu when the key is pressed while the Quick menu is displayed.

j

Software key (F1)

Select an operation displayed on the monitor.

k

Software key (F2)

l

Software key (F3)

m

Connector

Connector to the inverter. Connect this connector to the PU connector of the inverter.

n

For manufacturer setting. Do not use. Do not peel off the waterproof seal affixed to the FR-LU08-01.

o

Battery cover

Remove the battery cover when replacing the backup battery for the real time clock function.

p

Rating plate

-

Symbol

Name

Description

Summary of Contents for FR-LU08

Page 1: ...PRE OPERATION INSTRUCTIONS 1 FUNCTION AND BASIC OPERATION 2 MENU 3 CHECK FIRST WHEN YOU HAVE TROUBLE 4 SPECIFICATIONS 5 INSTRUCTION MANUAL INVERTER Option unit FR LU08 FR LU08 01 LCD Operation Panel ...

Page 2: ...ause these are important to personal safety Warning Do not remove the front cover or the wiring cover of the inverter while the inverter power is ON Do not operate the inverter with any cover or wiring cover removed as accidental contact with exposed high voltage terminals and internal components may occur resulting in an electrical shock Do not remove the inverter front cover even if the power su...

Page 3: ...ore starting operation each parameter must be confirmed and adjusted A failure to do so may cause some machines to make unexpected motions Warning Usage Since pressing the STOP RESET key of the operation panel may not stop output depending on the function setting status separate circuit and switch that make an emergency stop power OFF mechanical brake operation for emergency stop etc must be provi...

Page 4: ...of or IP5X dustproof ratings Although the FR LU08 01 except for the connector is rated with the IPX5 waterproof and IP5X dustproof ratings it is not intended for use in water Also the ratings do not guarantee protection of the FR LU08 01 from needless submersion in water or being washed under strong running water such as a shower Do not pour or apply the following liquids over the FR LU08 01 water...

Page 5: ...nitor function 17 2 1 1 Outline of the Main monitor indicator 17 2 1 2 Using the real time clock function 20 2 1 3 Switching between the Main monitor screen and the Menu screens 20 2 1 4 Changing the Main monitor screen 21 2 1 5 Changing the main monitor item from the Function menu 22 2 1 6 Changing the main monitor item by parameter 22 2 1 7 Setting of the monitor data screen at power ON first pr...

Page 6: ...arameter clear 34 3 2 2 Inverter reset 34 3 2 3 Terminal assignment 34 3 2 4 Parameter copy 35 3 2 5 Option installation monitor 37 3 2 6 USB memory 38 4 CHECK FIRST WHEN YOU HAVE TROUBLE 45 4 1 Troubleshooting 45 5 SPECIFICATIONS 46 5 1 Standard specifications 46 5 2 Outline and enclosure cut dimensions 47 Appendix 48 Appendix 1 Disposing of equipment in EU countries 48 Appendix 2 Restricted Use ...

Page 7: ...page 24 FR A820 00046 0 4K to 04750 90K FR A840 00023 0 4K to 06830 280K FR A842 07700 315K to 12120 500K FR A846 00023 0 4K to 03610 132K MADE in Japan 55 or later MADE in China 56 or later FR F820 00046 0 75K to 04750 110K FR F840 00023 0 75K to 06830 315K FR F842 07700 355K to 12120 560K MADE in Japan 54 or later MADE in China 55 or later Parameter information refer to page 29 FR A820 00046 0 4...

Page 8: ... of one symbol two characters indicating the production year and month and six characters indicating the control number The last digit of the production year is indicated as the Year and the Month is indicated by 1 to 9 X October Y November or Z December 1387 02 5 287387 6 5 0 1 SERIAL number Country of origin ...

Page 9: ... Separated converter type IP55 compatible model Protective structure IP40 except for the PU connector IP55 except for the PU connector Outline dimension W H D mm 72 78 5 17 80 96 19 Number of fixing screws 2 4 Operation mode indicator PU EXT HAND AUTO Operation key PU EXT key HAND AUTO key Installation on the enclosure Available Not available ...

Page 10: ...rward operation REV key Starts the reverse operation e STOP RESET key Stop operation commands Reset the inverter when the protective function is activated f Setting dial Used to change the frequency and parameter settings Press the setting dial while the fault history is displayed to display the details of the fault Displays a description of the parameter when the setting dial is held down in the ...

Page 11: ...al h MON key Displays the first priority monitor i MENU key Displays the Quick menu Displays the Function menu when the key is pressed while the Quick menu is displayed j Software key F1 Select an operation displayed on the monitor k Software key F2 l Software key F3 m Connector Connector to the inverter Connect this connector to the PU connector of the inverter n For manufacturer setting Do not u...

Page 12: ...emoval of the operation panel refer to the Instruction Manual of the inverter 2 Align the connector of the FR LU08 01 with the PU connector of the inverter and insert the operation panel After confirming that the operation panel is fit securely tighten the screws For the FR LU08 01 tighten the screws in a diagonal order Tightening torque 0 40 to 0 45 N m for the FR LU08 0 39 to 0 49 N m for the FR...

Page 13: ...3 1 Removal 1 Loosen the screws on the FR LU08 01 These screws cannot be removed 2 Push the upper part of the FR LU08 01 and pull out the operation panel to remove FR LU08 FR LU08 FR LU08 01 FR LU08 01 Loosen Loosen Loosen Loosen ...

Page 14: ...uction Manual of the inverter 2 Securely insert one end of the connection cable into the PU connector of the inverter and the other end into the connection connector of the FR LU08 01 along the guides until the stoppers are fixed Removal Hold down the clip at the cable end and gently pull the connector NOTE The IP55 compatible inverter model does not conform to IP55 when the FR LU08 01 is removed ...

Page 15: ... Loosen the screw on the battery cover which is located on the back side of the FR LU08 01 NOTE Do not replace the battery of the FR LU08 01 while power is ON Do not use batteries that have been dropped or otherwise received an impact Battery leakage may occur Discard the batteries 2 Insert a flathead screwdriver to the slot and lift the cover to open 3 Place the battery as shown in the right figu...

Page 16: ...ration panel can be enabled or disabled 1 5 3 PU contrast adjustment Pr 991 With Pr 991 PU contrast adjustment the contrast of the monitor display of the operation panel can be adjusted NOTE For how to set parameters refer to page 26 Pr 990 setting Description 0 Without beeping sound 1 initial value With beeping sound Pr 991 setting Description 0 to 63 P R E V S E T N E X T Language S T O P P U Ja...

Page 17: ...Changing the Main monitor screen using or Refer to page 21 Changing the main monitor item using the Function menu Refer to page 22 Changing the main monitor item using Pr 52 Operation panel main monitor selection Refer to page 22 b Rotation direction Displays the direction of the start command STF forward STR reverse shows that no start command is input or that both forward and reverse directions ...

Page 18: ...leted TUNE highlighted and flashing Tuning error f USB connection password locked Displays the connection status of the USB A connector of the inverter and password function setting status USB A USB connection recognized USB A highlighted USB ready USB A flashing During USB operation LOCK Password locked g PLC function JOG operation Displays the status of the PLC function and JOG operation P RUN D...

Page 19: ... PU combined operation mode k Software key Displays operations performed by pressing the F1 left F2 center or F3 right key l Scroll Displayed when any data can be scrolled by turning Operation mode indicator FR LU08 FR LU08 01 Indication of EXT PU Indication of AUTO HAND Symbol Name Description P R E V S E T N E X T S T O P P U H z 1 2 3 4 0 00 P R E V S E T N E X T S T O P X T H z 1 2 3 4 0 00 E ...

Page 20: ...y is installed When the battery is not installed the FR LU08 01 reads the time from the inverter and starts time counting 2 1 3 Switching between the Main monitor screen and the Menu screens Pressing or switches the monitor display between the Main monitor screen and the Menu screens PREV SET NEXT STOP PU Hz Output frequency 1 2 3 4 P R E V S E T N E X T Easy setup wizard Pr list for App Simple Pr...

Page 21: ...yed only when new monitor item is registered from the Function menu Faults history 1 2 3 4 1 OHT 2 SER 3 OV2 4 OV2 5 OV2 6 OV2 7 OV3 8 T A Output current 1 2 3 4 Hz Set Frequency 1 2 3 4 V Output voltage 1 2 3 4 0 00 60 00 0 0 Output Hz Output I 1 2 3 4 0 00Hz 0 00A 0 0V PREV SET NEXT STOP PU Hz Output frequency 1 2 3 4 0 00 PREV SET NEXT STOP PU PREV SET NEXT STOP PU PREV SET NEXT STOP PU PREV CL...

Page 22: ...e monitor item on the third monitor screen can be changed However the item on the second monitor screen is changed accordingly when 17 load meter 18 motor excitation current or 24 motor load factor is set in Pr 52 2 1 7 Setting of the monitor data screen at power ON first priority monitor Set the monitor screen as the first priority monitor that is displayed first at power ON or when is pressed Wh...

Page 23: ...witch back the monitor display from the Frequency setting screen to the Main monitor screen press NOTE If the external start signal STF or STR is ON the External operation mode cannot be switched to the PU operation mode The screen can be switched to the Extended direct screen depending on the setting of Pr 1000 Direct setting selection Refer to page 24 SET BACK BACK SET STOP PU Frequency Setting ...

Page 24: ...requency setting screen to the Main monitor screen press Pr 1000 setting Description 0 Initial value Displays the Frequency setting screen 1 Displays the Direct set point setting screen 2 Displays the Direct set point setting screen and the Frequency setting screen SET One of the Main monitor screen Example of screen switching and shifting when the PID control is enabled Pr 128 0 Direct 1 screen 5...

Page 25: ...st eight faults can be checked by pressing How to clear the fault history Press while the fault history is displayed to display a confirmation screen for the fault history clear Press to clear the fault history and to return to the fault history screen BACK STOP PU Latest fault OC During Dec 2014 02 04 10 00 Frequency 60 00Hz PREV NEXT 1 2 3 4 NEXT CLR SET BACK ...

Page 26: ...elect the parameter number by turning Press to display the present set value PrSET Parameter setting P S E T T Parameter No input Parameter No SET P R E V S E T N E X T SET Pr SET STOP PU Quick menu LIST STOP PU 0000 BACK Easy setup wizard Pr list for App Simple Pr list SET BACK SET NEXT STOP PU 8 Dec time Pres value 5 0 sec 5 0 sec 0 3600 Set value 3 Turn to set the value to 180 0 and press The s...

Page 27: ...ST Group parameter setting P S E T T Function group Menu E Environm setting F Acc Dec D Opr Freq command SET BACK STOP PU Quick menu STOP PU Easy setup wizard Pr list for App Simple Pr list SET BACK SET STOP PU F Acc Dec 0 Time setting 1 Pattern setting 2 Backlash SET BACK SET STOP PU F0 Time setting 00 Acc Dec ref F 01 Time increments 02 JOG Acc Dcc time 4 Turn to move the cursor to 11 Dec time a...

Page 28: ...ameters SET P R E V S E T N E X T Parameter list Set parameter list Initial value list BACK SET STOP PU SET SKIP P R E V S E T Initial value list 0 Torque 1 Max fr 2 Min fr 6 0 120 0 0 00 BACK SET STOP PU SKIP 3 Turn to move the cursor to 8 Dec time and press The present set value is displayed 4 Turn to set the value to 180 0 and press The set value is changed 5 Press to display the next parameter...

Page 29: ...erter In the initial setting 0 is set in Pr 77 Parameter write selection and thus parameters can be written only while the inverter is stopped The parameters can be read even during the operation Note that some parameters can be always written For the details of Pr 77 refer to the Instruction Manual of the inverter In the following cases set values cannot be written 1 When the parameter number sel...

Page 30: ...ng the wizard guide 30 Parameter list by application Pr list for App The parameters related to each application of the inverter can be set 31 Simple setup list Simple Pr list Frequently used functions parameters can be set 32 Item Induction motor Magnet motor Applied motor Control method Control mode Motor capacity Number of motor poles Rated motor current Rated motor voltage Rated motor frequency...

Page 31: ...U Induction motor BACK S E T N E X T Please choose the kind of induction motor NEXT STOP PU SF JR under 1 5kW BACK S E T N E X T Please choose the control method NEXT STOP PU V F control BACK S E T N E X T Please input the number of motor poles NEXT STOP PU 4 Screen examples of Easy setup wizard SET SET BACK S E T N E X T Select application Common Fan Pump SET STOP PU BACK S E T N E X T Fan 78 Rev...

Page 32: ...apacity Number of motor poles Auto tuning Control method selection Auto tuning setting Minimum frequency High speed maximum frequency Acceleration time Deceleration time Operation mode selection Language selection Item SF JR under 1 5kW SET SET SET SET BACK S E T N E X T Simple Pr list SET STOP PU Motor setting Auto tuning Min frequency BACK S E T N E X T Motor setting SET STOP PU Motor type Curre...

Page 33: ...t Resets the inverter 34 Terminal assignment Displays the signals assigned to the I O terminals of the control circuit and the ON OFF status of the signals 34 Parameter copy Parameter copy reading writing and verifying can be performed 35 Software version S W Version Displays the software control numbers of the inverter Option installation monitor Option Instl Mntr Displays the plug in options con...

Page 34: ... s protective function has been activated and the inverter has tripped output shut off the inverter reset can be executed only by pressing The inverter reset can also be executed by turning the inverter OFF and then ON or turning ON the RES signal For the details refer to the Instruction Manual of the inverter 3 2 3 Terminal assignment Displays the signals assigned to the I O terminals of the cont...

Page 35: ...the copy area for parameter setting storage and press 4 Turn to move the cursor to 1 Read VFD and press SET BACK S E T N E X T Parameter copy CopyArea1 CopyArea2 CopyArea3 SET STOP PU SET BACK S E T N E X T CopyArea1 1 Read VFD 2 Write VFD 3 Verifying SET STOP PU SET 5 A name up to 9 letters can be entered for the selected area Turn to select 0 to 9 A to Z _ or space Press to move the cursor Press...

Page 36: ... A confirmation screen appears for writing the parameters Press to write the parameters SET P R E V S E T N E X T Parameter copy CopyArea1 ABCDEFGHI CopyArea2 CopyArea3 SET STOP PU K BACK SET BACK S E T N E X T CopyArea1 ABCDEFGHI 1 Read VFD 2 Write VFD 3 Verifying SET STOP PU SET BACK S E T 2 Write VFD ABCDEFGHI Write Area 1 to VFD SET Execution BACK Cancel S E T S E T S E T SET STOP PU SET 6 Pre...

Page 37: ...nd press 4 Turn to select the target copy area and press 5 Turn to move the cursor to 3 Verifying and press 6 A confirmation screen appears for verification Press to execute the verification P R E V S E T N E X T Function menu Terminal assignment Parameter copy S W Version SET STOP PU SET P R E V S E T N E X T Parameter copy CopyArea1 ABCDEFGHI CopyArea2 CopyArea3 SET STOP PU K BACK SET BACK S E T...

Page 38: ...ve the cursor to USB Parameter Copy and press 4 Turn to move the cursor to AutoNumberedNewFile and press If File Name Select has been selected a file number selection screen appears SET BACK S E T N E X T USB Memory Device USB Parameter Copy PLC Project Copy SET STOP PU SET BACK S E T N E X T USB Parameter Copy AutoNumberedNewFile File Name Select SET STOP PU SET 5 A confirmation screen appears fo...

Page 39: ...le and press SET BACK S E T N E X T USB Memory Device USB Parameter Copy PLC Project Copy SET STOP PU SET AutoNumberedNewFile File Name Select USB Parameter Copy BACK S E T N E X T SET STOP PU SET BACK S E T N E X T USB Parameter Copy File Name Select SET STOP PU CP001 SET 6 Turn to move the cursor to 1 Copy INV to USB and press 7 A confirmation screen appears for execution Press to execute the co...

Page 40: ...arameter Copy PLC Project Copy SET STOP PU SET AutoNumberedNewFile File Name Select USB Parameter Copy BACK S E T N E X T SET STOP PU SET BACK S E T N E X T USB Parameter Copy File Name Select SET STOP PU CP001 SET 6 Turn to move the cursor to 2 Write USB to INV and press 7 A confirmation screen appears for execution Press to write the parameters 8 Press to reset the inverter BACK S E T N E X T SE...

Page 41: ...rget file and press SET BACK S E T N E X T USB Memory Device USB Parameter Copy PLC Project Copy SET STOP PU SET AutoNumberedNewFile File Name Select USB Parameter Copy BACK S E T N E X T SET STOP PU SET BACK S E T N E X T USB Parameter Copy File Name Select SET STOP PU CP001 SET 7 Turn to move the cursor to 3 Verify and press 8 A confirmation screen appears for execution Press to execute the veri...

Page 42: ...e cursor to the target file and press 5 Turn to move the cursor to 1 Copy INV to USB and press SET BACK S E T N E X T USB Memory Device USB Parameter Copy PLC Project Copy SET STOP PU SET BACK S E T N E X T PLC Project Copy Folder Name Select SET STOP PU PRG01 SET BACK S E T N E X T SET STOP PU PLC Prjct Copy PRG01 1 Copy INV to USB 2 Write USB to INV 3 Verify SET 6 A confirmation screen appears f...

Page 43: ...o 2 Write USB to INV and press SET BACK S E T N E X T USB Memory Device USB Parameter Copy PLC Project Copy SET STOP PU SET BACK S E T N E X T PLC Project Copy Folder Name Select SET STOP PU PRG01 SET BACK S E T N E X T SET STOP PU PLC Prjct Copy PRG01 1 Copy INV to USB 2 Write USB to INV 3 Verify SET 6 A confirmation screen appears for execution Press to write the project 7 Press to reset the inv...

Page 44: ... E T N E X T USB Memory Device USB Parameter Copy PLC Project Copy SET STOP PU SET BACK S E T N E X T PLC Project Copy Folder Name Select SET STOP PU PRG01 SET 6 Turn to move the cursor to 3 Verify and press 7 A confirmation screen appears for execution Press to execute the verification 8 If a verification error occurs the verification is stopped and an error screen appears Press to return to the ...

Page 45: ... operation panel Check that the operation panel is properly connected Check that the PU cable is fully inserted into the PU connector Check the connection of the operation panel and the PU cable The setting of Pr 991 PU contrast adjustment has changed from the initial value Check the Pr 991 setting Using the FR DU08 01 return the setting of Pr 991 to the initial value During inverter reset the fol...

Page 46: ...m Specifications Surrounding air temperature 10 C to 50 C non freezing Surrounding air humidity FR LU08 90 RH or less non condensing FR LU08 01 95 RH or less non condensing Storage temperature 20 C to 65 C Atmosphere Indoors free from corrosive gas flammable gas oil mist dust and dirt Altitude vibration Maximum 2500 m 5 9 m s2 or less at 10 to 55 Hz directions of X Y Z axes Power supply Power inpu...

Page 47: ...ction cable FR CB2 is connected to the operation panel connection connector FR ADP The combined length of the two connectors will be different if other 3rd party operation panel connection cables are used Outline drawing Panel cutting dimension drawing 66 72 5 21 5 22 20 2 M3 screw Air bleeding hole Operation panel connection cable FR CB2 option Unit mm 19 80 0 5 3 5 0 3 96 5 0 5 89 5 0 3 68 0 5 5...

Page 48: ...Please dispose of this equipment at your local community waste collection recycling centre if it is to be disposed of in EU countries In the European Union there are separate collection systems for used electronic products Please help us to conserve the environment we live in NOTE This symbol is for EU countries only This symbol is according to the directive 2006 66 EC Article 20 Information for e...

Page 49: ... of the Use of Hazardous Substances in Electrical and Electronic Products of the People s Republic of China 电器电子产品有害物质限制使用标识要求 本产品中所含有的有害物质的名称 含量 含有部件如下表所示 产品中所含有害物质的名称及含量 上表依据SJ T11364的规定编制 表示该有害物质在该部件所有均质材料中的含量均在GB T26572规定的限量要求以下 表示该有害物质在该部件的至少一种均质材料中的含量超出GB T26572规定的限量要求 即使表中记载为 根据产品型号 也可能会有有害物质的含量为限制值以下的情况 根据产品型号 一部分部件可能不包含在产品中 环境保护使用期限标识 部件名称 有害物质 铅 Pb 汞 Hg 镉 Cd 六价铬 Cr VI 多溴联苯 PBB 多溴二苯醚 PBDE...

Page 50: ...50 MEMO IB NA 0600539ENG F ...

Page 51: ...st edition Dec 2014 IB NA 0600539ENG B Addition FR LU08 01 May 2015 IB NA 0600539ENG C Addition Easy setup wizard Parameter list by application Extended direct setting Oct 2015 IB NA 0600539ENG D Modification Language selection Jun 2018 IB NA 0600539ENG E Addition Parameter information Nov 2018 IB NA 0600539ENG F Modification Language selection ...

Page 52: ...ntrol circuit and the ON OFF status of the signals The terminal status of the plug in option can be checked if a plug in option FR A8AX or FR A8AY is installed Correct Displays the signals assigned to the I O terminals of the control circuit and the ON OFF status of the signals The terminal status of the plug in option can be checked if a plug in option FR A8AY and FR A8AR are installed individual...

Page 53: ...INVERTER IB NA 0600539ENG F 1811 MEE Printed in Japan Specifications subject to change without notice HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Reviews: