![Mitsubishi Electric FR-HEL-0.4K Instruction Manual Download Page 49](http://html.mh-extra.com/html/mitsubishi-electric/fr-hel-0-4k/fr-hel-0-4k_instruction-manual_1811890049.webp)
17
Outline Dimension Drawings
ENGLISH
FR-HEL-H15K to H55K
Maximum size (The size changes according to the bending of the cable.)
P
P1
H
H1
H2
W
W1
D2
D3
D1
Max D *1
Earth (ground) terminal
Terminal screw
Installation screw
FR-HEL-H[]K
Motor
Capacity
(kW)
Rated
current
value
(A)
Inductance
(mH)
D
D1 D2 D3
W W1
H
H1 H2
Terminal
screw
Installation
screw
Earth
(ground)
Terminal
Mass
(kg)
15
15
27.5
1.77
125 57 115 95
105 75
152 130 111 M6
M5
M5×10 5
18.5
18.5
33.9
1.44
120 55 100 80
114 75
162 140 121 M6
M5
M5×10 5
22
22
40.3
1.21
120 55 95
75
133 90
180 157 137 M6
M5
M5×10 6
30
30
55
0.9
120 58 100 80
133 90
180 157 137 M6
M5
M5×10 6.5
37
37
67.5
0.73
155 70 120 100 133 90
184 161 137 M8
M5
M5×10 8.5
45
45
81.9
0.6
170 71 130 110 133 90
184 161 137 M8
M5
M5×10 10
55
55
98.7
0.49
170 65 126 106 152 105 203 180 156 M8
M6
M6×12 11.5
(Unit: mm)
Summary of Contents for FR-HEL-0.4K
Page 4: ...1 目 次 1 製品の確認 2 2 据 付 け 3 3 配 線 4 4 電線サイズと圧着端子 5 5 仕 様 7 6 外形寸法図 8 付録 20 ...