![Mitsubishi Electric FR-HEL-0.4K Instruction Manual Download Page 37](http://html.mh-extra.com/html/mitsubishi-electric/fr-hel-0-4k/fr-hel-0-4k_instruction-manual_1811890037.webp)
5
Cable Size and Crimping Terminal
ENGLISH
4
Cable Size and Crimping Terminal
Refer to
page
for the wiring of terminals P and P1 and the earthing cable.
(1) 200V class
Torque value (reference value) for the iron screws with the 4.6 strength rating. Use the
tightening torque recommended for the applied screw (bolt).
This cable gauge is with the continuous maximum permissible temperature of 75°C (HIV
cable (600 V class 2 vinyl-insulated cable), etc.). Assumes that the surrounding air
temperature is 50°C or less and the wiring distance is 20 m or less.
This cable gauge is with continuous maximum permissible temperature of 75°C (THHW
cable). This assumes a surrounding air temperature of 40°C or lower and in-enclosure
wiring. (For the use in the United States or Canada, refer to Appendix 1 Instructions for UL
and cUL.)
FR-HEL-[]K
P, P1
Earth (Ground) Cable
Terminal
Screw
Size
Tightening
torque
N•m
Crimping
Terminal
HIV
Cable
Size
(mm
2
)
AWG
Terminal
Screw
Size
Tightening
torque
N•m
Crimping
Terminal
HIV
Cable
Size
(mm
2
)
0.4 to 2.2
M4
1.5
2-4
2
14
M4×8
1.5
2-4
2
3.7
M4
1.5
5.5-4
3.5
12
M4×8
1.5
5.5-4
3.5
5.5
M4
1.5
5.5-4
5.5
10
M4×8
1.5
5.5-4
5.5
7.5
M5
2.5
14-5
14
6
M4×8
1.5
5.5-4
5.5
11
M6
3.8
14-6
14
6
M6×12
3.8
8-6
8
15
M6
3.8
22-6
22
4
M6×12
3.8
14-6
14
18.5
M8
13.2*1
38-8
38
2
M6×12
3.8
14-6
14
22
M10
26.5*1
38-10
38
2
M6×12
3.8
22-6
22
30
M10
26.5*1
60-10
60
1/0
M6×12
3.8
22-6
22
37
M10
26.5*1
80-10
80
3/0
M6×12
3.8
22-6
22
45, 55
M12
46.1*1
100-12
100
4/0
M6×12
3.8
38-6
38
75
M12
46.1*1
150-12
125
250
M6
4.4
38-6
38
90
M12
46.1*1
150-12
150
300
M6
4.4
38-6
38
110
M12
46.1*1
100-12
2
100
2×4/0 M6
4.4
60-6
60