Limiting the output frequency
4.5 Limiting the output frequency
4.5.1
Maximum/minimum frequency (Pr. 1, Pr. 2, Pr. 18)
The above parameters can be set when
Pr. 160 Extended function display selection
= "0". (
Performing IPM parameter initialization changes the settings.
Even if a value higher than the maximum motor frequency
is set in
Pr. 18
under IPM motor control, the high speed maximum frequency is
limited to the maximum motor frequency
(2) Set minimum frequency
Use
Pr. 2 Minimum frequency
to set the minimum frequency.
If the set frequency is less than
Pr. 2
, the output frequency is clamped at
Pr. 2
(will not fall below
Pr. 2
).
Purpose
Parameter that should be Set
Refer to Page
Set upper limit and lower limit of
output frequency
Maximum/minimum
frequency
Pr. 1, Pr. 2, Pr. 18
Perform operation by avoiding
mechanical resonance points
Frequency jump
Pr. 31 to Pr. 36, Pr. 552
Motor speed can be limited.
Clamp the upper and lower limits of the output frequency.
Parameter
Number
Name
Initial Value
Setting Range
Description
1
Maximum frequency
120Hz
0 to 120Hz
Upper limit of the output frequency.
2
Minimum frequency
0Hz
0 to 120Hz
Lower limit of the output frequency.
18
High speed maximum
frequency
120Hz
120 to 400Hz
Set when performing the operation at 120Hz
or more.
(1) Set maximum frequency
Use
Pr. 1 Maximum frequency
to set the maximum frequency. If the
value of the frequency command entered is higher than the setting,
the output frequency is clamped at the maximum frequency.
To operate with a frequency higher than 120Hz under V/F control or
General-purpose magnetic flux vector control, set the upper limit for
the output frequency in
Pr. 18
High speed maximum frequency
.
(When
Pr. 18
is set,
Pr. 1
automatically switches to the frequency of
Pr. 18
. Also, when
Pr. 1
is set,
Pr. 18
is automatically changed to the
frequency set in
Pr. 1
.)
REMARKS
To operate with a frequency higher than 60Hz (rated IPM motor frequency under IPM motor control
) using
frequency-setting analog signals, change the
Pr. 125 (Pr. 126)
(frequency setting gain) setting. Changing only
Pr.1
and
Pr.18
does
not allow the operation with a frequency higher than 60Hz (rated IPM motor frequency under IPM motor control.
Under IPM motor control, the estimated output frequency (rotations per minute) is used to limit the frequency. Therefore, a
value equal to or higher than the upper limit frequency may be displayed in the monitor.
REMARKS
When
Pr. 15 Jog frequency
is equal to or less than
Pr. 2
, the
Pr. 15
setting has precedence over the
Pr. 2
setting.
When stall prevention is activated to decrease the output frequency, the output frequency may drop to
Pr. 2
or below.
Under IPM motor control, the estimated output frequency (rotations per minute) is used to limit the frequency. Therefore, the
value displayed in the monitor may reach the lower limit frequency or lower.
CAUTION
Note that when
Pr. 2
is set to any value equal to or more than
Pr. 13 Starting frequency
, simply turning ON the start signal will
run the motor at the preset frequency according to the set acceleration time even if the command frequency is not input.
Parameters referred to
Pr. 13 Starting frequency
Pr. 15
Jog frequency
Pr. 125 Terminal 2 frequency setting gain frequency, Pr. 126 Terminal 4 frequency setting gain frequency
Output frequency
(Hz)
Pr. 1
Pr. 18
Pr. 2
Frequency setting
Clamped at the
maximum frequency
Clamped at the
minimum frequency
5, 10V
(20mA)
0
(4mA)