15. (A) Application Parameters
15.1 Brake sequence function
15
(A) Application Parameters
15.1
Brake sequence function
This function outputs operation timing signals of the mechanical brake from the inverter, such as for lift applications.
This function is useful in preventing load slippage at a start due to poor mechanical brake timing and overcurrent alarm in stop
status and enable secure operation.
Purpose
Parameter to set
Refer to
page
To stop the motor with a mechanical
brake (operation timing of mechanical
brake)
Brake sequence function
P.A100 to P.A107,
P.F500, P.A108,
P.A109
Pr.278 to Pr.285, Pr.292,
Pr.639, Pr.640
To stop the motor with a mechanical
brake (vibration control at stop-on-
contact)
Stop-on-contact control
P.A200, P.A205,
P.A206
Pr.270, Pr.275, Pr.276
To strengthen or weaken the frequency
at a constant cycle
Traverse operation
P.A300 to P.A305
Pr.592 to Pr.597
To perform process control, such as for
the pump flow volume and air volume
PID control
P.A601 to P.A604,
P.A607, P.A610 to
P.A615, P.A621 to
P.A625
Pr.127 to Pr.134, Pr.553,
Pr.554, Pr.575 to Pr.577,
Pr.609, Pr.610, Pr.1015
PID display adjustment
P.A630 to P.A633
C42 to C45 (Pr.934,
Pr.935)
To control the dance roll for winding/
unwinding
Dancer control
P.A601, P.A602,
P.A610, P.A611,
P.A613 to P.A615,
P.A624, P.A625,
P.F020 to P.F021
Pr.44, Pr.45, Pr.128 to
Pr.134, Pr.609, Pr.610
To restart without stopping the motor at
instantaneous power failure
Automatic restart after
instantaneous power failure
/ flying start function for
induction motors
P.A700 to P.A703,
P.A710, P.F003
Pr.57, Pr.58, Pr.162,
Pr.165, Pr.299, Pr.611
Frequency search accuracy
improvement (V/F control,
offline auto tuning)
P.A700, P.A711,
P.A712, P.C110,
P.C210
Pr.96, Pr.162, Pr.298,
Pr.463, Pr.560
Automatic restart after
instantaneous power failure
/ flying start function for PM
motors
P.A700, P.A702,
P.F003
Pr.57, Pr.162, Pr.611
To decelerate the motor to a stop at
power failure
Power failure time
deceleration-to-stop
function
P.A730
Pr.261
To operate with sequence program
PLC function
P.A800, P.A801,
P.A804, P.A805,
P.A810 to P.A859
Pr.414, Pr.415, Pr.498,
Pr.675, Pr.1150 to
Pr.1199
To store the operating status of the
inverter in the RAM in the inverter
Trace function
P.A900, P.A902 to
P.A906, P.A910 to
P.A920, P.A930 to
P.A939
Pr.1020, Pr.1022 to
Pr.1047
Magnetic flux
Magnetic flux
Magnetic flux Sensorless
Sensorless
Sensorless Vector
Vector
Vector
Pr.
Name
Initial
value
Setting
range
Description
278
A100
Brake opening frequency
3 Hz
0 to 30 Hz
Set the frequency value calculated by adding approx. 1.0 Hz to the
rated slip frequency. This can be set only when
Pr.278
≤
Pr.282
.
279
A101
Brake opening current
130%
0% to 400%
Set between 50% and 90% because load slippage is more likely to
occur when a start setting is too low.
The inverter rated current is regarded as 100%, or the rated motor
torque is regarded as 100%. (According to
Pr.639
setting)
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...