Parameter
MODBUS®/TCP (FR-E700 SC ENE)
FR-E700 SC EC/ENE
6 - 345
MODBUS® register
●
The following shows the MODBUS® registers for system environment variables (read/write), real
time monitor items (read), parameters (read/write), faults history data (read/write), and model
information monitor items (read).
●
System environment variables
햲
Settings in the communication parameters are not cleared.
햳
The data is written as a control input command for writing.
The data is read as the inverter status for reading.
햴
The data is written as an operation mode setting for writing.
The data is read as the operation mode status for reading.
햲
The signal within parentheses ( ) is the initial status. The input signal function can be changed
using Pr. 180 to Pr. 184 (Input terminal function selection). (Refer to page 6-116)
햳
The signal within parentheses ( ) is the initial status. The output signal function can be changed
using Pr. 190 to Pr. 192 (Output terminal function selection). (Refer to page 6-126)
Register
Beschreibung
Lesen/Schreiben Bemerkung
40002
Inverter reset
Write
Any value
40003
Parameter clear
Write
Set H965A.
40004
All parameter clear
Write
Set H99AA.
40006
Parameter clear
Write
Set H5A96.
40007
All parameter clear
Write
Set HAA99.
40009
Inverter status / control input command
Read/Write
Refer to Tab. 6-134
40010
Operation mode / inverter setting
Read/Write
Refer to Tab. 6-135
40014
Running frequency (RAM value)
Read/Write
The frequency indication can be changed to
the machine speed indication using Pr. 37.
(Refer to page 6-138)
40015
Running frequency (E²PROM value)
Write
Tab. 6-133:
System environment variables
Bit
Definition
Control input command
Inverter status
0
Stop command
RUN (Inverter running)
1
Forward rotation command
During forward rotation
2
Reverse rotation command
During reverse rotation
3
RH (High-speed command)
SU (Up to frequency)
4
RM (Middle-speed operation command)
OL (Overload)
5
RL (Low-speed operation command)
0
6
0
FU (Frequency detection)
7
RT (Second function selection)
ABC (Fault)
8
AU (Current input selection)
0
9
0
Safety monitor output
10
MRS (Output stop)
0
11
0
0
12
RES (Inverter reset)
0
13
0
0
14
0
0
15
0
Fault occurrence
Tab. 6-134:
Inverter status / control input command
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......