1 PRODUCT CHECKING AND PARTS IDENTIFICATION
Unpack the inverter and check the capacity plate on the front cover and the rating plate on the inverter side face to ensure that
the product agrees with your order and the inverter is intact.
z
Installation of the inverter
Enclosure surface mounting
Remove the front cover and wiring cover to fix the inverter to the surface.
NOTE
y
When encasing multiple inverters, install them in parallel as a
cooling measure.
y
When using the inverters at the surrounding air temperature of
40°C (104°F) or less, the inverters can be installed without any
clearance between them (0cm (0 inch) clearance). When
surrounding air temperature exceeds 40°C (104°F), clearances
between the inverters should be 1cm (0.39inch) or more (5cm
(1.96inch) or more for the FR-E720-240(SC) and FR-E740-
120(SC), or more).
y
Install the inverter vertically.
FR
E740
095
Displays the
rated current
Control circuit terminal specification
Symbol
Standard control circuit terminal
(screw type)
No symbol
Safety stop function model
SC
-
-
- NA
Inverter model
Inverter model
Serial number
Capacity plate
FR-E740-095-NA
Capacity plate
Rating plate
Inverter model
Input rating
Output rating
Serial number
FR-E740-095-NA
Rating plate
Symbol Voltage class
E720
E740
Three-phase 200V class
Three-phase 400V class
Single-phase 200V class
E720S
Single-phase 100V class
E710W
Front cover
Wiring cover
Front cover
Wiring cover
FR-E720-008(SC) to 050(SC)
FR-E720S-008 to 030
FR-E710W-008 to 030
FR-E720-080(SC) or more
FR-E740-016(SC) or more
FR-E720S-050 or more
FR-E710W-050
V
ertical
10cm(3.94inches)
or more
10cm(3.94inches)
or more
Refer to the
clearances
on the left.