Troubleshooting
Check first when you have troubles
FR-D700 SC EC
7 - 25
7.6.7
Acceleration/deceleration is not smooth
Check points Possible Cause
Countermeasures
Refer to
Page
Parameter
Setting
Acceleration/deceleration time is too
short.
Increase acceleration/deceleration time.
Torque boost (Pr. 0, Pr. 46) setting is
improper under V/f control, so the stall
prevention function is activated.
Increase/decrease Pr. 0 "Torque boost"
setting value by 0.5% increments to the
setting.
The base frequency does not match the
motor characteristics.
For V/f control, set Pr. 3 "Base frequency"
and Pr. 47 "Second V/f (base frequency)".
For general-purpose magnetic flux vector
control, set Pr. 84 "Rated motor fre-
quency".
Stall prevention function is activated due
to a heavy load.
Reduce the load weight.
—
Set Pr. 22 "Stall prevention operation level
"higher according to the load. (Setting
Pr. 22 too large may result in frequent
overcurrent trip (E.OC
).)
Check the capacities of the inverter and
the motor.
—
Regeneration avoidance operation is per-
formed
If the frequency becomes unstable during
regeneration avoidance operation,
decrease the setting of Pr. 886 "Regene-
ration avoidance voltage gain".
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......