Misoperation prevention and parameter setting restriction
Parameter
6 - 160
6.16
Misoperation prevention and parameter setting restriction
6.16.1
Reset selection/disconnected PU detection/PU stop selection (Pr. 75)
You can select the reset input acceptance, disconnected PU (FR-PU04/FR-PU07) connector
detection function and PU stop function.
The above parameter can be set when Pr. 160 = 0.
The Pr. 75 value can be set any time. Also, if parameter (all) clear is executed, this setting will
not return to the initial value.
The above parameter allows its setting to be changed during operation in any operation mode
even if "0" is set in Pr. 77.
Purpose
Parameters that must be set
Refer to
Section
Limit reset function
Make alarm stop when PU is
disconnected
Stop from PU
Reset selection/
disconnected PU detection/
PU stop selection
Pr. 75
Prevention of parameter rewrite
Parameter write selection
Pr. 77
Prevention of reverse rotation of the
motor
Reverse rotation prevention selection
Pr. 78
Displays necessary parameters
Display of applied parameters
Pr. 160
Parameter restriction with using
password
Password function
Pr. 296, Pr. 297
Control of parameter write by
communication
E²PROM write selection
Pr. 342
Pr.
No.
Name
Initial
Value
Setting
Range
Description
Parameters referred to
Refer to
Section
75
Reset selection/
disconnected PU
detection/
PU stop selection
14
0–3/
14–17
For the initial value, reset always
enabled, without disconnected PU
detection, and with PU stop func-
tion are set.
250
551
Stop selection
PU mode opera-
tion command
source selection
Pr. 75
Reset Selection
Disconnected PU Detection PU Stop Selection
0
Reset input always enabled.
If the PU is disconnected,
operation will be continued.
Pressing the STOP
key decelerates the
motor to a stop only in
the PU operation
mode.
1
Enabled only when the protective function
is activated
2
Reset input always enabled.
When the PU is discon-
nected, the inverter output is
shut off.
3
Enabled only when the protective function
is activated
14
(initial
value)
Reset input always enabled.
If the PU is disconnected,
operation will be continued.
Pressing the STOP
key decelerates the
motor to a stop in any
of the PU, external and
communication opera-
tion modes.
15
Enabled only when the protective function
is activated
16
Reset input always enabled.
When the PU is discon-
nected, the inverter output is
shut off.
17
Enabled only when the protective function
is activated
Tab. 6-31:
Setting of parameter 75
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......