Misoperation prevention and parameter setting restriction
4.15.2 Parameter write disable selection (Pr. 77)
(1) Write parameters only during stop (setting "0" initial value)
Parameters can be written only during a stop in the PU operation mode.
The shaded parameters in the parameter list
can always be written regardless of the operation mode and
operating status.
(2) Inhibit parameter write
(setting "
1"
)
(3) Write parameters during operation (setting "2")
Parameters can always be written.
The following parameters cannot be written when the drive unit is running even if
Pr. 77
= "2". Stop the drive unit when
changing their parameter settings.
You can select whether write to various parameters can be performed or not. Use this function to prevent parameter
values from being rewritten by misoperation.
Parameter
Number
Name
Initial Value
Setting Range
Description
77
Parameter write selection
0
0
Write is enabled only during stop.
1
Parameter cannot be written.
2
Parameter write is enabled in any operation
mode regardless of operation status.
The above parameter can be set when
Pr. 160
Extended function display selection
= "0".
Pr. 77
can always be set independently from the operation mode and operation status.
Parameter write is not enabled.
(Read is enabled.)
Parameter clear and all parameter clear cannot be
performed, either.
The parameters given on the right can be written even if
Pr.
77
= "1".
Parameter
Number
Name
22
Stall prevention operation level
75
Reset selection/disconnected PU detection/
PU stop selection
77
Parameter write selection
79
Operation mode selection
160
Extended function display selection
296
Password lock level
297
Password lock/unlock
997
Fault initiation
Parameter
Number
Name
40
RUN key rotation direction selection
48
Second stall prevention operation current
71
Applied motor
79
Operation mode selection
80
Motor capacity
81
Number of motor poles
82
Motor excitation current
83
Rated motor voltage
84
Rated motor speed
90, 92, 93
(Motor constant)
96
Auto tuning setting/status
178 to 182
(input terminal function selection)
190, 192
(output terminal function selection)
561
PTC thermistor protection level
643
Voltage compensation amount setting
658
Wiring resistance
672, 702,
706, 707,
711, 712,
717, 721, 724
to 726, 859
(PM motor tuning)
736
Electromagnetic brake interlock time
785
PM control torque boost
795
DC brake torque boost
800
Control method selection
998
PM parameter initialization
999
Automatic parameter setting