Parameter list
Parameter list
54
Parameter List
4.2 Parameter list
4.2.1
parameter list
For simple variable-speed operation of the drive unit, the initial setting of the parameters may be used. Set the necessary
parameters to meet the load and operational specifications. Parameter setting, change and check can be made from the
operation panel.
Symbol in the Remarks column.
...Specifications differ according to the date assembled.
to check the SERIAL number.
These instruction codes are used for parameter read and write by using Mitsubishi inverter protocol with the RS-485 communication.
(
for RS-485 communication.)
"
" indicates valid and "
" indicates invalid of "control mode-based correspondence table", "parameter copy", "parameter clear", and "all parameter clear".
Function
Parameter
Name
Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting
Parameter
Remarks
Instruction Code
Parameter
Read
Write
Extended
Copy
Clear
All Clear
Basic functions
1
Maximum setting
0 to 12000r/min/
0 to 8000r/min
1r/min
3000r/min
1
01
81
0
2
Minimum setting
0 to 3600r/min/
0 to 2400r/min
1r/min
0r/min
2
02
82
0
4
Multi-speed setting (high speed)
0 to 12000r/min/
0 to 8000r/min
1r/min
3000r/min
4
04
84
0
5
Multi-speed setting (middle speed)
0 to 12000r/min/
0 to 8000r/min
1r/min
1500r/min
5
05
85
0
6
Multi-speed setting (low speed)
0 to 12000r/min/
0 to 8000r/min
1r/min
300r/min
6
06
86
0
7
Acceleration time
0 to 3600s
0.1s
5s
7
07
87
0
8
Deceleration time
0 to 3600s
0.1s
5s
8
08
88
0
9
Electronic thermal O/L relay
0 to 500A
0.01A
Rated motor
current
9
09
89
0
D
C
in
je
ct
io
n
br
ak
e
10
Coasting speed
0 to 3600r/min/
0 to 2400r/min
1r/min
90r/min
10
0A
8A
0
11
DC injection brake operation time
0 to 10s
0.1s
0.5s
11
0B
8B
0
—
13
Starting speed
0 to 1800r/min/
0 to 1200r/min
1r/min
15r/min
13
0D
8D
0
JO
G
oper
atio
n
15
Jog speed setting
0 to 12000r/min/
0 to 8000r/min
1r/min
150r/min
15
0F
8F
0
16
Jog acceleration/deceleration time
0 to 3600s
0.1s
0.5s
16
10
90
0
—
17
MRS input selection
0, 2, 4
1
0
17
11
91
0
Ac
cel
era
tion/
de
ce
le
ra
tion
ti
m
e
20
Acceleration/deceleration reference
speed
30 to 12000r/min/
20 to 8000r/min
1r/min
3000r/min
20
14
94
0
Sta
ll
pre
vent
io
n
22
Stall prevention operation level
0 to 200%
0.1%
150%
22
16
96
0
Multi-speed
setting
24
Multi-speed setting (speed 4)
0 to 12000r/min/
0 to 8000r/min
, 9999
1r/min
9999
24
18
98
0
25
Multi-speed setting (speed 5)
0 to 12000r/min/
0 to 8000r/min
, 9999
1r/min
9999
25
19
99
0
26
Multi-speed setting (speed 6)
0 to 12000r/min/
0 to 8000r/min
, 9999
1r/min
9999
26
1A
9A
0
27
Multi-speed setting (speed 7)
0 to 12000r/min/
0 to 8000r/min
, 9999
1r/min
9999
27
1B
9B
0
Parameter
Name
Initial Value
Setting Range
Remarks
160
Extended function display
selection
9999
9999
Displays only the simple mode parameters
0
Displays simple mode + extended parameters
REMARKS
indicates simple mode parameters.
The parameters surrounded by a black border in the table allow its setting to be changed during operation even if "0" (initial
value) is set in
Pr. 77 Parameter write selection
.
Summary of Contents for FR-D720-0.2K-G
Page 45: ...34 MEMO ...
Page 293: ...290 MEMO ...