184
Communication operation and setting
4.17.2 Initial settings and specifications of RS-485 communication
(Pr. 117 to Pr. 120, Pr. 123, Pr. 124, Pr. 549)
The following parameters are used to perform required settings for RS-485 communication between the drive unit and
personal computer.
Use PU connector of the drive unit for communication.
You can perform parameter setting, monitoring, etc. using Mitsubishi inverter protocol or MODBUS RTU protocol.
To make communication between the personal computer and drive unit, setting of the communication specifications
must be made to the drive unit in advance.
Data communication cannot be made if the initial settings are not made or there is any setting error.
Parameter
Number
Name
Initial
Value
Setting Range
Description
117
PU communication
station number
0
0 to 31 (0 to 247)
Drive unit station number specification
Set the drive unit station numbers when two or more
drive units are connected to one personal computer.
118
PU communication speed
192
48, 96, 192, 384
Communication speed
The setting value X 100 equals to the
communication speed.
Example)19200bps if 192
119
PU communication stop
bit length
1
Stop bit length
Data length
0
1 bit
8 bits
1
2 bits
10
1 bit
7 bits
11
2 bits
120
PU communication parity
check
2
0
Without parity check
1
With odd parity check
2
With even parity check
123
PU communication
waiting time setting
9999
0 to 150ms
Set the waiting time between data transmission to
the drive unit and response.
9999
Set with communication data.
Waiting time: setting data × 10ms
124
PU communication CR/LF
selection
1
0
Without CR/LF
1
With CR
2
With CR/LF
549
Protocol selection
0
0
Mitsubishi inverter (computer link operation) protocol
1
MODBUS RTU protocol
The above parameters can be set when
Pr. 160 Extended function display selection
= "0".
When "1" (MODBUS RTU protocol) is set in
Pr. 549
, the setting range within parentheses is applied.
NOTE
Always reset the drive unit after making the initial settings of the parameters. After you have changed the
communication-related parameters, communication cannot be made until the drive unit is reset.
Summary of Contents for FR-D720-0.2K-G
Page 45: ...34 MEMO ...
Page 293: ...290 MEMO ...