3 WIRING
3.1 Terminal connection diagram
NOTE
y
To prevent a malfunction caused by noise, separate the signal cables more than 10cm (3.93inch) from the power cables.
Also separate the main circuit wire of the input side and the output side.
y
After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes
in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
y
The output of the single-phase power input model is three-phase 200V.
Earth
(Ground)
Motor
IM
Earth (Ground)
Three-phase
AC power
supply
MCCB
MC
R/L1
P1
P/+
PR N/-
S/L2
T/L3
U
V
W
Earth
(Ground)
*8 Brake resistor (FR-ABR, MRS type, MYS
type)
Install a thermal relay to prevent an
overheat and burnout of the brake resistor.
(The brake resistor can not be connected
to the FR-D720-008 and 014, FR-D720S-
008 and 014, FR-D710W-008 and 014.)
Forward
rotation start
Reverse
rotation start
Middle
speed
High
speed
Low
speed
Control input signals (No voltage input allowed)
24VDC power supply
(Common for external power supply transistor)
Contact input common
STR
STF
RH
RM
RL
SD
PC
Relay output
Running
Open collector output
Open collector output common
Sink/source common
RUN
SO
SE
A
B
C
Frequency setting signals (Analog)
2 0 to 5VDC
10(+5V)
2
3
1
4 4 to 20mADC
Frequency
setting
potentiometer
1/2W1k
Ω
Terminal 4
input
(Current
input)
(+)
(-)
5(Analog common)
*4 It is recommended to use
2W1k
Ω
when the
frequency setting signal is
changed frequently.
*4
*2 When using terminals PC-
SD as a 24VDC power
supply, take care not to
short across terminals
PC-SD.
PU
connector
*
1. DC reactor (FR-HEL)
When connecting a DC reactor, remove the
jumper across P1-P/+.
Single-phase 100V power input model is not
compatible with DC reactor.
Control circuit terminal
Main circuit terminal
Sink logic
Jumper
*1
*6
*8
*7
*2
*3
*5
The function of these
terminals can be changed
to the reset signal, etc.
with the input terminal
assignment (
Pr.178
to
Pr.182
).
Multi-speed selection
Terminal functions vary by
Pr. 190 RUN terminal function
selection
Terminal functions vary
by
Pr. 192
A,B,C terminal
function selection
SINK
SOURCE
V
I
*5
0 to 5VDC
(0 to 10VDC)
0 to 10VDC
*5 Terminal input specifications can be changed by analog
input specifications switchover (
Pr. 267
). Set the
voltage/current input switch in the "
V
" position to select
voltage input (0 to 5V/0 to10V) and "
I
" (initial value) to
select current input (4 to 20mA).To use terminal 4 (initial
setting is current input), set "4" in any of
Pr.178 to Pr.182
(input terminal function selection)
to assign the function, and
turn ON AU signal.
Voltage/current
input switch
Main circuit
Control circuit
R
Relay output
(Fault output)
Brake unit
(Option)
*3 Terminal input specifications
can be changed by analog
input specifications
switchover (
Pr. 73
).
Terminal 10 and terminal 2
are used as PTC input
terminal (
Pr. 561
).
Safety stop signal
S1
S2
SC
Shorting
wire
Single-phase
AC power
supply
MCCB
MC
R/L1
S/L2
Single-phase power input
AM
5
(+)
(-)
Analog signal output
(0 to 10VDC)
*7 A brake transistor is not built-in to the
FR-D720-008 and 014, FR-D720S-008
and 014, FR-D710W-008 and 014.
*6 Terminal P1 is not available for single-
phase 100V power input model.
Terminal functions vary by
Pr. 197
SO terminal function selection
*9
Common terminal of terminal SO is
terminal SC. (Connected to
terminal SD inside of the inverter.)
Safety monitor output *9
Safety stop input (Channel 1)
Safety stop input (Channel 2)
Safety stop input common