3.3 Control circuit specifications
(1) Control circuit terminal layout
(2) Wiring method
z
Wiring
Use a blade terminal and a wire with a sheath stripped off for the control circuit wiring. For a single wire, strip off the sheath of
the wire and apply directly.
Insert the blade terminal or the single wire into a socket of the terminal.
1) Strip off the sheath about the length below. If the length of the sheath peeled is too long, a short circuit may occur among
neighboring wires. If the length is too short, wires might come off.
Wire the stripped wire after twisting it to prevent it from becoming loose. In addition, do not solder it.
2) Crimp the blade terminal.
Insert wires to a blade terminal, and check that the wires come out for about 0 to 0.5 mm (0.02 inch) from a sleeve.
Check the condition of the blade terminal after crimping. Do not use a blade terminal of which the crimping is
inappropriate, or the face is damaged.
Blade terminals available on the market: (as of January 2010)
z
Phoenix Contact Co.,Ltd.
∗1
A blade terminal with an insulation sleeve compatible with MTW wire which has a thick wire insulation
∗2
Applicable for terminal ABC.
z
NICHIFU Co.,Ltd.
Wire stripping length
Wire Size (mm
2
)
Blade Terminal Model
Crimping Tool
Name
With Insulation
Sleeve
Without Insulation
Sleeve
for UL wire
0.3
AI 0,5-10WH
—
—
CRIMPFOX 6
0.5
AI 0,5-10WH
—
AI 0,5-10WH-GB
0.75
Al 0,75-10GY
A 0,75-10
AI 0,75-10GY-GB
1
AI 1-10RD
A 1-10
AI 1-10RD/1000GB
1.25, 1.5
AI 1,5-10BK
A 1,5-10
AI 1,5-10BK/1000GB
0.75 (for two cables)
AI-TWIN 2 X 0,75-10GY
—
—
Wire Size (mm
2
)
Blade terminal product
number
Insulation product number
Crimping tool
product number
0.3 to 0.75
BT 0.75-11
VC 0.75
NH 69
STF STR
PC
SD
RH
RM
RL
AM
C
B
A
10
2
5
4
RUN SE
S1 S2 SC
SO
SD
Recommended wire size:
0.3mm
2
to 0.75mm
2
10mm
(0.39 inch)
Unstranded
wires
Damaged
Wires are not inserted
into the shell
Crumpled tip
Sleeve
Shell
W
ire
0 to 0.5mm (0.02 inch)