(N) Operation via communication and its settings
128
Setting items and set data
• After completion of parameter settings, set the instruction codes and data, then start communication from the computer to
allow reading/writing of parameters and monitoring.
Item
Read/
write
Instruction
code
Data description
Number of data
digits
(Format)
Monitor
Converter
output
voltage
Read
H6F
H0000 to HFFFF: Converter output voltage (hexadecimal) in 0.1 V
increments
4 digits (B.E/D)
Input current
Read
H70
H0000 to HFFFF: Input current (hexadecimal) in 0.1 A increments
4 digits (B.E/D)
Electric
thermal relay
function load
factor
Read
H71
H0000 to HFFFF: Electronic thermal relay function load factor
(hexadecimal) in 0.1% increments
4 digits (B.E/D)
Special
monitor
Read
H72
H0000 to HFFFF: Monitor data selected in the instruction code HF3
4 digits (B.E/D)
Special
monitor
selection No.
Read
H73
Monitor selection data (Refer to
on selection No.)
2 digits (B.E1/D)
Write
HF3
2 digits (A1, C/D)
Fault record
Read
H74 to H77
H0000 to HFFFF: Two latest fault records
(Refer to
for details on fault record read data.)
4 digits (B.E/D)
Converter status
monitor
(extended)
Read
H79
Status of the output signals can be monitored. (For the details, refer to
.)
4 digits (B.E/D)
Converter status
monitor
Read
H7A
2 digits (B.E1/D)
Converter reset
Write
HFD
H9696: Converter unit reset
• As the converter unit is reset at the start of communication by the
computer, the converter unit cannot send reply data back to the computer.
4 digits (A, C/D)
H9966: Converter unit reset
• When data is sent normally, ACK is returned to the computer, and then the
converter is reset.
4 digits (A, D)
Fault history batch
clear
Write
HF4
H9696: Fault history batch clear
4 digits (A, C/D)
b15
b8 b7
b0
Latest fault
Second fault in past
Third fault in past
Fourth fault in past
Fifth fault in past
Sixth fault in past
Seventh fault in past
Eighth fault in past
H74
H75
H76
H77
With the read data H3040
Fault record display example (instruction code H74)
(Last fault : E.THC)
(Present fault : E.FIN)
0
b15
Present fault
(H40)
Last fault
(H30)
0 1 1 0 0 0 0
b8
0
b7
1 0 0 0 0 0 0
b0