(M) Monitor display and monitor output signal
101
5
GROUP
M
5.4
(M) Monitor display and monitor output signal
5.4.1
Monitor display selection using operation panel
or via communication
Purpose
Parameter to set
Refer to
page
To change the monitored item on
the operation panel
Operation panel monitor
selection
Cumulative monitor
clear
P.M020 to P.M023,
P.M044,
P.M100 to P.M104
Pr.170, Pr.268,
Pr.290, Pr.563,
Pr.774 to Pr.776,
Pr.891, Pr.992
To assign functions to output
terminals
Output terminal function
assignment
P.M400 to P.M405
Pr.190 to Pr.195
To detect the control circuit
temperature
Control circuit
temperature monitor
P.M060
Pr.663
The monitored item to be displayed on the operation panel can be selected. Install the operation panel of the inverter on
the converter unit.
Pr.
Name
Initial value
Setting range
Description
774
M101
Operation panel monitor
selection 1
9999
(Converter output
voltage)
2, 8, 13, 20, 25, 43,
44, 55, 62, 68, 98,
9999
The converter output voltage, input
current and electronic thermal relay
function load factor monitor that are
displayed in monitor mode on the
operation panel can be switched to a
specified monitor.
775
M102
Operation panel monitor
selection 2
9999
(Input current)
776
M103
Operation panel monitor
selection 3
9999
(Electric thermal relay
function load factor)
992
M104
Operation panel setting
dial push monitor
selection
8
(Converter output
voltage)
2, 8, 13, 20, 25, 43,
44, 55, 62, 68, 98
Select the monitor to be displayed when
the setting dial on the operation panel is
pushed.
170
M020
Watt-hour meter clear
9999
0
Set "0" to clear the watt-hour monitor.
10
Sets the maximum value for the
monitoring from 0 to 9999 kWh.
9999
Sets the maximum value for the
monitoring from 0 to 65535 kWh.
563
M021
Energization time
carrying-over times
0
(0 to 65535)
(Read-only.)
Displays the numbers of times that the
cumulative energization time monitor
exceeded 65535 h. Read-only.
268
M022
Monitor decimal digits
selection
9999
0
Displays as integral value.
1
Displays in 0.1 increments.
9999
No function
891
M023
Cumulative power
monitor digit shifted
times
9999
0 to 4
Set the number of times to shift the
cumulative power monitor digit.
The monitored value is clamped at the
maximum value.
9999
No shift.
The monitored value is cleared when it
exceeds the maximum value.
290
M044
Monitor negative output
selection
0
0, 2, 4, 6
Set the availability of output with a minus
sign for the operation panel display or
monitoring via communication.