59
7
RWw11,
RWw13,
RWw15,
RWw17,
RWw19,
RWw1B
Write data
Set the data specified by the instruction code of RWw10, 12, 14, 16, 18 and 1A (when required).
RWw10, 12, 14, 16, 18, and 1A correspond to RWw11 13, 15, 17, 19, and 1B, respectively.
Set "1" in RY25 after setting the instruction codes (RWw10, 12, 14, 16, 18, and 1A) and the
corresponding register.
Set "0" when the write code is not required.
RWw21
Faults history No.
Set the number of previous faults you want to be able to read in the faults history.
Up to 8 previous faults can be read.
Last two digits: H00 (most recent fault) to H07 (8th most recent fault)
Set H08 to HFF to make the faults history No. to "0."
RWw26
Monitor code 1
Set the monitor code to be monitored (refer to
). By setting "1" in RY20 after setting, the
specified monitored data is stored in RWr26 to RWr2F.
If a monitor code out of the setting range is set, no item is monitored (the monitor value is fixed to 0).
RWw27
Monitor code 2
RWw28
Monitor code 3
RWw29
Monitor code 4
RWw2A
Monitor code 5
RWw2B
Monitor code 6
RWw2C
Monitor code 7
RWw2D
Monitor code 8
RWw2E
Monitor code 9
RWw2F
Monitor code 10
Setting increment differs according to the combination of
Pr.37, Pr.144, and Pr.811
. (
Pr.811
is only available for the FR-A800 series.)
Refer to the Instruction Manual (Detailed) of the inverter for the details.
When
Pr.541 Frequency command sign selection
= "1", the setting value has or -. When the setting value is negative, the
command is the inverse from the command.
Setting range: -327.68 Hz to 327.67 Hz (-327.68 to 327.67) 0.01 Hz increments.
For details refer to
.
When
Pr.128
= "50, 51, 60, 61", they are valid. If the data outside the range is set, the previous setting is retained.
Refer to the Instruction Manual (Detailed) of the inverter for details of
Pr.128
.
Write data is in hexadecimal, and only two digits are valid. (The upper two digits are ignored.)
The signal is valid only for the FR-A800 series.
The value in RWw2 is used as the torque limit value during speed control or position control, and as the torque command value during
torque control. (Torque control cannot be performed with a PM motor.) To use the value as the torque limit value, set
Pr.810
= "2".
This setting is available only when the inverter supports this function. (Refer to
Device No.
Signal
Description