Adjusting the analog signal (Pr.307, Pr.308, Pr.311, Pr.312)
Use
Pr. 307
or
Pr. 311
to set the values at zero analog output (meter points 0) and
Pr. 308
or
Pr. 312
at maximum analog
output (full scale).
When outputting the same signal from terminals AM0 and AM1, use
Pr.307
to set the value at zero analog output and
Pr.308
at
maximum analog output. When outputting separate signals from terminals AM0 and AM1, use
Pr.307
(for terminal AM1) and
Pr.311
(for terminal AM0) to set the value at zero analog output, and
Pr.308
(for terminal AM1) and
Pr.312
(for terminal AM0) at
maximum analog output. (Refer to
NOTE
• When
Pr.307
Pr.308
and
Pr.311
Pr.312
, the output values from the terminals AM0 and AM1 will always be zero.
Pr.309 = "0, 1"
Pr.1019 = "0" (output without minus sign)
Pr.1019 = "1" (output with minus sign)
0
Output signal
value
100%
-100%
Output signal value
(
Pr. 308
or
Pr. 312
)
for maximum analog output
Output signal value
(
Pr. 307
or
Pr. 311
)
for zero output signal
Current (AM1):
20 mA
Voltage (AM0):
10 V
Analog output
Current (AM1): 20 mA
Voltage (AM0): 10 V
Analog output
-10V
0
Output signal
value
100%
-100%
Output signal value
(
Pr. 308
or
Pr. 312
)
for maximum analog output
Output signal value
(
Pr. 307
or
Pr. 311
)
for zero output signal