3
PRE-OPERATION INSTRUCTIONS
1
1.3 Specifications
(1) Output signals
Voltage output (across terminals AM0-AMC) 0 to 10VDCMAX
Current output (across terminals AM1-AMC) 0 to 20mADC
(2) Output resolution
Voltage output 3mV
Current output 10
μ
A
(3) Output accuracy (reference value)
±10% of the full-scale output value
Depends on the output signal type.
(4) Meters used
•
Voltmeter
DC voltmeter Full-scale 10V (internal impedance 10k
Ω
or more)
•
Ammeter
DC ammeter Full-scale 20mA (internal impedance 300
Ω
or less)
•
Wiring length
Maximum 10m