8
DATA
3
3-1. NOISE CRITERION CURVES
PUHZ-W50VHA2
PUHZ-W50VHA2R1
PUHZ-W50VHA2-BS PUHZ-W50VHA2R1-BS
1.5 m
1 m
MICROPHONE
UNIT
GROUND
3-2. STANDARD OPERATION DATA
Mode
Cooling (A35/W7)
Heating (A7/W35)
Total
Capacity
W
4,500
5,000
Input
kW
1.53
1.11
Electrical circuit
Outdoor unit
PUHZ-W50VHA2
Phase, Hz
1, 50
Voltage
V
230
Current
A
6.8
5.4
Refrigerant
circuit
Discharge pressure
MPa
2.51
2.13
Suction pressure
MPa
0.83
0.68
Discharge temperature
ºC
69
68
Condensing temperature ºC
43
37
Suction temperature
ºC
6
6
W
ater
conditions
Flow volume
L/min
12.9
14.3
Outlet water temperature
ºC
7
35
Outdoor conditions
Intake air
temperature
D.B. ºC
35
7
W.B. ºC
24
6
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is: 1 (MPa) = 10.2 (kgf/cm
2
)
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
90
80
70
60
50
40
30
20
10
OCT
AVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
63
125
250
500
1000 2000 4000 8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
BAND CENTER FREQUENCIES, Hz
COOLING
MODE
HEATING
45
SPL(dB)
46
LINE
OCH605A
Summary of Contents for ecodan PUHZ-W50VHA2