50
OPERATING PROCEDURE
13. Removing the compressor (MC)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove 2 screws (5
×
12) and remove the cover panel (front).
(4) Remove the electrical parts box. (See Photo 4)
(5) Remove 3 screws (4
×
10) and remove the valve bed.
(See Photo 10)
(6) Remove 3 screws (5
×
12) in the rear of the unit and
remove the side panel (R). (See Photo 4)
(7) Remove 5 screws (1: 4
×
10, 4: 5
×
12) and remove the
front panel.
(See Photo 2)
(8) Remove 3 screws (4
×
10) and remove the separator. (See
Photo 4)
(9) Remove the terminal cover and remove the lead wire for
compressor.
(10) Remove the soundproof cover for compressor.
(11) Recover refrigerant.
(12) Remove the 3 points of the compressor fixing nut using a
spanner or a adjustable wrench.
(13) Remove the welded pipe of the compressor, then remove
the compressor.
Note 1: Recover refrigerant without spreading it in the air.
14. Removing the receiver
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove 2 screws (5
×
12) and remove the cover panel (front).
(4) Remove the electrical parts box. (See Photo 4)
(5) Remove 3 screws (4
×
10) and remove the valve bed.
(See Photo 4)
(6) Remove 3 screws (5
×
12) in the rear of the unit and
remove the side panel (R). (See Photo 4)
(7) Recover the refrigerant.
(8) Remove 2 welded pipes of receiver.
(9) Remove 2 receiver leg fixing screws (4
×
10), then remove
the receiver.
Note 1: Recover refrigerant without spreading it in the air.
15. Removing the plate heat exchanger
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove 2 screws (5
×
12) and remove the cover panel (front).
(4) Remove the electrical parts box. (See Photo 4)
(5) Remove 3 screws (4
×
10) and remove the valve bed. (See Photo 4)
(6) Remove 3 screws (5
×
12) in the rear of the unit and
remove the side panel (R). (See Photo 4)
(7) Recover the refrigerant.
(8) Remove 2 welded pipes of plate heat exchanger inlet and
outlet.
(9) Remove 2 plate heat exchanger fixing screws (4
×
10),
then remove the plate heat exchanger.
Note 1: Recover refrigerant without spreading it in the air.
Note 2: Before removing the thermistor <Inlet Water> (TH32),
recover water in the plate heat exchanger.
Photo 10
Photo 11
Compressor
fixing nut
Compressor
(MC)
Terminal cover
Lead wire for
compressor
Receiver
Plate heat
exchanger fixing
screw
Receiver leg fixing screws
Plate heat
exchanger
PHOTOS
OCH605A
Summary of Contents for ecodan PUHZ-W50VHA2
Page 57: ...57 OCH605A ...
Page 60: ...Ecodan FTC5 Databook M P0729 ...