background image

10

en

2. Selecting an installation site

2.1. About the product

This unit uses R32-type refrigerant.

Indoor units that are all WP, all W, or all WL models are connectable to the HBC.

Piping for systems using R32 may be different from that for systems using 
conventional refrigerant because the design pressure in systems using R32 is 
higher. Refer to the Data Book for more information.

Some of the tools and equipment used for installation with systems that use other 
types of refrigerant cannot be used with the systems using R32. Refer to the Data 
Book for more information.

Do not use the existing piping, as it contains chlorine, which is found in 
conventional refrigerating machine oil and refrigerant. This chlorine will 
deteriorate the refrigerant machine oil in the new equipment. The existing piping 
must not be used as the design pressure in systems using R32 is higher than that 
in the systems using other types of refrigerant and the existing pipes may burst.

2.2. Installation site

Install the unit in a place not exposed to rain. The HBC is designed to be installed 
indoors.

Install the unit with adequate space around it for servicing.

Do not install the unit in a place that would result in the piping length restrictions 
being exceeded.

Check for refrigerant leaks before service. 
- If the refrigerant leaks, fire may result.

Install or store the unit in a place not exposed to direct radiant heat from other 
heat sources or naked flame or other ignition sources.

Do not install the unit in any oily steamy place or near any machine that 
generates high frequencies. Doing so may cause a risk of fire, erroneous 
operation or condensation.

Depending on the operation conditions, HBC unit generates noise caused by 
valve actuation, refrigerant flow, and pressure changes even when operating 
normally. Therefore install the unit in places such as machinery rooms.

Install indoor unit and HBC at least 5 m away from each other when installed in a 
space with low background noise, e.g., hotel rooms.

Allow enough space and access to ensure water piping, refrigerant piping and 
electrical wiring can be easily connected.

Avoid places exposed to the generation, inflow, accumulation or leakage of 
flammable and sulfuric gases.

Ensure a downward gradient of at least 1/100 for drain piping.

Properly install the unit on a stable, load-bearing surface.

1. For hanging from the ceiling [Fig. 2.2.1] (P.2)

Provide 2 inspection holes 450 mm square in the ceiling surface as shown in 
[Fig. 2.3.2] (P.2).

Install the unit in a suitable location (such as in the ceiling of a corridor or in the 
bathroom etc) away from places regularly occupied. Avoid installing in the center 
of a room.

Ensure hanging bolts are of sufficient pull out strength.

Warning:

Be sure to install the unit in a place that can sustain the entire weight.
If there is a lack of strength, it may cause the unit to fall down, resulting in an 
injury.

Caution:

Be sure to install the unit horizontally.
Install the HBC level (less than 1° tilt to downward), so that the drain pan 
can function correctly.

Install the HBC in an environment where the temperature in always above 
0°C.

2.3.  Securing installation and service space

1. Installation

(This is a reference view showing the least installation space.)

[Fig. 2.3.1] (P.2)

[Fig. 2.3.2] (P.2)

2.4.  Checking the installation site

Check that the difference of elevation between indoor and outdoor units and the 
length of refrigerant piping are within the following limitations.

1. CMB-WM350F-AA + CMB-WM108V-BB

(CMB-WM500F-AA)   (CMB-WM1016V-BB) 
[Fig. 2.4.1] (P.2)

Notes:
*1 Indoor units that are connected to the same branch joint cannot be 

simultaneously operated in different operation modes.

Warning:

(When R32 refrigerant is used)

Do not use means to accelerate the defrosting process or to clean, other

 

than those recommended by the manufacturer.

The unit shall be stored in a room without continuously operating ignition 
sources (for example: open flames, an operating gas appliance or
an operating electric heater.)

Do not pierce or burn.

Be aware that refrigerants may not contain an odour.

The unit shall be installed, operated and stored in a room with a floor area
according to the following figure.

When installing an HBC, take safety measures in accordance with the 
European Standard, based on the system refrigerant amount and the room 
volume as shown in the figure below. (The installation restrictions can be 
simply found by using the flowchart provided on the “Safety handling for 
R32” document.)

Notes:

Refer to the outdoor unit manual about additional refrigerant amount of 
HBC and maximum amount of system refrigerant. 

Be sure to protect pipings from physical damage.

<A> Front view

<B> Right side view

A

Side of outdoor unit piping

B

Side of Sub-HBC piping

C

Side of indoor unit piping

D

Service space

*1 Dimensions with which pipe connection can be handled at site

<A> Top view

<B> Front view

A

Inspection hole

B

Side of Main-HBC piping

C

Control box

D

Side of indoor unit piping

E

Service space

*1 Dimensions with which pipe connection can be handled at site

A

Outdoor unit

B

Main-HBC

C

Sub-HBC

D

Indoor unit

E

Less than H=50 m (when the outdoor unit is higher than HBC)

F

Less than H1=40 m (when the outdoor unit is lower than HBC)

G

Branch joint (field supply)

H

Junction pipe (field supply)

I

Less than 110 m

J

Less than 60 m

K

Connecting indoor unit less than 80

L

Connecting indoor unit more than 100

M

Up to three units for 1 branch port
Total capacity: less than 80 (but in same mode, cooling/heating)

N

Less than 15 m

O

Less than 15 m

(Unit: m)

Item

Piping portion

Allowable value

Pipe

 Leng

ths Between outdoor unit and HBC 

(refrigerant piping work)

A

110 or less

Water piping work between indoor units 
and HBC

f + g + j + k

60 or less

Dif

fere

nce

 of e

lev

atio

n

Between 
indoor and 
outdoor units

Above outdoor unit

H

50 or less

Below outdoor unit

H1

40 or less

Between indoor units and HBC

h1

15 or less

Between indoor units

h2

15 or less

0

10

20

30

40

50

60

70

80

0

50

100

150

200

250

300

350

400

450

500

550

600

650

Sy

Stem

 r

efr

ig

er

an

t a

m

ou

nt

 [kg

]

Room volume [m

3

]

At least two safety 
measures are 
required.

NG (ISO 5149)

At least one safety 
measure is required.

Construction guidance

01_WT09805X01_en.book  10 ページ  2021年11月1日 月曜日 午前8時47分

Summary of Contents for CMB-WM1016V-BB

Page 1: ...alar a unidade de ar condicionado sv INSTALLATIONSHANDBOK Läs den här installationshandboken noga innan luftkonditioneringsenheten installeras för säker och korrekt användning tr MONTAJ ELKİTABI Emniyetli ve doğru biçimde nasıl kullanılacağını öğrenmek için lütfen klima cihazını monte etmeden önce bu elkitabını dikkatle okuyunuz pl PODRĘCZNIK INSTALACJI W celu bezpiecznego i poprawnego korzystania...

Page 2: ...tdoor unit is higher than HBC F Less than H1 40 m when the outdoor unit is lower than HBC G Branch joint field supply H Junction pipe field supply I Less than 110 m J Less than 60 m K Connecting indoor unit less than 80 L Connecting indoor unit more than 100 M Up to three units for 1 branch port Total capacity less than 80 but in same mode cooling heating N Less than 15 m O Less than 15 m CMB WM35...

Page 3: ...door unit side PURY E M200 HBC CMB WM350F AA ø15 88 Brazing ø19 05 Brazing PURY E M250 ø15 88 Brazing ø22 2 Brazing PURY E M300 ø15 88 Brazing ø22 2 Brazing PURY E M350 ø15 88 Brazing ø28 58 Brazing PURY E M400 HBC CMB WM500F AA ø19 05 Brazing ø28 58 Brazing PURY E M450 ø19 05 Brazing ø28 58 Brazing PURY E M500 ø19 05 Brazing ø28 58 Brazing Note Be sure to use non oxidative brazing A To outdoor un...

Page 4: ...ew for drain pan A Holes for drain piping field supply B Drain pan C Socket field supply D Drain piping field supply E Insulation for drain piping field supply Unit mm 1 A A B C B A 25 cm B 1 5 2 m A Downward gradient of more than 1 100 B Insulating material C Supporting bracket D Sub HBC E Tie band accessory F Insertion margin G Drain hose accessory H Drain pipe O D ø32 PVC TUBE field supply I In...

Page 5: ...ting port J Water inlet EXP VESSEL Note Remove burr after cutting the piping to prevent entering the pipe connection Check that there is no crack at the edge of the piping Water inlet port EXP VESSEL connecting port Sub HBC connecting port Indoor unit connecting port Main HBC connecting port Indoor unit connecting port Unit mm A B C C D D E E F F Note See Fig 5 1 5 when connecting valves to the on...

Page 6: ... mm W WP WL151 W WP WL250 I D 32 6 mm I D 32 6 mm II D 39 6 mm W WP WL251 W WP WL300 I D 32 6 mm I D 39 6 mm I D 50 8 mm W WP WL301 W WP WL750 I D 50 8 mm I D 50 8 mm I D 50 8 mm A To outdoor unit B End connection brazing C Main HBC Maximum total capacity of connected indoor units W WP WL170 D Sub HBC Maximum total capacity of connected indoor units W WP WL250 E Indoor unit F Branch joint field su...

Page 7: ...F Unit side insulating material C B A D C E F C E C A E Fig 6 0 1 A Control box B Power source wiring C ø21 hole closed rubber bushing D Transmission wiring E Cable strap F Wire saddle CMB WM350F AA CMB WM500F AA A B C D E E A Control box B Power source wiring C ø21 hole closed rubber bushing D Transmission wiring E Clip cables here CMB WM108V BB CMB WM1016V BB 01_WT09805X01_en book 7 ページ 2021年11月...

Page 8: ...eration may lead to damage fire explosions etc Do not change the set values as this may lead to damage fire explosions etc Use of any product except that specified by this company may lead to damage fire explosions etc Do not spray water on electrical parts This could lead to shorting fire smoke electrical shock unit failure etc Do not create a situation where the refrigeration circuit is sealed y...

Page 9: ...here food pets plants precision instruments or artwork are kept The quality of the food etc may deteriorate Do not use the air conditioner in special environments Oil steam sulfuric smoke etc can significantly reduce the performance of the air conditioner or damage its parts When installing the unit in a hospital communication station or similar place provide sufficient protection against noise So...

Page 10: ...so that the drain pan can function correctly Install the HBC in an environment where the temperature in always above 0 C 2 3 Securing installation and service space 1 Installation This is a reference view showing the least installation space Fig 2 3 1 P 2 Fig 2 3 2 P 2 2 4 Checking the installation site Check that the difference of elevation between indoor and outdoor units and the length of refri...

Page 11: ...hat load is not imparted to the HBC s end connections 3 When using mechanical couplings use the ones that meet ISO14903 4 Support the on site pipes near the HBC at 0 5 meter intervals or less and at 2 meter intervals or less in other areas Warning When installing and moving the unit do not charge it with refrigerant other than the refrigerant R32 specified on the unit Mixing of a different refrige...

Page 12: ... must be covered with insulation with its seam facing upward and fastened with the bands 4 4 Additional refrigerant charge Notes Charge refrigerant in a liquid state Do not use a charging cylinder when charging refrigerant The use of a charging cylinder may change the composition of the refrigerant and lead to a performance drop The table below summarizes the factory charged amount of refrigerant ...

Page 13: ...16 kg m High pressure pipe ø15 88 total length 0 11 kg m Outdoor unit model Amount kg HBC model Amount kg E M200 1 0 350F 5 6 E M250 1 0 500F 5 6 E M300 0 E M350 0 E M400 0 E M450 0 E M500 0 Amount of refrigerant to be charged for single module units Amount of additional charge kg High pressure pipe ø22 2 total length 0 19 kg m High pressure pipe ø19 05 total length 0 13 kg m High pressure pipe ø1...

Page 14: ...t port on the HBC Failure to do so will result in incorrect running Please list the indoor units on the naming plate in the HBC unit with addresses and end connection numbers Use the reverse return method to insure proper pipe resistance to each unit Provide some joints and valves around inlet outlet of each unit for easy maintenance checkup and replacement Install a suitable air vent on the water...

Page 15: ...to an HBC the pipes that connect the unit to the same set of HBC ports cannot be branched out to connect additional units Selection of water piping Select the size according to the total capacity of indoor units to be installed down stream Do not connect multiple indoor units to the same port when operating each of them in different modes cooling heating stop and thermo OFF The indoor units connec...

Page 16: ...alve and pres sure reducing valve 5 3 Water treatment and quality control To preserve water quality use the closed type of water circuit When the circulating water quality is poor the water heat exchanger can develop scale leading to a reduction in heat exchange power and possible corrosion Pay careful attention to water processing and water quality control when installing the water circulation sy...

Page 17: ...set to 000 when shipped from the factory Set the address switch to an address that equals the lowest address of the indoor units that are connected to the HBC Sub HBC plus 50 Assign the HBC address that equals the lowest address of the indoor units that are connected to the HBC Sub HBC plus 50 However if the address overlaps any other units addresses assign the address that equals the next lowest ...

Page 18: ... on DIP SW001 1 Water circuit valve setting valve open when stopped 7XUQ RQ 3 6 1XOOL FDWLRQ RI WKH GUDLQ RYHUÀRZ HUURU IRU KRXUV SSOLFDEOH ZKHQ D 6XE 0 0 9 LV FRQQHFWHG 2 Turn on the breaker for each unit and then open the manual air vent valves on the Sub HBC and the indoor units The Main HBC does not have a manual air vent valve 1RWH WKDW LI WKH PDQXDO DLU YHQW YDOYHV DUH RSHQHG WRR PXFK D ODUJ...

Page 19: ...al operation is being performed no other functions of the Maintenance Tool are available for use 1 Follow the procedures below after connecting the MN converter and starting up the Maintenance Tool Manuals are accessible from the Maintenance Tool Debris removal operation procedure without connection to an outdoor unit 2SWLRQĺ RPPLVVLRQLQJ VXSSRUWĺ 95 5 FRPPLVVLRQLQJ 1 6HOHFW 2SWLRQ ĺ RPPLVVLRQLQJ ...

Page 20: ...ts inside IWHU FOHDQLQJ DQG UH WWLQJ WKH VWUDLQHU WXUQ Rႇ 3 6 7 Make sure the strainers are re installed properly Flowchart for debris removal operation Turn on DIP SW002 1 Air 1 Intermittent operation of water pump 20 min The operation is performed to discharge air from the water circuits Air1 Air 2 Water supply to all indoor units 20 min Debris in the pipe will accumulate into the strainer by su...

Page 21: ...air tightness test of refrigerant piping evacuation of refrigerant circuits and refrigerant charging have been completed because the initial air vent operation may not be able to remove all dissolved oxygen in the water circuit 1 Preparation for air vent operation 1 DIP SW settings Main HBC Turn on DIP SW001 1 Water circuit valve setting valve open when stopped 7XUQ RQ 3 6 1XOOL FDWLRQ RI WKH GUDL...

Page 22: ...to an outdoor unit 2SWLRQĺ RPPLVVLRQLQJ VXSSRUWĺ 95 5 FRPPLVVLRQLQJ 1 6HOHFW 2SWLRQ ĺ RPPLVVLRQLQJ VXSSRUW ĺ 95 5 commissioning 2 FRQ UPDWLRQ ZLQGRZ ZLOO DSSHDU KHFN WKH PHVVDJH DQG SUHVV Next to proceed 0DQXDOV DUH DFFHVVLEOH IURP WKH FRQ UPDWLRQ ZLQGRZ 3 After the units are searched for a sign that indicates the completion of preparation will appear Turn on DIP SW002 3 of the Main HBC to start t...

Page 23: ...ndoor units extracts and releases saturated air from the water FLUFXLW LU ĺ LU 1 The operation can be forced to stop by turning on DIP SW002 4 2 If it is found during any step that air has not been discharged to the desired degree repeat the air discharge operation from the beginning 3 I DQ HUURU VLJQ UU DSSHDUV RQ WKH RQ WKH FLUFXLW ERDUG RI WKH WXUQ Rႇ WKH EUHDNHU WXUQ LW EDFN RQ DQG UHSHDW WKH ...

Page 24: ...PS Date of manufacture is indicated in format yyyy mm in the YEAR OF MANUFACTURE field on the nameplate 01_WT09805X01_en book 25 ページ 2021年11月1日 月曜日 午前8時47分 ...

Page 25: ... bortset fra forbindelseselementer som f eks bolte med den drevne enhed f eks aksel eller selve huset og må ikke være desig net på en sådan måde at motoren kan adskilles fuldstændig fra den drevne enhed og fungere uafhængigt Adskillelsesprocessen skal bevirke at motoren sættes ud af drift d den specifikke grund til DE a Herstellername oder Handelsmarke Handelsregisternummer und Adresse b Modellken...

Page 26: ...zna nie może być sprawdzona niezależnie od produktu nawet przy zapewnieniu tymczasowego łożyska od strony tarczy i od strony napędu taki silnik musi posiadać wspólne komponenty oprócz elementów łączących takich jak śruby z napędzanym urządzeniem np wał lub obudowę i nie może być zaprojektowany w sposób umożliwiający jego całkowite oddzielenie od napędzanego urządzenia i niezależną eksploatację Pro...

Page 27: ...01_WT09805X01_en book 31 ページ 2021年11月1日 月曜日 午前8時47分 ...

Page 28: ...y Directive 2014 30 EU Pressure Equipment Directive 2014 68 EU Machinery Directive 2006 42 EC Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN MANUFACTURER MITSUBISHI ELECTRIC CORPORATION Air conditioning Refrigeration Systems Works 5 66 Tebira 6 Chome Wakayama city 64...

Page 29: ...Related Links Model Number CMB WM1016V BB CMB WM F V AA B _InstallationManual_WT09805X01 CMB WM F AA_ServiceHandbook_HWE21050 HVRF_Information_Pack_Ver1 0_ Vertical Horizontal HBC Databook MEES21K003 ...

Reviews: