19
GB
D
F
E
I
NL
P
GR
RU
TR
CZ
SV
SL
HG
PO
Warning:
•
Be sure to use specified wires for connections and ensure no external force is imparted to terminal connections. If connections are not fixed firmly, heating
or fire may result.
•
Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.
Caution:
•
A breaker for current leakage must be attached to the power supply. If no earth leakage breaker is installed, it may cause an electric shock.
•
Do not use anything other than a breaker and fuse with the correct capacity. Using a fuse or wire of too large capacity may cause malfunction or fire.
1. Use dedicated power supplies for the outdoor unit and indoor unit. Ensure OC and OS are wired individually.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum value for metal conduit wiring. If the voltage drops, use a wire that is one rank thicker in diameter.
Make sure the power-supply voltage does not drop more than 10%.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57). For example,
use wiring such as YZW.
6. A switch with at least 3 mm [1/8 in] contact separation in each pole shall be provided by the Air conditioner installation.
<Power source: 460V>
Main cable
Switch (A)
Minimum wire thickness (mm
2
[AWG])
Branch
Capacity
Fuse
Ground
Model
Unit combination
Breaker for current leakage
Outdoor
unit
PUHY-P72YJMU-A(-BS)
-
PUHY-P96YJMU-A(-BS)
-
PUHY-P120YJMU-A(-BS)
-
PUHY-P144YJMU-A(-BS)
-
PUHY-P168YSJMU-A
PUHY-P96YJMU-A(-BS)
PUHY-P72YJMU-A(-BS)
PUHY-P192YSJMU-A
PUHY-P120YJMU-A(-BS)
PUHY-P72YJMU-A(-BS)
PUHY-P216YSJMU-A
PUHY-P120YJMU-A(-BS)
PUHY-P96YJMU-A(-BS)
PUHY-P240YSJMU-A
PUHY-P120YJMU-A(-BS)
PUHY-P120YJMU-A(-BS)
PUHY-P264YSJMU-A
PUHY-P144YJMU-A(-BS)
PUHY-P120YJMU-A(-BS)
PUHY-P288YSJMU-A
PUHY-P144YJMU-A(-BS)
PUHY-P144YJMU-A(-BS)
PUHY-P120YJMU-A(-BS)
PUHY-P312YSJMU-A
PUHY-P120YJMU-A(-BS)
PUHY-P72YJMU-A(-BS)
PUHY-P120YJMU-A(-BS)
PUHY-P336YSJMU-A
PUHY-P120YJMU-A(-BS)
PUHY-P96YJMU-A(-BS)
PUHY-P144YJMU-A(-BS)
PUHY-P360YSJMU-A
PUHY-P120YJMU-A(-BS)
PUHY-P96YJMU-A(-BS)
15A 30mA or 100mA 0.1sec. or less
20A 30mA or 100mA 0.1sec. or less
25A 30mA or 100mA 0.1sec. or less
30A 30mA or 100mA 0.1sec. or less
20A 30mA or 100mA 0.1sec. or less
15A 30mA or 100mA 0.1sec. or less
25A 30mA or 100mA 0.1sec. or less
15A 30mA or 100mA 0.1sec. or less
25A 30mA or 100mA 0.1sec. or less
20A 30mA or 100mA 0.1sec. or less
25A 30mA or 100mA 0.1sec. or less
25A 30mA or 100mA 0.1sec. or less
30A 30mA or 100mA 0.1sec. or less
25A 30mA or 100mA 0.1sec. or less
30A 30mA or 100mA 0.1sec. or less
30A 30mA or 100mA 0.1sec. or less
25A 30mA or 100mA 0.1sec. or less
25A 30mA or 100mA 0.1sec. or less
15A 30mA or 100mA 0.1sec. or less
25A 30mA or 100mA 0.1sec. or less
25A 30mA or 100mA 0.1sec. or less
20A 30mA or 100mA 0.1sec. or less
30A 30mA or 100mA 0.1sec. or less
25A 30mA or 100mA 0.1sec. or less
20A 30mA or 100mA 0.1sec. or less
12
18
17
27
23
35
27
43
17
27
12
18
23
35
12
18
23
35
17
27
23
35
23
35
27
43
23
35
27
43
27
43
23
35
23
35
12
18
23
35
23
35
17
27
27
43
23
35
17
27
2.1 [14]
-
2.1 [14]
15
15
15
3.3 [12]
-
3.3 [12]
20
20
20
5.3 [10]
-
5.3 [10]
25
25
25
5.3 [10]
-
5.3 [10]
30
30
30
3.3 [12]
-
3.3 [12]
20
20
20
2.1 [14]
-
2.1 [14]
15
15
15
5.3 [10]
-
5.3 [10]
25
25
25
2.1 [14]
-
2.1 [14]
15
15
15
5.3 [10]
-
5.3 [10]
25
25
25
3.3 [12]
-
3.3 [12]
20
20
20
5.3 [10]
-
5.3 [10]
25
25
25
5.3 [10]
-
5.3 [10]
25
25
25
5.3 [10]
-
5.3 [10]
30
30
30
5.3 [10]
-
5.3 [10]
25
25
25
5.3 [10]
-
5.3 [10]
30
30
30
5.3 [10]
-
5.3 [10]
30
30
30
5.3 [10]
-
5.3 [10]
25
25
25
5.3 [10]
-
5.3 [10]
25
25
25
2.1 [14]
-
2.1 [14]
15
15
15
5.3 [10]
-
5.3 [10]
25
25
25
5.3 [10]
-
5.3 [10]
25
25
25
3.3 [12]
-
3.3 [12]
20
20
20
5.3 [10]
-
5.3 [10]
30
30
30
5.3 [10]
-
5.3 [10]
25
25
25
3.3 [12]
-
3.3 [12]
20
20
20
Breaker for
wiring (NFB)(A)
Recommended setting
MCA
(A)
MOCP
(A)