Connecting the on-site piping and the service valve piping
When routing the pipes through the front of the unit
Liquid side
Gas side
EP200
Use the supplied connecting pipe
①
.
Expand the end of the on-site piping. (ID ø9.52 mm (ø3/8 in)) Use the supplied connecting elbow
⑤
and connecting
pipe
⑥
.
EP250
*1
*2
Use the supplied connecting pipes
①
and
⑧
.
Expand the end of the on-site piping. (ID ø12.7 mm (ø1/2 in))
EP300
*3
Use the supplied connecting pipes
②
and
⑨
.
Expand the end of the on-site piping. (ID ø9.52 mm (ø3/8 in))
Use the supplied connecting elbow
⑤
and connecting
pipe
④
.
*4
Use the supplied connecting pipe
②
.
Expand the end of the on-site piping. (ID ø12.7 mm (ø1/2 in))
EP350
EP400
EP450
Use the supplied connecting pipe
③
.
EP500
When routing the pipes through the bottom of the unit
Liquid side
Gas side
EP200
Sever the supplied connecting pipe
①
as shown in the figure below with
a pipe cutter.
Expand the end of the on-site piping. (ID ø9.52 mm (ø3/8 in))
Use the supplied connecting pipe
⑦
.
Expand the end of the on-site piping. (ID
ø22.2 mm (ø7/8 in))
EP250
*1
*2
Sever the supplied connecting pipe
①
as shown in the figure below with
a pipe cutter, and connect it to connecting pipe
⑧
.
Expand the end of the on-site piping. (ID ø12.7 mm (ø1/2 in))
EP300
*3
Sever the supplied connecting pipe
②
as shown in the figure below with
a pipe cutter, and connect it to connecting pipe
⑨
.
Expand the end of the on-site piping. (ID ø9.52 mm (ø3/8 in))
Expand the end of the on-site piping. (ID
ø28.58 mm (ø1-1/8 in))
*4
Sever the supplied connecting pipe
②
as shown in the figure below with
a pipe cutter.
Expand the end of the on-site piping. (ID ø12.7 mm (ø1/2 in))
EP350
EP400
EP450
Sever the supplied connecting pipe
③
as shown in the figure below with
a pipe cutter.
Expand the end of the on-site piping. (ID ø15.88 mm (ø5/8 in))
EP500
<Reference> Size of refrigerant pipes
On-site piping [mm (in)]
Service valve piping [mm (in)]
Liquid
Gas
Liquid
Gas
EP200
ø9.52 (ø3/8)
ø22.2 (ø7/8)
ø9.52 (ø3/8)
ø28.58 (ø1-1/8)
EP250
*1
ø9.52 (ø3/8)
*2
ø12.7 (ø1/2)
EP300
*3
ø9.52 (ø3/8)
ø28.58 (ø1-1/8)
ø12.7 (ø1/2)
*4
ø12.7 (ø1/2)
EP350
ø12.7 (ø1/2)
EP400
ø12.7 (ø1/2)
ø15.88 (ø5/8)
EP450
ø15.88 (ø5/8)
EP500
ø15.88 (ø5/8)
*1 When the piping length from the outdoor unit to the farthest indoor unit is less than 90 m (295 ft)
*2 When the piping length from the outdoor unit to the farthest indoor unit is 90 m (295 ft) or more
*3 When the piping length from the outdoor unit to the farthest indoor unit is less than 40 m (131 ft)
*4 When the piping length from the outdoor unit to the farthest indoor unit is 40 m (131 ft) or more.
<Reference> Severed section
[mm (in)]
Ⓐ
Ⓐ
Ⓐ
Ⓑ
Ⓑ
Ⓑ
Ⓐ
Pipe section to be cut (Use a pipe cutter.)
Ⓑ
Service valve side
20 (26/32)
18 (23/32)
25 (1)
Connecting pipe
①
Connecting pipe
②
Connecting pipe